Important information regulation regarding the refrigerant used
This product contains uorinated greenhouse gases. Hermetically sealed system. Do not vent gases into the atmosphere.
t Inform user if system contains 5 tCOe or more of uorinated greenhouse gases. In this case, it has to be checked
for leakage at least once every 12 months, according to regulation n°517/2014. This activity has to be covered by
qualied personnel only.
t In case situation above (5 tCOe or more of R-410A), installer (or recognised person which has responsability for
nal check) has to provide a maintenance book, with all the information recorded according to REGULATION(EU)
N° 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April 2014 on uorinated greenhouse
gases.
CAUTION
Please ll in the following with indelible ink on the refrigerant charge label
supplied with this product and on this manual.
f ① : The factory refrigerant charge of the product.
f ② : The additional refrigerant amount charged in the eld.
f ①+② The total refrigerant charge.
a. Factory refrigerant charge of the product: see unit name plate
b. Additional refrigerant amount charged in the eld(Refer to the
above information for the quantity of refrigerant replenishment.)
c. Total refrigerant charge
d. Refrigerant cylinder and manifold for charging
NOTE
❋ The lled-out label must be adhered in the proximity of the product charging
port (e.g. onto the inside of the stop valve cover).
Unit kg tCOe
①, a
②, b
①+②, c
Refrigerant type GWP value
R-410A 2088
❋ GWP=Global Warming Potential
❋ Calculating tCOe : kg x GWP /
1000
Indoor unit
Outdoor unit
d
②
①
Pressure table for temperatures
If you need extra refrigerant charging due to leakage or relocating the product, refer to below table before charging
refrigerant.
f AC071JXSCEH/EU
❋ Cooling operation Unit : [kPa, G]
Indoor Temp.(°C)
(Dry-Bulb/Wet Bulb)
Outdoor Temp.(°C)
32/23 27/19 21/15
50 1134 1020 916
35 1040 944 777
21 999 896 802
7 1020 912 808
-18 1008 874 766