DVM E-D/B(cover)-E<03759 3/21/02 6:48 PM Page 1 S A M S U N G DVM Air Conditioner S A M S U N G D V MT M Air Conditioner Technical Manual SAMSUNG ELECTRONICS
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM I Page 2 I Control Overview system 1. DVM system series 1. Remote controller 1-1. What is DVM? 1-2. Features of DVM 1-3. DVM vs VAV 1-1. Wireless remote controller 1-2. Wired remote controller 1-3. Centralized controller 1-4. Function controller 6 7 12 2. DVM line-up 2-1. Numbering system of model 2-2. Combination I I Indoor 14 20 unit 1. Features 2 4 6 6 2. Receiver & display unit (Duct type) 2-1. Concealed type 2-2. Standard type 4.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 3 I V Outdoor V Installation unit 6. Refrigerant system diagram (Cooling only & heat pump) 6-1. Refrigerant system diagram 6-2. Main parts status 73 73 7. Electric circuit diagram 7-1. 1-way cassette type 7-2. 4-way cassette type 7-3. Duct type 7-4. Wall-mounted type 7-5. Floor standing type 7-6. Ceiling type 74 76 78 80 82 84 8. Noise level 8-1. Overall 8-2. Octave band level 1. Unit selection (with cooling load) 2. Specification 2-1. 50Hz 2-2.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM I Page 5 Overview 1. DVM system series 1-1. What is DVM? 1-2. Features of DVM 1-3. DVM vs VAV 2. 6 7 12 DVM line-up 2-1. Numbering system of model 2-2.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 6 I. Overview 1. DVM system series 1-1. What is DVM? The DVM(Digital Variable Multi) air conditioning system is operated by a variable-capacity compressor and is accommodated by multiple evaporators (indoor units). It is touted as the next-generation modular system in the world of high-efficiency air conditioning. lt has undoubtedly changed the face of cooling associated with high-storied buildings.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 7 1-2. Features of DVM (1) Customized air conditioner 1) Up to 16 indoor units can be connected to one outdoor unit. 2) Indoor units can be combined by various methods, according to each room’s use and shape. 3) There are several indoor units which can be applied; 1-way cassette type, 4-way cassette type, Ceiling, Duct (Low silhouette, Built-in, High pressure), Wall-mounted and Floor standing type.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 8 I. Overview 1. DVM system series (3) Variable compressor The world’s first PWM(Pulse Width Modulation) compressor controls the cooling & heating capacity automatically, depending on the load. 1) Principle of the digital compressor ① Composition The solenoid valve is installed for the compressor´s loading / unloading between the upper part of the fixed scroll and the suction pipe. ② Mechanism a.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 9 2) PWM (Pulse Width Modulation) valve PWM valve is the valve to take away the fixed scroll by lifting up through the difference of pressure after the digital scroll compress being connected to the outlet and inlet of suction. Therefore, the capacity of compressor is controlled automatically according to the operation status such as loading when the valve is closed or unloading when the valve is opened.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 10 I. Overview 1. DVM system series (5) Long & single piping system 1) Piping can be extended up to 100 meters; refer to the figure. (6) Convenient centralized control 15m (Height between indoor units) In addition, a maximum of 16 indoor units can be controlled with the centralized controller. 2) A maximum of 256 indoor units can be controlled by using the PC Control.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 11 (9) Space Saving The outdoor units connected with several indoor units do not require much space.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 12 I. Overview 1. DVM system series 1-3. DVM vs VAV (1) Excellent energy efficiency Zone control VAV Test condition Opening Capacity Power ratio (W) (W) A 25% 7344 7138 25% B 50% 1.134 8016 A 6313 11997 7353 50% B 75% 1.794 6486 13015 A 15857 7504 75% B 100% 2.298 16996 A 6626 7630 17200 100% B SEER (W/W) 2.492 19007 6802 DVM Opening Capacity Power ratio (W) (W) Max. 5381 2593 Min. 3997 1977 Max. 5510 2353 Min.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 13 (2) DVM test condition Pipe (Copper) (21kW) #1 (5.2kW) #2 (5.2kW) Outdoor unit #3 (5.2kW) #4 (5.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 14 I. Overview 2. DVM line-up 2-1.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 15 (2) Indoor unit and outdoor unit (New Model) 1) Indoor unit Model AVM K H 100 B A 0 ① ② ③ ④ ⑤ ⑥ ⑦ ① Semi-finished product Variable capacity free joint multi (DVM) ③ Mode AVM ② Classification of product ⑤ Power supply Cooling only (C/O) C 208~230V, 60Hz C Heat pump (H/P) H 220~240V, 50Hz E H/P+Heater E C/O+Heater G C/O+Hot water heater N ④ Capacity (kW x 100, 3 digits) 1-way K Cassette 4-way type 2-way C 000 Watt
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 16 I. Overview 2.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 17 (3) Options Parts Electronic expansion valve kit Model MEV- Distributor MXDkit ①②③ ①②③④⑤ Standard for model name Example MEV : Optional electronic expansion valve ● MEV-14SA ① : Electronic expansion valve model (2 digits) ② : Manufacturer ③ : Version ● MEV-18SA MXD : Optional distributor kit ● MXD-14K300A ① : Max diameter (2 digits) ② : Kinds (marked as K2 for two kinds) ③ : Minimum diameter ● MXD-14K218A ● MEV-24SA (1/4” 3) (1/4” 2, 1/8
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 18 I. Overview 2.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Parts Super cooler Page 19 Model MSC- ①②③④⑤ Standard for model name MSC : Super cooler ①, ② : HP of applicable outdoor unit (marked as 00 if it is 10.0 HP) ③ : Power supply B:220V, 60Hz C:208~230V, 60Hz E:220~240V, 50Hz Example ● MSC-00EB0 (Applied to the top of 10.0HP outdoor unit) ● MSC-45EA0 (Applied to the front of 4.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 20 I. Overview 2. DVM line-up 2-2. Combination (1) Outdoor unit 1) Cooling only Design Main Power supply Model Capacity(HP) Refrigerant Super cooler 50Hz 380~415V, 3ø RVMC060GDM0 6 R407C 60Hz 208~230V, 3ø RVMC050CBM0 5 R22 380~415V, 3ø RVMC060GAM0 6 R22 380~415V, 3ø RVMC060GAM1 6 R22 MUF7201F1 7.5 R22 208~230V, 3ø RVMC075FAM0 7.
DVM E-D/B(chapter1)-E<03759 Main 3/21/02 6:55 PM Page 21 Design Max. connectible indoor units Total capacity of indoor units (kW, ISO standard) Super cooler 8 8.0~20.8 - 7 7.2~18.8 - 8 8.0~20.8 - Super cooler Remark - 8 10 8.0~16.0 - 10.5~27.3 - 10.5~21.0 O 10.5~27.3 - 10.5~21.0 - 14.0~36.4 - 14.0~28.0 - 11.1~29.0 - 14.0~36.4 - 14.0~28.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 22 I. Overview 2.
DVM E-D/B(chapter1)-E<03759 Main 3/21/02 6:55 PM Page 23 Design Max. connectible indoor units Total capacity of indoor units (kW, ISO standard) Super cooler 8 8.0~20.8 - 8 8.0~20.8 - 7 7.2~18.8 - 11 11.0~29.0 - 14.0~36.4 - 14.0~28.0 - 14.0~36.4 - 14.0~36.4 - 14.0~28.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Page 24 I. Overview 1. System line-up (2) Indoor unit Design 1-way cassette type Power supply 50Hz 60Hz 4-way cassette type 50Hz 2.0kW 2.6kW 3.2kW 3.5kW 4.0kW 5.2kW 6.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM Design 1-way cassette type Page 25 Power 7.0kW 7.2kW 8.2kW 8.3kW 10.5kW 12.
