Air conditioner Installation manual AC777KX4D7H ŷ Thank you for purchasing this Samsung air conditioner. ŷ Before operating this unit, please read this manual carefully and retain it for future reference.
Contents Safety Information 3 General information 3 Installing the unit 4 Power supply line, fuse or circuit breaker 4 Installation Procedure 5 Step 1 Choosing the installation location 5 Step 2 Fixing the outdoor unit in place 7 Step 3 Connecting the power cables, communication cable, and controllers 8 Step 4 Optional: Extending the power cable 14 Step 5 Connecting the refrigerant pipe 16 Step 6 Optional: Cutting and flaring the pipes 17 Step 7 Installing oil traps 18 Step 8 Connect
Safety Information WARNING ŷ Hazards or unsafe practices that may result in severe personal injury or death. ŷ Hazards or unsafe practices that may result in minor personal injury or property damage. Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.
Safety Information Safety Information ŷ This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Installation Procedure Step 1 Choosing the installation location Installation location requirements ŷ Do not place the outdoor unit on its side or upside down. Failing to do so may cause the compressor lubrication oil to run into the cooling circuit and lead to a serious damage to the unit. ŷ Install the unit in a well-ventilated location away from direct sunlight or strong winds. ŷ Install the unit in a location that would not obstruct any passageways or thoroughfares.
Installation Procedure ŷ Install the unit in a place where water can drain smoothly. Minimum clearances for the outdoor unit When installing 1 outdoor unit (Unit: mm) 300 or more ŷ Be sure to clean the sea water and the dust on the heat exchanger of the outdoor unit and apply a corrosion inhibitor on it. (At least once in a year.) 1500 or more ŷ If you have any difficulty finding installation location as prescribed above, contact your manufacturer for details.
500 or more 500 or more 300 or more Wire rope Plate protection cloth 300 or more Step 2 Fixing the outdoor unit in place ŷ The outdoor unit must be installed according to the specified distances in order to permit accessibility from each side, to guarantee correct operation, maintenance, and repair of the unit. The components of the outdoor unit must be reachable and removable under safe conditions for people and the unit.
Installation Procedure CAUTION ŷ Install a drain outlet at the lowest end around the base for outdoor unit drainage ŷ When installing the outdoor unit on the roof, waterproof the unit and check the ceiling strength. Step 3 Connecting the power cables, communication cable, and controllers You must connect the following three electrical cables to the outdoor unit: ŷ The main power cable between the auxiliary circuit breaker and the outdoor unit.
When using earth leakage circuit breaker (ELCB) for a 3-phase, 4-wire system (3P4W) Main power cable Communication cable Outdoor-to-indoor power cable MCCB CAUTION ŷ If the outdoor unit is installed in a location vulnerable to an electric leak or submergence, make sure to install an ELCB.
Installation Procedure ŷ To protect the product from water and possible shock, you should keep the power cable and the connection cord of the indoor and outdoor units within ducts. (with appropriate IP rating and material selection for your application) CAUTION ŷ You should connect the power cable into the power cable terminal and fasten it with a clamp. ŷ The unbalanced power must be maintained within 2% of supply rating.
3-phase Model Outdoor unit Type Rated Indoor unit Input current (Amperes) Voltage range Outdoor unit Outdoor unit Power supply Indoor Total unit Hz Volts Min. Max. Cooling Heating AC100KN4DKH/EU AC100KX4DNH/EU 50 380 to 415 342 456.5 16.1 16.1 1.5 AC120KN4DKH/EU AC120KX4DNH/EU 50 380 to 415 342 456.5 16.1 16.1 1.5 AC140KN4DKH/EU AC140KX4DNH/EU 50 380 to 415 342 456.5 16.1 16.1 1.5 MCA MFA 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.6 17.
Installation Procedure Connecting the outdoor-to-indoor power cable and the communication cable 1-phase NOTE ŷ Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely. ŷ Ground wire for the indoor unit and outdoor unit connection cable must be clamped to a soft copper tin-plated eyelet terminal with M4 screw hole(NOT SUPPLIED WITH UNIT ACCESSORIES).
