User manual

21
ENGLISH
f If the terminal is loose, re may occur caused by arc. If the terminal is connected too rmly, the terminal may be
damaged.
5JHIUFOJOH5PSRVFLHGtDN
M3
5.0~7.5 Communication : F1, F2
M4
12.0~18.0 3phase AC power : 1(L), 2(N), L1(R), L2(S), L3(T), N
M5
20.0~30.0 1phase AC power : 1(L), 2(N), L, N
1N · m = 10 kgf · cm
t When connecting cables, you can connect the cables to the electrical part or connect them through the holes
below depending on the spot.
t Run transmission wiring between the indoor and outdoor units through a conduit to protect against
external forces, and feed the conduit through the wall together with rergerant piping.
t Remove all burrs at the edge of the knock-out hole and secure the cable to the outdoor knock-out using lining
and bushing with an electrical insulation such as rubber and so on.
t Must keep the cable in a protection tube.
t Keep distances of 50mm or more between power cable and communication cable.
t When the cables are connected through the hole, remove the Plate bottom.
CAUTION
How to connect your extended power cables
1. Prepare the following tools.
Tools Crimping pliers Connection sleeve (mm) Insulation tape Contraction tube (mm)
Spec MH-14 20xØ6.5(HxOD) Width 19mm 70xØ8.0(LxOD)
Shape
2. As shown in the gure, peel o the shields from the rubber and wire of the
power cable.
- Peel o 20 mm of cable shields from the pre-installed tube.
t For information about the power cable specications for indoor and
outdoor units, refer to the installation manual.
t After peeling o cable wires from the pre-installed tube, insert a
contraction tube.
CAUTION
120
60
202020
180
Power cable
20
Pre-installed tube for the power cable
(Unit: mm)
3. Insert both sides of core wire of the power cable into the connection sleeve.
f Method 1
Push the core wire into the sleeve from both sides.
Connection sleeve
f Method 2
Twist the wire cores together and push it into the sleeve.
Connection sleeve