DVM E-D/B(chapter1)-E<03759 3/21/02 6:55 PM II Page 27 Control System 1. Remote controller 1-1. Wireless remote controller 1-2. Wired remote controller 1-3. Centralized controller 1-4. Function controller 2. Receiver & display unit (Duct type) 2-1. Concealed type 2-2. Standard type 3. Transmitter 4. Installation 4-1. Wireless remote controller 4-2. Wired remote controller 4-3. Centralized controller 4-4. Function controller 4-5. Receiver & display unit - concealed type 4-6.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:32 PM Page 2 II. Control System 1. Remote controller 1-1.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:32 PM Page 3 (2) Duct type 1) Cooling only Operating mode selection button Operating mode Automatic Dry Fan Temperature adjustment buttons Cool Filter Reset button Fan speed adjustment button Timer Cancel button On timer button Off timer button On/Off & Timer set/cancel button 2) Heat pump Operating mode selection button Operating mode Automatic Dry Fan Temperature adjustment buttons Cool Heat Filter Reset button Fan speed adjustment button Timer Cancel bu
DVM E-D/B(chapter2)-E<03759 3/21/02 7:32 PM Page 4 II. Control System 1. Remote controller 1-2.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:32 PM Page 5 (2) Duct type 1) Cooling only Operating mode Automatic Dry Fan Temperature adjustment buttons Cool On/Off & Timer set/cancel button Operating indicator Fan speed adjustment button On/Off timer button Test operation button Filter Reset button Operating mode selection button 2) Heat pump Operating mode Automatic Dry Fan Temperature adjustment buttons Cool Heat On/Off & Timer set/cancel button Operating indicator Fan speed adjustment button On/Of
DVM E-D/B(chapter2)-E<03759 3/21/02 7:32 PM Page 6 II. Control System 1. Remote controller 1-3. Centralized controller Operating lamp All On button All Off button On/off indicators Individual On/Off button Index 1-4.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:32 PM Page 7 2. Receiver & display unit (Duct type) 2-1. Concealed type (1) Cooling only Filter sign indicator Fan indicator Timer indicator Remote control sensor On/Off button (2) Heat pump Filter sign indicator Fan indicator Timer indicator Remote control sensor On/Off button(Blue) & Removing frost indicator(Red) Note ◆ The shape of receiver & display unit for cooling model is same with heat pump’s.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:32 PM Page 8 II. Control System 2. Receiver & display unit (Duct type) 2-2.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:32 PM Page 9 3.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:32 PM Page 10 II. Control System 4. Installation 4-1.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 11 4-2. Wired remote controller (1) Accessories Wired Remote Controller (1) Cable-Tie(2) Cable Clamp (5) M4x16 Indoor Unit Tapped Screw Power Drawing (7) Cable (1) Owner’s instructions(1) Installation manual (1) (2) Installation 1) Open the wired remote controller by using two grooves on its top. 2) Secure the rear cover of the wired remote controller on the wall with 2 screws.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 12 II. Control System 4. Installation (3) Setting up option switches Indoor unit PCB 1) Adjust K1 DIP switch(SW03) on the PCB to the “OFF” K1 K2 K3 K4 position. SW03 2) Turn the arrow of RMC rotary switch(SW01) to the RMC SW01 appropriate position. Result : It is controlled by a wired remote controller which has the same address. Wired remote controller PCB 1) Assign an address to the wired remote controller by turning the arrow of rotary switch.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 13 (4) Example of installing wired remote controller Individual control Means a wired remote controller controls only 1 indoor unit. In this case, the RMC address of the indoor unit should be the same with the address of wired remote controller.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 14 II. Control System 4. Installation 4-3. Centralized controller (1) Accessories Centralized Controller (1) Note Cable-tie (2) Cable Clamp (5) M4x16 Tapped Screw (7) Owner’s instructions(1) Installation manual(1) ◆ If you would like to install the centralized controller, you must install the optional transmitter in the outdoor unit. (2) Wiring diagram Each outdoor unit connected to the same centralized controller must have its own transmitter.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 15 (4) Assigning address Turn the arrow of rotary switch on the transmitter to appropriate position. Transmitters controlled with the same centralized controller must have different addresses. Transmitter rotary switch (5) Setting up option switches In case of installing centralized controller only Adjust K2 DIP switch(SW03) on the indoor unit PCB to the “OFF” position. It means use of the centralized controller.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 16 II. Control System 4. Installation In Case of Installing wired remote controller together 1) Adjust K2 DIP switch(SW03) on the indoor unit PCB to the K1 K2 K3 K4 “OFF” position. It means use of the centralized controller. Note SW03 ◆ The number of button on the centralized controller is decided by the RMC addresses of indoor units. Refer to the table below. Button No. RMC Address Button No.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 17 (6) Example of centralized controller & wired remote controller Installation of 1 centralized controller, 4 outdoor units, and 12 indoor units ◆ 6 indoor units connected to the outdoor unit 1 and 2 are controlled with their own wired remote controller and a centralized controller. ◆ 3 indoor units connected to the outdoor unit 3 are controlled as a group by a wired remote controller and a centralized controller.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 18 II. Control System 4. Installation Level of centralized controller ◆ Adjust the DIP switch on the centralized controller PCB, if necessary. Refer to the table below. Switch No. 1 2 3 4 Level 0 OFF OFF OFF OFF Level 1 ON Level 2 OFF Meaning The air conditioner is operated by a controller adjusted the last among the wired and wireless remote controller, and centralized controller.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 19 4-4. Function controller (1) Accessories Function controller (1) Cable-tie(2) Cable clamp (6) M4x16 Tapped screw (7) Owner’s instructions(1) Installation manual (1) (2) Installation 1) Disassemble the function controller by using a groove on its top. 2) Secure the rear cover of the function controller on the wall with two screws. 3) Connect the C1 and C2 terminals in the function controller to the same terminals in the centralized controller.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 20 II. Control System 4. Installation (3) Wiring diagram ◆ Install the transmitter, another optional accessory, in the outdoor unit which will be controlled by the centralized controller, then connect the function controller and the centralized controller to the transmitter. ◆ Each outdoor unit connected to the same centralized controller must have its own transmitter.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 21 4-5. Receiver & display unit - Concealed type (1) Accessories Receiver & Display Unit (1) STS 2S-2x10 2S-4x12 Tapped Tapped Screw (4) Screw (2) Owner’s instructions(1) Installation manual(1) Wire kit (Length:10m) (2) Installation 1) Remove the receiver & display unit cover by using the tab on its bottom. 2) Open the receiver & display unit.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 22 II. Control System 4. Installation 4-6. Receiver & display unit - Standard type (1) Accessories Function controller (1) Cable-Tie(2) Cable Clamp (6) M4x16 Owner’s Tapped Screw instructions(1) (7) Installation manual (1) Wire kit (Length:10m) (2) Installation 1) Remove the receiver & display unit cover by using the tab on its bottom. 