Performing leak test
Use leak tester or soapsuds on the pipe connection part after performing vacuum pump.
Check for
leakage
Check for
leakage
Test part for indoor unit
Test part for outdoor unit
Before inspecting the leakage, use a torque wrench to close the cap for the service valve.(Comply with a tightening
torque for each size of the diameter, and tighten the cap firmly to prevent any leakage.)
To check for any possible leakage, insert inert gas into the pipes connected to indoor/outdoor units and check the
connection part of the indoor/outdoor units with soap lather or liquid for leakage test.
Tightening torque for charging port cap
(Refer to the table)
Tightening torque for body cap
(Refer to the table)
R-22: Diameter of the screw - 7/16-20UNF
R-410A: Diameter of the screw - 1/2-20UNF
Charging
core
Spindle
Outer
Diameter
(mm)
Tightening torque
Body cap
(N•m)
Charging port cap
(N•m)
Ø6.35 20 ~ 25
10 ~ 12
Ø9.52 20 ~ 25
Ø12.7 25 ~ 30
Ø15.88 30 ~ 35
Ø19.05 35 ~ 40
1N•m=10kgf•cm