User manual

Operating advanced function _31
ENGLISH
Field Setting Value (FSV) Table
Reset the power after changing the Field Setting Value.
•Code10:Upperandlowertemperaturelimitsofeachoperationmodeofwiredremotecontroller
Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)
•Code20:WaterlawdesignandexternalroomthermostatHeating(2WLsforfloor&FCU),
Cooling(2 WLs for floor & FCU), WL & Thermostat types
FieldSettingValue
Main Menu &
Code
Sub Menu Function Description Sub Code Default Min Max Step Unit
Remote
Controller
Setting Range
Code 10
Water Out Temp for Cooling
Max 11
25 18 25 1 ˚C
Min 12
16 5 18 1 ˚C
Room Temp for Cooling
Max 21
30 24 30 1 ˚C
Min 22
18 18 22 1 ˚C
Water Out Temp for Heating
Max 31
55 37 55 1 ˚C
Min 32
25 15 37 1 ˚C
Room Temp for heating
Max 41
30 24 30 1 ˚C
Min 42
16 16 22 1 ˚C
DHW Tank Temp
Max 51
50 50 70 1 ˚C
Min 52
40 30 40 1 ˚C
Back light timer
Time 61
5 0 30 1 sec
Water Law
Code 20
Outdoor Temp for Water Law
(Heating)
Point
11
-10 -20 5 1 ˚C
Point
12
15 10 20 1 ˚C
Water Out Temp for WL1
Heating (WL1-Floor)
Point
21
40 17 55 1 ˚C
Point
22
25 17 55 1 ˚C
Water Out Temp for WL2
Heating (WL2-Fan Coil Unit)
Point
31
50 17 55 1 ˚C
Point
32
35 17 55 1 ˚C
Heating Water Law for Auto
Mode
WL Type 41
1(WL1) 1 2 - -
Outdoor Temp for Water Law
(Cooling)
Point
51
30 25 35 1 ˚C
Point
52 40
35 45 1 ˚C
Water Out Temp for WL1
Cooling (WL1-Floor)
Point
61 25
18 25 1 ˚C
Point
62 18
5 18 1 ˚C
Water Out Temp for WL2
Cooling (WL2-Fan Coil Unit)
Point
71 18
18 25 1 ˚C
Point
72 5
5 18 1 ˚C
Cooling Water Law
WL Type 81
1(WL1) 1 2 - -
External Thermostat Application
#1(Floor) 91 0(No)
0 1(Yes) - -
#2(FCU) 92 0(No)
0 1(Yes) - -
•2021and2022valueisinfluencedbyeachother.
becuase 2021 is Max. Value and 2022 is Min Value.
so the 2022 Value can't set over than 2021 Value and the 2021 Value can't set under than 2022 Value.
2031, 2032 is same.