2) Open the receiver & display unit.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 23 4-7. Transmitter (1) Accessories Transmitter (1) Transmitter power cable (1) CN01 Transmitter communication cable (1) Installation manual (1) F1 F2 (2) Installation ◆ Attach the transmitter to the left side of the electrical component box in outdoor unit, then connect the power and communication cable between the transmitter and the outdoor; refer to the figure below.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 24 II. Control System 4. Installation (3) Wiring diagram ◆ Each outdoor unit connected to the same centralized controller has its own transmitter. ◆ Distance between the centralized controller and the last transmitter should be 1000 meters or less.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 25 5. Assigning address 5-1. Indoor unit 1) Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan. 2) The address of the indoor unit is assigned by adjusting MAIN(SW02) and RMC(SW01) rotary switches. SW03 K1 K2 K3 K4 SW04 K5 K6 K7 K8 K9 K10 K11 K12 SW05 Indoor unit PCB SW02 MAIN SW01 RMC 3) The MAIN address is for communication between the indoor unit and the outdoor unit.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 26 II. Control System 5. Assigning address 5-2. Outdoor unit Rotary switch Outdoor unit PCB You should display that how many indoor units are connected to the outdoor unit. Refer to the table below, then turn the arrow to appropriate position. Switch No. Number of indoor unit(s) Switch No.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 27 6. Indoor unit PCB option code 6-1. PCB option code input method (example : 021E31142285) Be sure to input the option code suitable for the indoor unit by use of wireless remote controller after replacing the PCB of indoor unit. Follow to do the following 15 steps sequentially. Operation method Applicable button ❋ Step 1 Method) ① Remove the battery of remote controller. ② Push the temperature adjustment button simultaneously. ③ Insert the battery.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 28 II. Control System 6. Indoor unit PCB option code Operation method Applicable button ❋ Step 4 Method) Input the third digit of option code by pressing the temperature adjustment button (down). example) 021E31142285 Result) If 1 is displayed, go to the step 5. ❋ Step 5 Method) Input the fourth digit of option code by pressing the fan speed adjustment button. example) 021E31142285 Result) If E displays, go to step 6.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 29 Operation method Applicable button ❋ Step 7 Method) Input the sixth digit by pressing the Off timer button. example) 021E31142285 Result) If 1 displays, go to step 8. ❋ Step 8 Method) After completion up to step 7, pressing mode button. ① 1 ~ 7 steps are saved internally. ② If the first number is 1 at the time, it is correct. So go to step 9. ✼ If wanting to see the screen of 2 ~7 steps, press the mode button to make the first digit 0.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 30 II. Control System 6. Indoor unit PCB option code Operation method Applicable button ❋ Step 10 Method) Input the ninth digit by pressing the temperature adjustment button (down). example) 021E31142285 Result) If 2 displays, go to step 11. ❋ Step 11 Method) Input the tenth digit by pressing fan speed adjustment button. example) 021E31142285 Result) If 2 displays, go to step 12. ❋ Step 12 Method) Input the 11st digit by pressing the On timer button.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 31 Operation method Applicable button Indicating state ❋ Step 13 Method) Input the 12th digit by pressing the Off timer button. example) 021E31142285 Result) If 5 displays, go to step 14. ■ Error ❋ Step 14 ① If the Operation, Timer and Fan Method) Turn the remote controller toward the indoor unit and press the On/Off button, and if the “Ting” or “Taririring” sounds, the input of option is completed.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 32 II. Control System 6. Indoor unit PCB option code 6-2.
DVM E-D/B(chapter2)-E<03759 Type 3/21/02 7:33 PM Model AVMHC105E(C)A0 Duct type AVMHC128E(C)A0 (High AVMHH105E(C)A0 pressure) AVMHH128E(C)A0 Page 33 SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Remark 0 1 5 A 0 0 1 0 0 0 0 0 0 1 5 A 0 0 1 2 0 0 0 0 AVMWC020E(C)A0 AVMWC026EA0 AVMWC032CA0 AVMWC035EA0 AVMWC040CA0 AVMWC052E(C)A0 Wall- AVMWC070EA0 mounted AVMWC072CA0 type AVMWH020E(C)A0 0 8 5 6 0 0 1 1 2 0 C 8 AVMWH026EA0 0 8 5 6 0 0 1 4 2 2
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 34 II. Control System 7. S-Net Transmitter PCB Rear of computer (Not supplied) Outdoor unit PCB Switch of converter slide 1 2 3 4 6 7 8 9 5 Power COM1 port Power Connector 1) Download S-NET program to your PC, then execute Setup.exe to install the program. 2) If the installation is completed successfully, connect RS-485 converter to COM1 or COM2 port on your computer.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 35 8.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 36 II. Control System 9.
DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM III 1. Page 37 Indoor unit Features 1-1. 1-way cassette type 1-2. 4-way cassette type 1-3. Duct type 1-4. Wall-mounted type 1-5. Floor standing type 1-6. Ceiling type 2. Functional parts and safety devices 3-1. 1-way cassette type 3-2. 4-way cassette type 3-3. Duct type (Low silhouette) 3-4. Duct type (Built-in) 3-5. Duct type (High pressure) 3-6. Wall-mounted type 3-7. Floor standing type 3-8. Ceiling type 4. 7. 34 34 35 36 36 37 38 38 8. 39 45 5-1.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:33 PM Page 2 III. Indoor unit 1. Features 1-1. 1-Way cassette type (1) Efficient cooling & stylish design This type sends cool air from the ceiling to one direction; thus immediate cooling. Even more, the stylish design blends with any interior design. (2) Space saving Installation in the ceiling translates to more available space in the room.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:33 PM Page 3 (3) Features of the 1-way cassette type 1) Long-life air filter The long-life filter requires no maintenance for up to 2,000 hours. 2) Bio heat exchanger & air filter Samsung’s own heat exchanger and air filter prevent any penetration of fungi or bacteria into the system. Insulating material (Foam PU) Insulating material EPS Cabinet 3) Double-insulated cabinet Dual insulation of the the steel cabinet inhibits rust caused by dew.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:33 PM Page 4 III. Indoor unit 1. Features 1-2. 4-Way cassette type (1) Powerful functions The 4-way cassette type air conditioner has all the features of the 1-way cassette type; compact design, long-life air filter, bio heat exchanger, lift-up drain pump, etc. (2) Higher & broader cooling This type is used in applications where a high ceiling and open space is present, resulting in equal & wide-range cooling.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:33 PM Page 5 (3) Features of 4-way cassette type 1) Fan speed adjustment Item Ceiling height Fan speed can be adjusted 3.5m according to the ceiling height. H 2.7~3.5m L 2.7m ✻ Max. installation ceiling height is 3.5 meters. 2) Versatile airflow The direction of airflow can be selected to meet installation or room specifications.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:33 PM Page 6 III. Indoor unit 1. Features 1-3. Duct type (1) Economic installation Several diffusers branch off from an indoor unit, adjusting the room temperature, which makes many rooms to be air conditioned with only one indoor unit. Looks of installed Duct (Built-in type) (2) High external static pressure Adjustable external static pressure allows ducts from the unit to be used more extensively.