B Nominal dimensions for cable (mm²) Nominal dimensions for screw (mm) D Standard Standard Allowance dimension dimension (mm) (mm) (mm) 4 9.5 8 15 10 8 15 ±0.2 16 8 16 4/6 50 70 12 16.5 8 16 8 22 8 22 8 24 L d2 t Standard Allowance dimension (mm) (mm) Min. (mm) Min. (mm) Max. (mm) Standard Allowance dimension (mm) (mm) Min. (mm) 5 20 4.3 +0.2 0 9 28.5 8.4 +0.4 0 3.4 7.1 +0.3 -0.2 4.5 ±0.2 7.9 9 30 8.4 +0.4 0 1.15 ±0.2 9 +0.3 -0.2 5.8 ±0.2 9.
Installation Procedure Outdoor-to-indoor power and communication cables specifications CAUTION ŷ For information about the power cable specifications for indoor and outdoor units, refer to the installation manual. Indoor power supply Power supply Max/Min (V) Indoor power cable 1ĭ, 220-240V, 50 Hz ±10% 2.5 mm² Ĺ, 3 wires ŷ After peeling off cable wires from the pre-installed tube, insert a contraction tube Power cable Communication cable 0.75 to 1.
ŷ After compressing it, pull both sides of the wire to make sure it is firmly pressed. Method 1 CAUTION ŷ Make sure that the connection parts are not exposed to outside. Method 2 Compress it 4 times. Compress it 4 times. 5 mm 5 mm 5 Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape.
Installation Procedure Step 5 Connecting the refrigerant pipe Items Maximum allowable length Installation Procedure Outdoor unit models AC071KX4DKH AC090KX4DKH AC100KX4DKH AC100KX4DNH AC120KX4DKH AC120KX4DNH AC140KX4DKH AC140KX4DNH Main pipe (L1) 50 m 75 m Max. height difference between outdoor and indoor units (h1) 30 m 30 m n=1 L1 h1 Outdoor ŷ Temper grade and minimum thickness of the refrigerant pipe Minimum thickness [mm] ø6.35 0.7 ø9.52 0.7 ø12.70 0.8 ø15.88 1.0 ø15.88 0.
CAUTION ŷ After connecting the pipes with knock-out treatment, plug the space around the pipes. ŷ After connecting the pipes, proceed exactly as directed in the guide to prevent interference with the internal parts. Step 6 Optional: Cutting and flaring the pipes Outer diameter (D) Depth (A) Flare dimension (L) ø6.35 mm 14 to 18 8.7 to 9.1 mm ø9.52 mm 34 to 42 12.8 to 13.2 mm ø12.70 mm 49 to 61 16.2 to 16.6 mm ø15.88 mm 68 to 82 19.3 to 19.7 mm ø19.05 mm 100 to 120 23.6 to 24.
Installation Procedure Step 7 Installing oil traps Check the following list and install an oil trap. ŷ Based on cooling operation, install it on the gas side pipe only. ŷ Install the oil trap only in between the outdoor unit and the first branch joint and it should be installed at every 10 m. ŷ Radius of curvature (R) on the oil trap are as follows; Pipe diameter (D) 12.70 15.88 19.05 22.23 25.40 28.60 31.
4 Open the valve of the low pressure side(A) of manifold gauge anticlockwise. CAUTION ŷ Connect the indoor and outdoor units using pipes with flared connections (not supplied). For the lines, use insulated, unwelded, degreased and deoxidized copper pipe, (Cu DHP type to ISO 1337 or UNI EN 12735-1), suitable for operating pressures of at least 4200 kPa and for a burst pressure of at least 20700 kPa. Copper pipe for hydro-sanitary applications is completely unsuitable.
Installation Procedure Indoor Unit Liquid side stop valve(service port) Gas side stop valve(service port) Outdoor Unit Indoor Unit Outdoor Unit Balance 2 Ref 1 Vacuum pump Installation Procedure Important information regulation regarding the refrigerant used Unit kg tCO2e ,a This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere. ,b + ,c CAUTION ŷ Inform user if system contains 5 tCO2e or more of fluorinated greenhouse gases.
