Operating instructions
38_ Operating advanced function
DHW Application
TheFSV#3011inthewiredremotecontrollershouldbesetto“1(Yes)”touseDHWfunction.
Heat Pump Variables for Controlling DHW Tank
• MaximumDHWtanktemperaturewithR410A(refrigerant)heatpumpoperation:
FSV#3021,Default50˚C,Range:45~55˚C.
• TemperaturedifferencedeterminingtheheatpumpOFFtemperature:
FSV#3022,Default2˚C,Range:2~10˚C.
• TemperaturedifferencedeterminingtheheatpumpONtemperature:
FSV#3023,Default5˚C,Range:1~20˚C.
• DHWheatingmodetimer:Modetimermanagetheoperationtermswhenthereare
simultaneous requests of space heating/cooling and DHW.
-FSV#3024(minimumSpaceheatingoperatingtime,Default5min.,Range0~20min.),
#3025(maximumDHWtime,Default30min.,Range5~95min.),#3026(maximumspace
heatingoperationtime,Default3hour,Range0~10hour)
- Maximum operation time is applied only when both DHW and Space heating request
operation. DHW or Space heating operates continuously until reaching at target
temperature without time limitation in the single operation.
TheFSV#4011forDHWpriorityshouldbesetto“0(DHW)”(Default).Spaceheatinggets
aprioritybysettingFSV#4011“1”,butthisisonlyvalidwhentheoutdoortemperatureis
lower than the specified temperature defined by FSV #4012.
Operating advanced function
FIELD SETTING MODE
FieldSettingValue
Main Menu
& Code
Sub Menu Function Description
Sub
Code
Default Min Max Step Unit
DHW Code
30
Domestic Hot Water Tank
Application
11 0(No) 0 1(Yes) - -
Heat Pump
Max Temp
21 50 45 55 1 ˚C
Stop
22 2 2 10 1 ˚C
Start
23 5 1 20 1 ˚C
Min. Space heating
operation time
24 5 0 20 1 min
Max. DHW operation time
25 30 5 95 5 min
Max. Space heating
operation time
26 3 0 10 0.5 hour
Booster Heater
Application
31 1(On) 0(OFF) 1 - -
Delay Time
32 20 20 95 5 min
Overshoot
33 0 0 4 1 ˚C
Compensation Temp
34 10 0 20 1 ˚C
Disinfection
Application
41 1(On) 0(OFF) 1 - -
Interval
42 Fri Mon Sun 1(All) day
Start Time
43 23 0 23 1 o'clock
Target Temp
44 70 40 70 5 ˚C
Duration
45 10 5 60 5 min
Power DHW by User Input
Timer OFF Function
51 0(Off) 0 1(On) - -
Timer Duration
52 60 30 300 10 min
Solar Panel
H/P Combination
61 0 0 1(Yes) - -
Direction of DHW valve
DHW Tank
71 0(Room) 0 1(Tank) - -