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 7 (3) Features of Duct type 1) Application methods L-shaped area Y-shaped area Areas far apart 2) Way of air intake & Inserting air filter Air intake can be positioned either at the back or below the unit. Similarly, the air filter can be inserted either from the back or from the bottom of the unit. min.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 8 III. Indoor unit 1. Features 1-4. Wall-mounted type (1) BIO-components Samsung air conditioners ensure cleaner cooling than any other air conditioner. The components of our air conditioners (including the filters) have been treated with our unique antibacterial formula, which prevent the proliferation of fungi and bacteria within the unit, helping to keep the unit clean, and to block odors from developing.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 9 ■ Bio 2) Look at how well these filters perform ① Hydrocarbon analysis - Test: A deodorizing filter is installed within the duct and its efficiency is tested.(at a wind speed of 0.35m3/min.) - Method: Measure the removal efficiency by installing a filter inside the duct, fixing the density of toluene gas and measuring its density at the exit point.-Tested by AFTL (U.S.A) ② Particle size vs.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 10 III. Indoor unit 1. Features 1-5. Floor standing type (1) Features of floor standing type 1) The auto shutter increased clean liness The auto shutter protects the air conditioner from dust even without a cover and the air conditioner goes well with any home.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 11 5) Design Air flow blades (up/down orientation) Air flow blades (right/left orientation) Automatic shutter Air outlet Air filter Air inlet ■ Control panel On/Off button Fan speed adjustment button Operation indicator Operating mode selection button Remote control sensor Temperature adjustment buttons II 11 Turbo button
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 12 III. Indoor unit 1. Features 1-6. Ceiling type (1) Convenient installation The ceiling type air conditioner can be easily installed into a corner of the ceiling even if the ceiling is very narrow. This is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as a lighting fixture.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 13 (3) Features of ceiling type 1) Long life filter with antibacterial treatment The detachable filter can be cleaned easily, thus controlling the propagation of fungi & bacteria. 2) Drain water lift-up mechanism (Optional) The “Drain water lift-up” mechanism offers more flexible installation.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 14 III. Indoor unit 2. Specification 2-1. 1-way cassette type (1) 50Hz AVMKC020EA0 Model Power supply AVMKC026EA0 ø, V, Hz Cooling only Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) Fan output AVMKH035EA0 Heat pump 12000 7000 9000 12000 7000 9000 kW 2.0 2.6 3.5 2.0 2.6 3.5 Btu/h - - - 7500 10000 13000 kW - - - 2.2 2.9 3.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 15 (2) 60Hz AVMKC020CA0 Model Power supply Sound Level ✻ 3) Fan output AVMKH032CA0 AVMKH040CA0 Heat pump 13500 Btu/h 7000 11000 13500 7000 11000 kW 2.0 3.2 4.0 2.0 3.2 4.0 Btu/h - - - 7500 12000 14500 kW - - - 2.2 3.5 4.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 16 III. Indoor unit 2. Specification 2-2. 4-way cassette type (1) 50Hz AVMCC052EA0 Model Power supply Sound Level ✻ 3) Fan output AVMCH105EA0 Heat pump 18000 24000 36000 18000 24000 kW 5.2 7.0 10.5 5.2 7.0 10.5 Btu/h - - - 19000 26000 39000 kW - - - 5.6 7.6 11.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 17 (2) 60Hz AVMCC052CA0 ABM1800B1 Model ø, V, Hz Power supply Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) Fan output AVMCH105CA0 1, 208 ~ 230, 60 Heat pump 24000 36000 18000 24000 kW 5.2 7.2 10.5 5.2 7.2 10.5 Btu/h - - - 19000 26000 39000 kW - - - 5.6 7.6 11.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 18 III. Indoor unit 2. Specification 2-3. Duct type (Low silhouette) (1) 50Hz AVMDC052EA0 Model Power supply Cooling only Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) Fan output (4mmAq) 24000 24000 18000 kW 5.2 7.0 5.2 7.0 Btu/h - - 19000 26000 kW - - 5.6 7.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 19 (2) 60Hz AVMDC052CA0 ADM1800B1 Model Power supply ø, V, Hz Cooling only Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) Fan output 24000 24000 18000 kW 5.2 7.2 5.2 7.2 Btu/h - - 19000 26000 kW - - 5.6 7.6 Cooling (High/Low) dB 35/32 38/36 35/32 38/36 Heating (High/Low) dB - - 35/32 38/36 - Sirocco Sirocco Sirocco Sirocco Type Watt 51 81 51 81 m3/min 15 18 15/15.5 18/18.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 20 III. Indoor unit 2. Specification 2-4. Duct type (Built-in) (1) 50Hz AVMBC020EA0 Model Power supply AVMBC026EA0 ø, V, Hz Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) 7000 9000 12000 18000 24000 kW 2.0 2.6 3.5 5.2 7.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 21 AVMBH020EA0 Model Power supply AVMBH026EA0 ø, V, Hz Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) 9000 12000 18000 kW 2.0 2.6 3.5 5.2 7.0 Btu/h 7500 10000 13000 19000 26000 kW 2.2 2.9 3.8 5.6 7.6 Cooling (High/Low) dB 37/34 41/38 42/39 43/40 45/42 Heating (High/Low) dB 37/34 41/38 42/39 43/40 Fan output 45/42 - Sirocco Sirocco Sirocco Sirocco Sirocco Type Watt 39 42 44 53 63 m3/min 8.2/8.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 22 III. Indoor unit 2. Specification (2) 60Hz AVMBC020CA0 Model Power supply AVMBC032CA0 ø, V, Hz Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) 7000 11000 13500 18000 24000 kW 2.0 3.2 4.0 5.2 7.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 23 AVMBH020CA0 Model Power supply AVMBH032CA0 ø, V, Hz Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) 11000 13500 18000 kW 2.0 3.2 4.0 5.2 7.2 Btu/h 7500 12000 14500 19000 26000 kW 2.2 3.5 4.3 5.6 7.6 Cooling (High/Low) dB 37/34 41/38 42/39 43/40 45/42 Heating (High/Low) dB 37/34 41/38 42/39 43/40 Fan output 45/42 - Sirocco Sirocco Sirocco Sirocco Sirocco Type Watt 39 42 44 53 63 m3/min 8.2/8.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 24 III. Indoor unit 2. Specification 2-5. Duct type (High pressure) (1) 50Hz AVMHC105EA0 Model Power supply Cooling only Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) Fan output 44000 44000 36000 kW 10.5 12.8 10.5 12.8 Btu/h - - 39000 47000 kW - - 11.4 13.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 25 (2) 60Hz AVMHC105CA0 Model Power supply Cooling only Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) Fan output 44000 44000 36000 kW 10.5 12.8 10.5 12.8 Btu/h - - 39000 47000 kW - - 11.4 13.8 Cooling (High/Low) dB 45/44 45/44 45/44 45/44 Heating (High/Low) dB - - 45/44 45/44 - Sirocco Sirocco Sirocco Sirocco Type Watt 193 214 193 214 m3/min 29 32 29/30 32/33 Running current Cooling A 2.55 2.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 26 III. Indoor unit 2. Specification 2-6. Wall-mounted type (1) 50Hz AVMWC020EA0 Model Power supply AVMWC026EA0 ø, V, Hz Remark Sound Level ✻ 3) 7000 9000 12000 18000 24000 kW 2.0 2.6 3.5 5.2 7.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 27 AVMWH020EA0 Model Power supply AVMWH026EA0 ø, V, Hz Remark Sound Level ✻ 3) 9000 12000 18000 kW 2.0 2.6 3.5 5.2 7.0 Btu/h 7500 11000 13000 19000 26000 kW 2.2 2.9 3.8 5.6 7.6 Cooling (High/Low) dB 29/28 34/30 38/35 41/37 44/41 Heating (High/Low) dB 29/28 34/30 38/35 41/37 Fan output 44/41 - Cross fan Cross fan Cross fan Cross fan Cross fan Type Watt 13 14 16 21 21 m3/min 5.5 6.5 7.8 12.7/13.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 28 III. Indoor unit 2. Specification (2) 60Hz AVMWC020CA0 Model Power supply AVMWC032CA0 ø, V, Hz Remark Sound Level ✻ 3) 7000 11000 13500 18000 24000 kW 2.0 3.2 4.0 5.2 7.2 Btu/h - - - - - kW - - - - - Cooling (High/Low) dB 29/28 34/30 38/35 41/37 44/41 Heating (High/Low) dB - - - - Fan output (4mmAq) - - Cross fan Cross fan Cross fan Cross fan Cross fan Type Watt 13 14 16 21 21 m3/min 5.5 7.