When installing the outdoor unit only Interconnection pipe length (m) Model AC071KX4DKH 0 to 30 30 to 40 40 to 50 50 to 60 60 to 70 70 to 75 +20 g/m over 5m AC090KX4DKH +50 g/m over 30 m AC100KX4DKH +50 g/m over 30 m AC100KX4DNH +50 g/m over 30 m +50 g/m over 30 m AC120KX4DNH +50 g/m over 30 m AC140KX4DKH '+50 g/m over 30 m AC140KX4DNH '+50 g/m over 30 m Step 10 Performing the gas leak test LEAK TEST WITH NITROGEN (before opening valves) In order to detect basic refrigerant leaks, befor
Installation Procedure 4 Ensure that the drained water runs off correctly and safely. Step 12 Insulating the refrigerant pipes Once you have checked that there are no leaks in the system, you can insulate the piping and hose. 1 To avoid condensation problems, place an insulator around each refrigerant pipe. No gap 80 mm 13 mm Installation Procedure 5 Be sure to plug the rest of drain holes not connected with drain plugs using drain caps.
Insulation Type (Heating/Cooling) Standard Pipe Pipe size [Less than 30°C, 85%] High humidity NOTE Remarks [over 30°C, 85%] ŷ The earthing wire for the telephone line cannot be used to ground the air conditioner. Carbon plastic EPDM, NBR Liquid pipe Gas pipe Ø6.35~Ø9.52 9t 9t Ø12.7~Ø19.05 13 t 13 t Ø6.35 13 t 19 t Ø9.52~Ø19.
Installation Procedure 2 Check the indoor unit. a Check that you have connected the power and communication cables correctly. (If the power cable and communication cables one mixed up or connected incorrectly, the PCB will be damaged.) b Check that the thermistor sensor, drain pump/ hose, and display are connected correctly. 3 Press K1 or K2 on the outdoor unit PCB to run the test mode and stop.
K4 short push SEG1 SEG2 SEG3 SEG4 Unit 1 Order frequency 1 Hundreds digit Tens digit Units digit Hz 2 Current frequency 2 Hundreds digit Tens digit Units digit Hz 3 The number of current indoor units 3 Hundreds digit Tens digit Units digit EA 4 The sensor for outdoor air intake 4 +/- Tens digit Units digit °C 5 Discharge sensor 5 Hundreds digit Tens digit Units digit °C 6 Eva-Mid sensor 6 +/- Tens digit Units digit °C 7 Cond sensor 7 +/- Tens digit Units
Installation Procedure 7 DIP switch option ON 1 ON 2 3 4 1 2 SW507 3 On (default) Off Switch 1 Auto Silence mode Manual Silence mode Switch 2 - - Switch 3 - - Switch 4 - - 4 SW508 8 Silence Mode DIP switch option ŷ DIP switch (SW507) option ŷ DIP switch (SW507) option Switch 3 Switch 4 Operation Installation Procedure On (default) Off On On Disable Silence mode Switch 1 Auto address (high level controller) Manual address (*1) (high level controller) On Off Silenc
Extra Procedures Pumping down refrigerant Pump down will be carried out when an evaporator is replaced or when the unit is relocated in another area. 1 Remove the cap from the low pressure side. 5 Disconnect the pipes connected to the outdoor units. At this time, cover the valve of the outdoor units and the other pipes using a cap or vinyl plug to avoid foreign material entering. Note: Make sure you do not bend the connection pipes in the middle and store together with the cables.
Extra Procedures NOTE ŷ Do not apply excessive force to the stop valve and always use special instruments. Otherwise, the stopping box can be damaged and the back sheet can leaks. ŷ If the watertight sheet leaks, turn the axis back by half, tighten the stopping box, then check the leakage again. If there is no leakage any more, tighten the axis entirely. Closing the stop valve 1 Remove the cap. 2 Turn the stop valve clockwise by using a hexagonal wrench.
