User manual

Operating advanced function _33
ENGLISH
• Code 40 : User’s options for heating devices including internal backup heater and external boiler
401 : Space/DHW heating priority and control variables
402 : Backup/Booster heater priority and control variables
403 : Additional backup boiler operating variables
• Code 50
: User’s options for extra functions
501 : New target temperatures of each mode by “Outgoing” hot key of remote controller
5021 : Temperature difference between before & after values in “Economic” DHW mode
504 : Power Peak control for Smart Grid
Field Setting Value
Main Menu &
Code
Sub Menu Function Description Sub Code Default Min Max Step Unit
Heating Code
40

Heat Pump Heating/DHW Priority

11 0(DHW) 0 1(Heating) - -
Outdoor Temp for Priority

12 0 -15 20 1 ˚C
Heating Off

13 35 14 35 1 ˚C
Overshoot

14 2 1 4 1 ˚C
Backup Heater Application

21 0(No) 0 1(Yes) - -
BUH/BSH Priority

22 0(Both) 0 2(BSH) 1 -
Cold weather compensation

23 1(Yes) 0(No) 1 - -
Threshold Temp

24 0 -15 35 1 ˚C
Defrost Backup Temp.

25 15 10 55 5 ˚C
Backup Boiler Application

31 0(No) 0 1(Yes) - -
Boiler Priority

32 0(No) 0 1(Yes) - -
Threshold Temp

33 -15 -20 5 1 ˚C
Others Code
50

Outing Water Out Temp for Cooling

11 25 5 25 1 ˚C
Room Temp for Cooling

12 30 18 30 1 ˚C
Water Out Temp for Heating

13 15 15 55 1 ˚C
Room Temp for Heating

14 16 16 30 1 ˚C
Auto Cooling WL1 Temp

15 25 5 25 1 ˚C
Auto Cooling WL2 Temp

16 25 5 25 1 ˚C
Auto Heating WL1 Temp

17 15 15 55 1 ˚C
Auto Heating WL2 Temp

18 15 15 55 1 ˚C
Target Tank Temp

19 30 30 70 1 ˚C
DHW Saving Mode Temp Difference

21 5 0 40 1 ˚C
Power Peak
Control
Application

41 0(No) 0 1(Yes) - -
Select forced off parts

42 0(All) 0 2 1 -
Using input voltage

43 1(High) 0(Low) 1 - -
Frequency Ratio Control

51 0(No)
30 150 10
%
• Code 5042
[D-00] Compressor Back up heater Booster heater
0 (Default) Forced off Forced off Forced off
1 Forced off Forced off Permitted
2 Permitted Forced off Forced off