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 29 AVMWH020CA0 Model Power supply AVMWH032CA0 ø, V, Hz Remark Sound Level ✻ 3) Fan output (4mmAq) 11000 14500 18000 kW 2.0 3.2 4.3 5.2 7.2 Btu/h 7500 12000 13200 19000 26000 kW 2.2 3.5 3.9 5.6 7.6 Cooling (High/Low) dB 29/28 34/30 38/35 41/37 44/41 Heating (High/Low) dB 29/28 34/30 38/35 41/37 44/41 - Cross fan Cross fan Cross fan Cross fan Cross fan Type Watt 13 14 16 21 21 m3/min 5.5/6.0 7.5/8.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 30 III. Indoor unit 2. Specification 2-7. Floor standing type (1) 50Hz AVMPC060EA0 Model Power supply Sound Level ✻ 3) Fan output AVMPH070EA0 AVMPH082EA0 Heat pump Btu/h 20000 24000 28000 20000 24000 kW 6.0 7.0 8.2 6.0 7.0 8.2 Btu/h - - - 22000 26000 30000 kW - - - 6.4 7.6 8.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 31 (2) 60Hz AVMPC060CA0 Model Power supply Sound Level ✻ 3) Fan output AVMPH072CA0 AVMPH083CA0 Heat pump Btu/h 20000 24000 28000 20000 24000 kW 6.0 7.2 8.3 6.0 7.2 8.3 Btu/h - - - 22000 26000 30000 kW - - - 6.4 7.6 8.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 32 III. Indoor unit 2. Specification 2-8. Ceiling type (1) 50Hz AVMFC052EA0 Model Power supply Cooling only Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) Fan output 24000 24000 18000 kW 5.2 7.0 5.2 7.0 Btu/h - - 19000 26000 kW - - 5.6 7.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 33 (2) 60Hz AVMFC052CA0 Model Power supply Cooling only Cooling ✻ 1) Performance Capacity Sound Level ✻ 3) Fan output 24000 24000 18000 kW 5.2 7.2 5.2 7.2 Btu/h - - 19000 26000 kW - - 5.6 7.6 Cooling (High/Low) dB 43/40 45/40 43/40 45/40 Heating (High/Low) dB - - 43/40 45/40 - Cross fan Cross fan Cross fan Cross fan Type Watt 51 53 51 53 m3/min 14 18 14/14.5 18/18.5 Running current Cooling A 0.77 0.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 34 III. Indoor unit 3. Functional parts and safety devices 3-1.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 35 3-3.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 36 III. Indoor unit 3. Functional parts and safety devices 3-4.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 37 3-6.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 38 III. Indoor unit 3. Functional parts and safety devices 3-7.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 39 4. Capacity table 4-1. 50Hz (1) Cooling Unit Size 020 026 035 TC : Total capacity Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 Indoor temperature (ºC, WB) 24.0 14.0 16.0 18.0 19.0 20.0 22.0 TC TC TC TC TC TC TC kW 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.90 1.90 1.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 40 III. Indoor unit 4. Capacity table TC : Total capacity Unit Size 052 070 Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 Indoor temperature (ºC, WB) 24.0 14.0 16.0 18.0 19.0 20.0 22.0 TC TC TC TC TC TC TC kW 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 5.12 5.12 5.12 5.12 5.12 5.12 5.12 5.12 5.12 5.12 5.12 5.12 5.12 5.
DVM E-D/B(chapter3-1)-E<03759 3/21/02 7:34 PM Page 41 TC : Total capacity Unit Size 105 128 Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 Indoor temperature (ºC, WB) 24.0 14.0 16.0 18.0 19.0 20.0 22.0 TC TC TC TC TC TC TC kW 7.68 7.68 7.68 7.68 7.68 7.68 7.68 7.68 7.68 7.68 7.68 7.68 7.68 7.68 7.68 7.68 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 kW 9.07 9.07 9.07 9.07 9.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 42 III. Indoor unit 4. Capacity table (2) Heating Unit Size 020 026 035 TC : Total capacity Outdoor temperature (ºC) DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 Indoor temperature (ºC, DB) 16.0 18.0 20.0 22.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 43 TC : Total capacity Unit Size 052 070 105 Indoor temperature (ºC, DB) Outdoor temperature (ºC) DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 II 16.0 18.0 20.0 22.0 TC TC TC TC TC kW 3.7 4.1 4.6 5.0 5.4 5.7 5.9 6.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 44 III. Indoor unit 4. Capacity table TC : Total capacity Unit Size 128 Outdoor temperature (ºC) DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 Indoor temperature (ºC, DB) 16.0 18.0 20.0 22.0 24.0 TC TC TC TC TC kW 9.1 10.2 11.5 12.4 13.4 14.1 14.6 14.9 15.5 15.9 16.1 16.1 16.1 16.1 kW 9.0 10.1 11.2 12.1 12.8 13.5 14.1 14.6 14.9 14.9 14.9 14.9 14.9 14.9 kW 8.8 10.0 10.9 11.8 12.4 13.0 13.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 45 4-2. 60Hz (1) Cooling Unit Size 020 032 040 TC : Total capacity Outdoor temperature (ºC, WB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 Indoor temperature (ºC, WB) 24.0 14.0 16.0 18.0 19.0 20.0 22.0 TC TC TC TC TC TC TC kW 1.46 1.46 1.46 14.6 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 2.34 2.34 2.34 2.34 2.34 2.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 46 III. Indoor unit 4. Capacity table TC : Total capacity Unit Size 052 072 083 Outdoor temperature (ºC, WB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 Indoor temperature (ºC, WB) 24.0 14.0 16.0 18.0 19.0 20.0 22.0 TC TC TC TC TC TC TC kW 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 5.27 5.27 5.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 47 TC : Total capacity Unit Size 105 128 Outdoor temperature (ºC, WB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 Indoor temperature (ºC, WB) 24.0 14.0 16.0 18.0 19.0 20.0 22.0 TC TC TC TC TC TC TC kW 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 9.37 kW 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 48 III. Indoor unit 4. Capacity table (2) Heating Unit Size 020 032 040 TC : Total capacity Outdoor temperature (ºC) DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 Indoor temperature (ºC, DB) 16.0 18.0 20.0 22.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 49 TC : Total capacity Unit Size 052 072 105 Indoor temperature (ºC, DB) Outdoor temperature (ºC) DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 II 16.0 18.0 20.0 22.0 TC TC TC TC TC kW 3.7 4.1 4.6 5.0 5.4 5.7 5.9 6.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 50 III. Indoor unit 4. Capacity table TC : Total capacity Unit Size 128 Outdoor temperature (ºC) DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 Indoor temperature (ºC, DB) 16.0 18.0 20.0 22.0 TC TC TC TC TC kW 9.1 10.2 11.5 12.4 13.4 14.1 14.6 14.9 15.5 15.9 16.1 16.1 16.1 16.1 kW 9.0 10.1 11.2 12.1 12.8 13.5 14.1 14.6 14.9 14.9 14.9 14.9 14.9 14.9 kW 8.8 10.0 10.9 11.8 12.4 13.0 13.8 13.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 51 5. Dimension 5-1. 1-way cassette type Unit : mm ◆ Check the position of remote control sensor and indicators before installing the unit. ◆ If you want to install optional parts, refer to an appropriate installation manual.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 52 III. Indoor unit 5. Dimension 5-2. 4-way cassette type (1) 5.2kW ~ 7.2kW Unit : mm ◆ Check the position of remote control sensor and indicators before installing the unit. ◆ If you want to install optional parts, refer to an appropriate installation manual.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 53 (2) 10.5kW Unit : mm ◆ Check the position of remote control sensor and indicators before installing the unit. ◆ If you want to install optional parts, refer to an appropriate installation manual.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 54 III. Indoor unit 5. Dimension 5-3. Duct type (Low silhouette) Unit : mm ◆ If you want to install optional parts, refer to an appropriate installation manual.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 55 5-4. Duct type (Built-in) (1) 2.0kW ~ 4.0kW Unit : mm ◆ If you want to install optional parts, refer to an appropriate installation manual.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 56 III. Indoor unit 5. Dimension (2) 5.2kW ~ 7.2kW Unit : mm ◆ If you want to install optional parts, refer to an appropriate installation manual.