Appendix Troubleshooting The table below list the self-diagnostic routines. For some of error codes, you must contact an authorized service centre. If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB. No.
Appendix No. Error Code Meaning Remarks 1. Check if the service valve is open 18 E422 Blockage detected on high pressure pipe 2. Check for refrigerant leakage (pipe connections, heat exchanger) and charge refrigerant if necessary 3. Check if there's any blockage on the refrigerant cycle (indoor unit/outdoor unit) 4. Check if additional refrigerant has been added after pipe extension Appendix 19 E425 Reverse phase or open phase Check whether 3 phase is reversed or opened.
Technical specifications Model Net weight Net dimension (W × D × H) AC071KX4DKH/EU 50.5 kg 880 mm × 310 mm × 798 mm AC090KX4DKH/EU 72.0 kg 940 mm × 330 mm × 998 mm AC100KX4DKH/EU 72.0 kg 940 mm × 330 mm × 998 mm AC100KX4DNH/EU 72.0 kg 940 mm × 330 mm × 998 mm AC120KX4DKH/EU 80.0 kg 940 mm × 330 mm × 998 mm AC120KX4DNH/EU 80.0 kg 940 mm × 330 mm × 998 mm AC140KX4DKH/EU 90.0 kg 940 mm × 330 mm × 1210 mm AC140KX4DNH/EU 90.
Appendix COMMISSION DELEGATED REGULATION (EU) No 626/2011i) PRODUCT FICHE (ENERGY LABELLING OF AIR CONDITIONERS)ii) A Supplier's name - Samsung Electronics Co.. Ltd. AC071KN4DKH / AC071KX4DKH AC090KN4DKH / AC090KX4DKH AC100KN4DKH / AC100KX4DKH B Model name (Indoor/Outdoor) - C Sound Power Level (Indoor/Outdoor) dB(A) 53 / 65 60 / 68 61 / 69 D Refrigerant name1) - R-410A R-410A R-410A E GWP - 2088 2088 2088 F SEER 6.2 6.8 6.
COMMISSION DELEGATED REGULATION (EU) No 626/2011i) PRODUCT FICHE (ENERGY LABELLING OF AIR CONDITIONERS)ii) A Supplier's name - Samsung Electronics Co.. Ltd. AC100KN4DKH / AC100KX4DNH AC120KN4DKH / AC120KX4DKH AC120KN4DKH / AC120KX4DNH B Model name (Indoor/Outdoor) - C Sound Power Level (Indoor/Outdoor) dB(A) 61 / 69 61 / 70 61 / 70 D Refrigerant name1) - R-410A R-410A R-410A E GWP - 2088 2088 2088 F SEER 6.8 5.7 5.
Appendix [Spanish-ES] [French-FR] [Italian-IT] [Portuguese-PT] i REGLAMENTO DELEGADO (UE) No 626/2011 DE LA COMISIÓN RÈGLEMENT DÉLÉGUÉ (UE) No 626/2011 DE LA COMMISSION REGOLAMENTO DELEGATO (UE) N. 626/2011 DELLA COMMISSIONE REGULAMENTO DELEGADO (UE) N.
[German-DE] [Greek-EL] [Dutch-NL] [Polish-PL] i DELEGIERTE VERORDNUNG (EU) Nr. 626/2011 DER KOMMISSION Ȁǹȉ¶ ǼȄȅȊȈǿȅǻǵȉǾȈǾ ȀǹȃȅȃǿȈȂǵȈ ǼǼ ĮȡȚș ȉǾȈ ǼȆǿȉȇȅȆdzȈ GEDELEGEERDE VERORDENING (EU) VAN DE COMMISSIE Nr.
Appendix [Hungarian-HU] [Czech-CS] [Slovak-SK] [Romanian-RO] i A BIZOTTSÁG 626/2011/ EU FELHATALMAZÁSON ALAPULÓ RENDELETE NAŘÍZENÍ KOMISE V PŘENESENÉ PRAVOMOCI (EU) č. 626/2011 DELEGOVANÉ NARIADENIE KOMISIE (EÚ) č. 626/2011 REGULAMENT DELEGAT (UE) NR.
