Field Setting Value (FSV) Table
Reset the power after changing the Field Setting Value.
•Code10:Upperandlowertemperaturelimitsofeachoperationmodeofwiredremotecontroller
Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)
•Code20:WaterlawdesignandexternalroomthermostatHeating(2WL’sforfloor&FCU),
Cooling(2 WL’s for floor & FCU), WL & Thermostat types
FieldSettingValue
Main Menu &
Code
Sub Menu Function Description Sub Code Default Min Max Step Unit
Remote
Controller
Setting Range
Code 10
Water Out Temp for Cooling
Max 11
25 18 25 1 ˚C
Min 12
16 5 18 1 ˚C
Room Temp for Cooling
Max 21
30 24 30 1 ˚C
Min 22
18 18 22 1 ˚C
Water Out Temp for Heating
Max 31
55 37 55 1 ˚C
Min 32
25 15 37 1 ˚C
Room Temp for heating
Max 41
30 24 30 1 ˚C
Min 42
16 16 22 1 ˚C
DHW Tank Temp
Max 51
50 50 70 1 ˚C
Min 52
40 30 40 1 ˚C
Back light timer
Time 61
5 0 30 1 sec
Water Law
Code 20
Outdoor Temp for Water Law
(Heating)
Point
11
-10 -20 5 1 ˚C
Point
12
15 10 20 1 ˚C
Water Out Temp for WL1
Heating (WL1-Floor)
Point
21
40 17 55 1 ˚C
Point
22
25 17 55 1 ˚C
Water Out Temp for WL2
Heating (WL2-Fan Coil Unit)
Point
31
50 17 55 1 ˚C
Point
32
35 17 55 1 ˚C
Heating Water Law for Auto
Mode
WL Type 41
1(WL1) 1 2 - -
Outdoor Temp for Water Law
(Cooling)
Point
51
30 25 35 1 ˚C
Point
52 40
35 45 1 ˚C
Water Out Temp for WL1
Cooling (WL1-Floor)
Point
61 25
18 25 1 ˚C
Point
62 18
5 18 1 ˚C
Water Out Temp for WL2
Cooling (WL2-Fan Coil Unit)
Point
71 18
18 25 1 ˚C
Point
72 5
5 18 1 ˚C
Cooling Water Law
WL Type 81
1(WL1) 1 2 - -
External Thermostat Application
#1(Floor) 91 0(No)
0 1(Yes) - -
#2(FCU) 92 0(No)
0 1(Yes) - -
•2021and2022valueisinfluencedbyeachother.
becuase 2021 is Max. Value and 2022 is Min Value.
so the 2022 Value can't set over than 2021 Value and the 2021 Value can't set under than 2022 Value.
2031, 2032 is same.