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 57 5-5. Duct type (High pressure) Unit : mm ◆ If you want to install optional parts, refer to an appropriate installation manual.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 58 III. Indoor unit 5. Dimension 5-6. Wall-Mounted type (1) 2.0kW ~ 4.0kW Unit : mm ◆ If you want to install optional parts, refer to an appropriate installation manual.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 59 (2) 5.2kW ~ 7.2kW Unit : mm ◆ If you want to install optional parts, refer to an appropriate installation manual.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 60 III. Indoor unit 5. Dimension 5-7. Floor standing type 600m m 330m m 1016mm 1850mm 312mm Unit : mm ◆ If you want to install optional parts, refer to an appropriate installation manual.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 61 5-8.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 62 III. Indoor unit 5. Dimension 5-9.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 63 ◆ AVMKC✻ MGKC118IE0 MGKC118IM0 MGKC118IA0 MGKC118IC0 Remote control sensor Timer indicator Fan indicator On/off indicator Filter sign indicator ◆ AVMKH✻ MGKH118IE0 MGKH118IM0 MGKH118IA0 MGKH118IC0 Remote control sensor Timer indicator Fan indicator On/off(Green) & Removing frost(Red) indicator Filter sign indicator II 63
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 64 III. Indoor unit 5.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 65 ◆ AVMWC✻ Timer indicator Remote control sensor On/off indicator Filter sign indicator On/off button Fan indicator ◆ AVMWH✻ Timer indicator On/off(Green) & Removing frost(Red) indicator On/off button II 65 Remote control sensor Filter sign indicator Fan indicator
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 66 III. Indoor unit 5.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 67 ◆ AVMFC✻ ◆ AVMFH✻ II 67
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 68 III. Indoor unit 5.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 69 ◆ MRK-B00(concealed type) ◆ MRW-10A(wire kit) ◆ MRK-A00(standard type) ◆ MRW-10A(wire kit) II 69
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 70 III. Indoor unit 5. Dimension 5-10.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 71 (2) For duct type (AVMD✻ / AVMB✻ / AVMH✻) ◆ MWR-AC00 Wiring hole ◆ MWR-AH00 Wiring hole II 71
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 72 III. Indoor unit 5. Dimension 5-11.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 73 6. Refrigerant system diagram(Cooling only & heat pump) 6-1. Refrigerant system diagram electronic expansion valve kit fan temperature sensor motor strainer strainer heat exchanger temperature sensor temperature sensor 6-2. Main parts status (1) Temperature sensor (EIS, Evaporator Inlet Sensor) The means to measure the refrigerant temperature at the inlet of heat exchanger which is used as the data for control of electronic expansion valve.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 74 III. Indoor unit 7. Electric circuit diagram 7-1.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 75 (2) Heat pump (AVMKH✻) II 75
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 76 III. Indoor unit 7. Electric circuit diagram 7-2.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 77 (2) Heat pump (AVMCH✻) II 77
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 78 III. Indoor unit 7. Electric circuit diagram 7-3.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 79 (2) Heat pump (AVMDH✻ / AVMBH✻ / AVMHH✻) II 79
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 80 III. Indoor unit 7. Electric circuit diagram 7-4.
DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 81 (2) Heat pump (AVMWH✻) II 81
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 82 III. Indoor unit 7. Electric circuit diagram 7-5.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 83 (2) Heat pump (AVMPH✻) II 83
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 84 III. Indoor unit 7. Electric circuit diagram 7-6.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 85 (2) Heat pump (AVMFH✻) II 85
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 86 III. Indoor unit 8. Noise level 8-1. Overall ◆ 1-way cassette type ◆ 4-way cassette type ◆ Duct type(Low silhoutte) Duct 1m 1m 230V/50Hz 220V/60Hz High Low High Low 32.0 29.0 32.0 29.0 ✻✻026/032✻✻ 36.0 32.0 36.0 32.0 ✻✻035/040✻✻ 38.0 35.0 38.0 35.0 ✻✻020✻✻ ◆ Duct type(Built-in) 230V/50Hz 220V/60Hz Low High Low 31.0 28.0 31.0 28.0 ✻✻070/072✻✻ 35.0 32.0 35.0 32.0 34.0 41.0 34.0 ✻✻052✻✻ ✻✻105✻✻ 41.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 87 8-2. Octave band level (1) 1-way cassette type ✻✻020✻✻ Sound pressure level (dB, ref.2xE-5) 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) Sound pressure level (dB, ref.2xE-5) ✻✻026/032✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 88 III. Indoor unit 8. Noise level Sound pressure level (dB, ref.2xE-5) ✻✻035/040✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 89 (2) 4-way cassette type Sound pressure level (dB, ref.2xE-5) ✻✻052✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) Sound pressure level (dB, ref.2xE-5) ✻✻070/072✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 90 III. Indoor unit 8. Noise level Sound pressure level (dB, ref.2xE-5) ✻✻105✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 91 (3) Duct type (Low silhouette) Sound pressure level (dB, ref.2xE-5) ✻✻052✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) Sound pressure level (dB, ref.2xE-5) ✻✻070/072✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 92 III. Indoor unit 8. Noise level (4) Duct type (Built-in) Sound pressure level (dB, ref.2xE-5) ✻✻020✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) Sound pressure level (dB, ref.2xE-5) ✻✻026/032✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 93 Sound pressure level (dB, ref.2xE-5) ✻✻035/040✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) Sound pressure level (dB, ref.2xE-5) ✻✻052✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 94 III. Indoor unit 8. Noise level Sound pressure level (dB, ref.2xE-5) ✻✻070/072✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 95 (5) Duct type (High pressure) Sound pressure level (dB, ref.2xE-5) ✻✻105✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) Sound pressure level (dB, ref.2xE-5) ✻✻128✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 96 III. Indoor unit 8. Noise level (6) Wall-mounted type Sound pressure level (dB, ref.2xE-5) ✻✻020✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) Sound pressure level (dB, ref.2xE-5) ✻✻026/032✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 97 Sound pressure level (dB, ref.2xE-5) ✻✻035/040✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) Sound pressure level (dB, ref.2xE-5) ✻✻052✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 98 III. Indoor unit 8. Noise level Sound pressure level (dB, ref.2xE-5) ✻✻070/072✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 99 (7) Floor standing type Sound pressure level (dB, ref.2xE-5) ✻✻060✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) Sound pressure level (dB, ref.2xE-5) ✻✻070/072✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 100 III. Indoor unit 8. Noise level Sound pressure level (dB, ref.2xE-5) ✻✻082/083✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 101 (8) Ceiling type Sound pressure level (dB, ref.2xE-5) ✻✻052✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) Sound pressure level (dB, ref.2xE-5) ✻✻070/072✻✻ 70.0 NC-65 60.0 NC-60 NC-55 50.0 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 NC-25 NC-20 High Low 10.0 NC-15 0.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 102 III. Indoor unit 9. Velocity of air flow & temperature distribution 9-1. 