Operating instructions
32_ Operating advanced function
Operating advanced function
FIELD SETTING MODE
•Code30:User’soptionsfordomestichotwater(DHW)tankheating
3011:ApplicationofDHWtankinuser’ssystem
302:Heatpumpvariablesfortanktemp.controlandcombinationwithboosterheater
303:Boosterheatervariablesforcombinationwithheatpump
304:Periodicaldisinfectionheatingofwatertank
305:OfftimerforpowerDHWmodebyhotkeyofwiredremotecontroller
3061:CombinationofexternalfieldsolarpanelforwithheatpumpforDHWheating
307:DefaultdirectionoftheDHWvalveorZone#1,#2valve
When the 3way valve is applied to DHW Valve terminal block instead of 2way valve,
default direction is Space Heating (Room)
FieldSettingValue
Main Menu
& Code
Sub Menu Function Description Sub Code Default Min Max Step Unit
DHW Code
30
Domestic Hot Water Tank Application
11 0(No) 0 1(Yes) - -
Heat Pump Max Temp
21 50 45 55 1 ˚C
Stop
22 2 2 10 1 ˚C
Start
23 5 1 20 1 ˚C
Min. Space heating
operation time
24 5 0 20 1 min
Max. DHW operation
time
25 30 5 95 5 min
Max. Space heating
operation time
26 3 0 10 0.5 hour
Booster Heater Application
31 1(On) 0(OFF) 1 - -
Delay Time
32 20 20 95 5 min
Overshoot
33 0 0 4 1 ˚C
Compensation Temp
34 10 0 20 1 ˚C
Disinfection Application
41 1(On) 0(OFF) 1 - -
Interval
42 Fri Mon Sun 1(All) day
Start Time
43 23 0 23 1 o'clock
Target Temp
44 70 40 70 5 ˚C
Duration
45 10 5 60 5 min
Power DHW by User Input Timer OFF Function
51 0(Off) 0 1(On) - -
Timer Duration
52 60 30 300 10 min
Solar Panel H/P Combination
61 0 0 1(Yes) - -
Direction of DHW valve DHW Tank
71 0(Room) 0 1(Tank) - -