[Bulgarian-BG] [Croatian-HR] [Slovenian-SL] [Danish-DA] i ȾȿɅȿȽɂɊȺɇ ɊȿȽɅȺɆȿɇɌ ȿɋ ʋ ɇȺ ɄɈɆɂɋɂəɌȺ DELEGIRANA UREDBA KOMISIJE (EU) br. 626/2011 DELEGIRANA UREDBA KOMISIJE (EU) št. 626/2011 KOMMISSIONENS DELEGEREDE FORORDNING (EU) Nr.
Appendix [Swedish-SV] [Finnish-FI] [Estonian-ET] [Latvian-LV] i KOMMISSIONENS DELEGERADE FÖRORDNING (EU) nr 626/2011 DELEGOITU KOMISSION ASETUS (EU) N:o 626/2011, KOMISJONI DELEGEERITUD MÄÄRUS (EL) nr 626/2011, KOMISIJAS DELEĢĒTĀ REGULA (ES) Nr.
[Lithuanian-LT] [Serbian-SR] i KOMISIJOS DELEGUOTASIS REGLAMENTAS (ES) Nr.
Appendix [Spanish-ES] 1 Las fugas de refrigerante contribuyen al cambio climático. Cuanto mayor sea el potencial de calentamiento global (GWP) de un refrigerante, más contribuirá a dicho calentamiento su vertido a la atmósfera. Este aparato contiene un líquido refrigerante con un GWP igual a [2088].
[Portuguese-PT] 1 A fuga de fluido refrigerante contribui para as alterações climáticas. Os fluidos refrigerantes com menor potencial de aquecimento global (PAG) contribuem menos para o aquecimento global do que os fluidos refrigerantes com maior PAG, em caso de fuga para a atmosfera. Este aparelho contém um fluido refrigerante com um PAG igual a [2088].
Appendix [Polish-PL] 1 Wycieki czynników chłodniczych przyczyniają się do zmiany klimatu. W przypadku przedostania się do atmosfery czynnik chłodniczy o niższym współczynniku ocieplenia globalnego (GWP) ma mniejszy wpływ na globalne ocieplenie niż czynnik o wyższym współczynniku GWP. Urządzenie zawiera płyn chłodniczy o współczynniku GWP wynoszącym [2088].
[Romanian-RO] 1 Scurgerea de agent frigorific contribuie la schimbările climatice. Dacă s-ar scurge în atmosferă, agenții frigorifici cu un potențial de încălzire globală (GWP) mai redus ar contribui într-un mod mai puțin semnificativ la încălzirea globală decât un agent frigorific cu un GWP mai ridicat. Acest aparat conține un fluid refrigerant cu un GWP egal cu [2088].
Appendix [Danish-DA] 1 Kølemiddeludslip medvirker til klimaforandringerne. Slipper kølemidlet ud i atmosfæren, bidrager det mindre til den globale opvarmning, hvis dets potentiale for global opvarmning (GWP) er lavt, end hvis det er højt. Dette apparat indeholder en kølevæske, hvis GWP-tal er [2088]. Det betyder, at lækkes 1 kg af dette kølemiddel til atmosfæren, så vil det gennem en periode på 100 år bidrage [2088] gange mere til den globale opvarmning end 1 kg CO2.
[Latvian-LV] 1 Aukstumaģentu noplūdes veicina klimata pārmaiņas. Aukstumaģenta noplūdes gadījumā ierīces ar zemāku aukstumaģenta globālās sasilšanas potenciālu (GSP) nodara mazāku kaitējumu videi. Šajā ierīcē atrodas dzesēšanas šķidrums, kura globālās sasilšanas potenciāls GSP ir [2088]. Tas nozīmē, ka, ja vidē nokļūst 1 kg šā dzesēšanas šķidruma, ietekme uz globālo sasilšanu 100 gadu laikā ir [2088] reizes lielāka nekā 1 kg CO2.