1-way cassette type (1) AVMKH035✻ 1) Velocity of air flow 1.5 2.0m/sec 1 1.5m/sec 1.0m/sec 0.5 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 2 2.5 3 3.5 4 4.5 2) Heating temperature distribution 35 C 1.5 32 C 1 26 C 29 C 0.5 0 Note 0.5 1 1.5 ◆ If a ceiling is high, you can apply a 1-way cassette type air conditioner.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 103 9-2. 4-way cassette type (1) AVMCH070✻ 1) Velocity of air flow 1.5m/sec 1.5 1.0m/sec 1 0.5m/sec 0.5 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 2) Heating temperature distribution 35 C 1.5 32 C 29 C 1 26 C 0.5 0 Note 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 ◆ The standard ceiling height is 2.7 meters and those values are tested at the standard height.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 104 III. Indoor unit 9. Velocity of air flow & temperature distribution (2) AVMCH105✻ 1) Velocity of air flow 2.0m/sec 1.5 1.5m/sec 1 1.0m/sec 0.5m/sec 0.5 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 4.5 5 2) Heating temperature distribution 35 C 1.5 32 C 1 29 C 26 C 0.5 0 Note 0.5 1 1.5 2 2.5 3 3.5 4 ◆ The standard ceiling height is 2.7 meters and those values are tested at the standard height.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 105 9-3. Wall-mounted type (1) AVMWH035✻ 1) Velocity of air flow 1.5 1.5m/sec 1 1.0m/sec 0.5m/sec 0.5 0 1 1.5 2 2.5 3 2) Heating temperature distribution 1.5 26 C 35 C 32 C 1 29 C 0.5 0 Note 1 1.5 2 2.5 3 ◆ The standard ceiling height is 2.7 meters and those values are tested at the standard height.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 106 III. Indoor unit 9. Velocity of air flow & temperature distribution (2) AVMWH070✻ 1) Velocity of air flow 1.5 2.0m/sec 1.5m/sec 1 1.0m/sec 0.5m/sec 0.5 0 1 1.5 2 2.5 3 2.5 3 2) Heating temperature distribution 1.5 35 C 29 C 1 32 C 26 C 0.5 0 Note 1 1.5 2 ◆ The standard ceiling height is 2.7 meters and those values are tested at the standard height.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 107 9-4. Ceiling type (1) AVMFH070✻ 1) Velocity of air flow 2.0m/sec 1.5 1 1.0m/sec 0.5m/sec 0.5 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 3 3.5 4 4.5 2) Heating temperature distribution 1.5 35 C 29 C 1 26 C 32 C 0.5 0 Note 0.5 1 1.5 2 2.5 ◆ The standard ceiling height is 2.7 meters and those values are tested at the standard height.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 108 III. Indoor unit 10. Fan specifications 10-1. Duct type (Low silhoutte) (1) ✻✻052✻✻ (2) ✻✻070/072✻✻ 7 External Static Pressure (mmAq) External Static Pressure (mmAq) 14 8 HI Reliable TURBO 6 Range of normal use LOW 5 4 Reliable 3 10 9 11 13 14 13 12 Reliable 11 HI 10 TURBO 9 Range of normal use 8 7 LOW 6 Reliable 5 4 3 12 10 15 Fan Speed (CMM) 14 16 18 20 22 Fan Speed (CMM) 10-2.
3/21/02 7:38 PM Page 109 12 11 11 10 10 9 External static pressure (mmAq) 12 Limitation of max. air flow TURBO 8 7 Limitation of use HI 6 5 4 3 2 1 MID LOW 7 9 10 11 12 (5) ✻✻070/072✻✻ 12 9 8 Limitation of use 7 HI 6 MID 2 1 0 TURBO Limitation of max. air flow 10 Limitation of min.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 110 III. Indoor unit 10. Fan specifications 10-3.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 111 11. Panel 11-1.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 112 III. Indoor unit 11. Panel 11-2.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 113 12. Electronic expansion valve kit 12-1. Design A B C 12-2. Status depending on the combination MEV-14 Item MEV-18 #1 #2 #3 MXD14K300A O O O MXD14K218A O O #1 #2 #3 O ◆ An electronic expansion valve can be applied to 1~3 indoor units. If you want to install more indoor units, separate it properly.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 114 III. Indoor unit 13.
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 115 Optional items Item 1-way cassette type 4-way cassette type Low silhouette Duct type Wireless Receiver Receiver & Receiver & Wired display unint display unint remote & display remote (Concealed (Standard controller unit wire controller type) type) Fresh air intake C/O - MR-AC01 - - - MWR-AC01 X H/P - MR-AH01 - - - MWR-AH01 X C/O - MR-AC01 - - - MWR-AC01 X H/P - MR-AH01 - - - MWR-AH01 X C/O MDP-075SA MR-AC00 MRW
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 116 II 116
DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM IV Page 117 Outdoor unit 1. Selection of outdoor units (based on cooling load) 2. Specification 2-1. 50Hz 2-2. 60Hz 3. Functional parts and safety devices 3-1. Outdoor unit 3-2. Super cooler 4. 10 42 44 Consideration for outdoor unit selection 8-1. Change of capacity depending on refrigerant piping length 8-2. Condition of operating restriction 9. 35 38 Electric circuit diagram 7-1. Cooling only 7-2. Heat pump 8.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 2 IV. Outdoor unit 1. Unit selection (with cooling load) 1-1. Indoor unit selection Select the nearest load capacity indoor unit with given load after finding indoor and outdoor temperature using indoor unit capacity table. (The indoor unit capacity should larger than given load.) ◆ The described capacity may be different to each indoor unit according to combination. So, the real capacity should be calculated with outdoor unit capacity table. 1-2.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 3 1-4. Example for unit selection with cooling load (1) Given condition 1) Design condition 2) Cooling load Location Room A Room B Room C Room D Room E Room F Load (kW) 2.4 2.8 3.2 3.4 4.8 7.2 3) Power supply unit: 3 Phase 380V 50Hz 4) Pipe length: 30m (2) Indoor unit selection Select the suitable capacity for condition of 'Indoor 20°C(WB), Outdoor 33°C(DB)' using indoor unit capacity table.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 4 IV. Outdoor unit 2. Specification 2-1. 50Hz Model Power supply ø, V, Hz RVMC060GAM0 RVMC060GAM1 RVMC060GDM0 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 Cooling only Remark Performance Capacity Set Set Set Cooling ✻ 1) Btu/h 55000(7000~55000) 55000(7000~55000) 95500(7000~95500) kW 16.0(2.0~16.0) 16.0(2.0~16.0) 28.0(2.0~28.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Model Power supply ø, V, Hz Page 5 RVMH060GBM0 RVMH060GDM0 RVMH080GAM0 RVMH100GAM0 RVMH100GCM0 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 3, 380~415, 50 Remark Heat pump Performance Capacity Cooling ✻ 1) Heating ✻ 2) Cooling Sound Level (Front View) ✻ 3) Heating Power Compressor Set Set Set Set Set Btu/h 55000(7000~55000) 55000(7000~55000) 76000(7000~76000) 95500(7000~95500) 95500(7000~95500) kW 16.0(2.0~16.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 6 IV. Outdoor unit 2. Specification 2-2. 60Hz RVMC080FAM0 RVMC100FAM0 RVMH050CBM0 RVMH100FAM0 3, 208~230, 60 3, 208~230, 60 1, 208~230, 60 3, 208~230, 60 Cooling only Heat pump Set Set Set Set Set 95500(7000~95500) 95500(7000~95500) 50000(7000~50000) 76000(7000~76000) 50000(7000~50000) Performance Capacity (ISO) Cooling ✻ 1) Btu/h 28.0(2.0~28.0) 28.0(2.0~28.0) 14.5(2.0~14.5) 22.4(2.0~22.4) 14.5(2.0~14.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Model Power supply Remark Function / Option MUF7201F1 Sound Level Cooling (Front View) ✻ 4) Heating Model Compressor Type Btu/h kW Btu/h kW Btu/h kW dB dB - Super Cooler - Piston displacement Output Type Fan output Output Air flow rate Running current Cooling (ISO) Heating Cooling Power input (ISO) Heating Running current Cooling (SASO) Heating Cooling Power input (SASO) Heating Design pressure Name Refrigerant Charge Control Refrigerant oil Name Charge
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 8 IV. Outdoor unit 3. Functional parts and safety devices 3-1. Outdoor unit Item Compressor Code Name RVMC050CBM0 RVMC060GAM0 RVMC060GAM1 RVMC060GDM0 - Motor output ZRD49KC-PFV 3.7kW ZRD72KC-TFD 4.5kW ZRD72KCE-TFD 4.5kW - Compressor safety OLP 120°C 145°C 145°C 37A 48A 48A CCH open temp.
