Operating instructions
34_ Operating advanced function
Operating advanced function
FIELD SETTING MODE
Remote Controller Setting Range : Code 10
Space Cooling
• Targetwateroutlettemperature:Upperlimit(#1011,Default25ºC,Range:18~25ºC),
Lowerlimit(#1012,Default16ºC,Range:5~18ºC)
- With this default FSV settings, user can change the target water outlet temperature within
therangeof5~25ºCforcooling
• Targetroomtemperature:Upperlimit(#1021,Default30ºC,Range:24~30ºC),
Lowerlimit(#1022,Default18ºC,Range:18~22ºC)
- With this default FSV settings, user can change the target room temperature within the
rangeof18~30ºCforcooling.
•The#1DIPswitchinthewiredremotecontrollershouldbesetto“OFF”(Default)for
cooling operation of heat pump.
•The#2DIPswitchinthewiredremotecontrollershouldbesetto“OFF”(Default)to
control the water outlet temperature.
•The#2DIPswitchinthewiredremotecontrollershouldbesetto“ON”tocontrolthe
room temperature.
Space Heating
• Targetwateroutlettemperature:Upperlimit(#1031,Default55ºC,Range:37~55ºC),
Lowerlimit(#1032,Default25ºC,Range:15~37ºC)
- With this default FSV settings, user can change the target water outlet temperature within
therangeof25~55ºCforheating.
• Targetroomtemperature:Upperlimit(#1041,Default30ºC,Range:24~30ºC),
Lowerlimit(#1042,Default16ºC,Range:16~22ºC)
- With this default FSV settings, user can change the target room temperature within the
rangeof16~30ºCforheating.
•The#2DIPswitchinthewiredremotecontrollershouldbesetto“OFF”(Default)to
control the water outlet temperature.
•The#2DIPswitchinthewiredremotecontrollershouldbesetto“ON”tocontrolthe
room temperature.
DHW Heating
• TargetDHWtanktemperature:Upperlimit(#1051,Default50ºC,Range:50~70ºC),
Lowerlimit(#1052,Default40ºC,Range:30~40ºC)
- With this default FSV settings, user can change the target tank temperature within the
rangeof40~50ºCforDHWheating.
TheFSV#3011inthewiredremotecontrollershouldbesetto“1(Yes)”touseDHW
function.
Back Light
• Remotecontroller’sbacklighttimer:#1061,Default5sec,Range:0~30sec
-
WiththisFSVsettings,usercanchangethetimetobacklightwithintherangeof0~30sec.
FieldSettingValue
Main Menu & Code Sub Menu Function Description Sub Code Default Min Max Step Unit
Remote Controller
Setting Range
Code 10
Water Out Temp for Cooling Max 11 25 18 25 1 ˚C
Min 12 16 5 18 1 ˚C
Room Temp for Cooling Max 21 30 24 30 1 ˚C
Min 22 18 18 22 1 ˚C
Water Out Temp for Heating Max 31 55 37 55 1 ˚C
Min 32 25 15 37 1 ˚C
Room Temp for heating Max 41 30 24 30 1 ˚C
Min 42 16 16 22 1 ˚C
DHW Tank Temp Max 51 50 50 70 1 ˚C
Min 52 40 30 40 1 ˚C
Back light timer Time 61 5 0 30 1 sec