Operating instructions

44_ Operating advanced function
Operating advanced function
FIELD SETTING MODE
Others : Code 50
Outing Mode (Hot Key of Wired Remote Controller)
• All the target temperatures – space heating and cooling, water law, DHW, Room
temperature – are set to the values defined in the above table under the holiday mode
(outing hot key)
Withtheloweredtargettemperatures(FSV#5011~#5019),thesystemoperates
normally.
Economic DHW Heating
• DHW heating only by the heat pump to save energy. Target DHW temperature is lower than
thetemperaturesetbyuser.ThetemperaturedifferenceisdefinedbyFSV#5021.(default:
5°C)
 - If user sets the temperature 45°C, the system sets the target temperature 40°C with the
default setting.
FieldSettingValue
Main Menu &
Code
Sub Menu Function Description Sub Code Default Min Max Step Unit
Others Code
50

Outing Water Out Temp for Cooling

11 25 5 25 1 ˚C
Room Temp for Cooling

12 30 18 30 1 ˚C
Water Out Temp for Heating

13 25 15 55 1 ˚C
Room Temp for Heating

14 16 16 30 1 ˚C
Auto Cooling WL1 Temp

15 25 5 25 1 ˚C
Auto Cooling WL2 Temp

16 25 5 25 1 ˚C
Auto Heating WL1 Temp

17 15 15 55 1 ˚C
Auto Heating WL2 Temp

18 15 15 55 1 ˚C
Target Tank Temp

19 30 30 70 1 ˚C
DHW Saving Mode Temp Difference

21 5 0 40 1 ˚C
Power Peak
Control
Application

41 0(No) 0 1(Yes) - -
Select forced off parts

42 0 0 2 - -
Using input voltage

43 1(High) 0(Low) 1 - -