Peak Power Control
• If users make contracts with local electric power company for limiting the amount of power
consumptionwhenasurgeinpowerusage,userscansetFSVof“Forcedoff”.
• According to FSV (#5041), Default is Non-usage. And According to FSV (#5042), If input is
“0(default)”,allthethermalapplicationsareunavailablewhileexternalcontactsishigh.
Ifinputis“1”,Onlytheboosterheaterisavailable.
Ifinputis“2”,Onlythebackupheaterisavailable.
• Applying the control when power voltage of input contact is high is default. According to
FSV (#5043), it is available to adopt this logic in low condition exceptionally.
• Whenapplyingtothislogic,SAMSUNGcontrollercometoget“Thermooff”conditionforall
operation.
• If not used for a long time, anti-freeze fluid shall be used for preventing damage to the unit in
cold condition.