DVM E-D/B(chapter4-1)-E<03759 Item Compressor 3/21/02 7:39 PM Code Page 9 Name - Motor output - Compressor safety OLP CCH MUF7201F1 open temp. Fan motor 70A 90W 90W 90W OSM1076SRC OSM1076SRC OSM4508SRC OSM4506SRC OSM4508SRC output 106W + 106W 106W + 106W on 150°C off 100°C 580W 450W 450W 150°C 150°C 150°C 150°C 100°C 100°C 100°C 100°C HPS High pressure switch OFF : 30(±1)kg/cm2 ON : 22(±1)kg/cm2 LPS Low pressure switch OFF : 1.2(±0.2)kg/cm2 ON : 2.2(±0.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 10 IV. Outdoor unit 3. Functional parts and safety devices Item Compressor Code Name RVMH050CBM0 RVMH060GBM0 RVMH060GDM0 RVMH080GAM0 - Motor output ZRD49KC-PFV 3.7kW ZRD72KC-TFD 4.5kW ZRD72KCE-TFD 4.5kW ZRDU13MC-TFD 4.2kW + 3.5kW - Compressor safety OLP open temp.
DVM E-D/B(chapter4-1)-E<03759 Item Compressor 3/21/02 7:39 PM Page 11 Code Name RVMH100GAM0 RVMH100FAM0 - Motor output ZRDT14MC-TFD 4.2kW + 4.2kW ZRDU13MC-TF5 5.5kW + 4.3kW - Compressor safety OLP open temp. 155°C 155°C trip current 70A 70A 90W 90W OSME4506SRC OSME4508SRC CCH Crank case heater Fan motor Motor model output 450W 450W on 150°C 150°C off 100°C Safety thermostat Safety devices HPS High pressure switch LPS Low pressure switch OFF : 1.2(±0.2)kg/cm2 ON : 2.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 12 IV. Outdoor unit 3. Functional parts and safety devices Item Code Name - Motor output - Compressor safety OLP Compressor CCH 4.2kW + 4.2kW 155°C open temp. 70A trip current 90W Crank case heater Fan motor Motor Safety devices RVMH100GCM0 ZRDT14MCE-TFD model OSME4506SRC output 450W on 150°C Safety thermostat 100°C off HPS High pressure switch OFF : 30(±1)kg/cm2 ON : 22(±1)kg/cm2 LPS Low pressure switch OFF : 1.2(±0.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 13 3-2. Super cooler Item Code Name - Motor output - Compressor safety OLP Compressor CCH MUF7201F1 (SUB) open temp.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 14 IV. Outdoor unit 4. Capacity table 4-1.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 15 TC : Total capacity, PI : Power input Combination, %(Capacity index) 70 60 50 Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 Indoor temperature (ºC, WB) 14 16 18 19 20 22 24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW 8.20 8.20 8.20 8.20 8.20 8.20 8.20 8.20 8.20 8.20 8.20 8.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 16 IV. Outdoor unit 4. Capacity table 2) ✻✻100✻✻ Combination, %(Capacity index) 100 90 80 TC : Total capacity, PI : Power input Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 Indoor temperature (ºC, WB) 14 16 18 19 20 22 24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW 20.5 20.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 17 TC : Total capacity, PI : Power input Combination, %(Capacity index) 70 60 50 Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 Indoor temperature (ºC, WB) 14 16 18 19 20 22 24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW 14.34 14.34 14.34 14.34 14.34 14.34 14.34 14.34 14.34 14.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 18 IV. Outdoor unit 4. Capacity table (2) Heating 1) ✻✻060✻✻ Combination, %(Capacity index) 100 90 80 TC : Total capacity, PI : Power input Indoor temperature (ºC, DB) Outdoor temperature ºC, DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 ºC, WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 19 2) ✻✻100✻✻ Combination, %(Capacity index) 100 90 80 TC : Total capacity, PI : Power input Indoor temperature (ºC, DB) Outdoor temperature ºC, DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 ºC, WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 20 IV. Outdoor unit 4. Capacity table 4-2.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 21 TC : Total capacity, PI : Power input Combination, %(Capacity index) 70 60 50 Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 Indoor temperature (ºC, WB) 14 16 18 19 20 22 24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW 7.43 7.43 7.43 7.43 7.43 7.43 7.43 7.43 7.43 7.43 7.43 7.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 22 IV. Outdoor unit 4. Capacity table 2) ✻✻060✻✻ Combination, %(Capacity index) 100 90 80 TC : Total capacity, PI : Power input Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 Indoor temperature (ºC, WB) 14 16 18 19 20 22 24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW 11.7 11.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 23 TC : Total capacity, PI : Power input Combination, %(Capacity index) 70 60 50 Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 Indoor temperature (ºC, WB) 14 16 18 19 20 22 24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW 8.20 8.20 8.20 8.20 8.20 8.20 8.20 8.20 8.20 8.20 8.20 8.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 24 IV. Outdoor unit 4. Capacity table 3) ✻✻072✻✻ Combination, %(Capacity index) 100 90 80 TC : Total capacity, PI : Power input Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 Indoor temperature (ºC, WB) 14 16 18 19 20 22 24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW 15.2 15.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 25 TC : Total capacity, PI : Power input Combination, %(Capacity index) 70 60 50 Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 Indoor temperature (ºC, WB) 14 16 18 19 20 22 24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW 10.66 10.66 10.66 10.66 10.66 10.66 10.66 10.66 10.66 10.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 26 IV. Outdoor unit 4. Capacity table 4) ✻✻100✻✻ Combination, %(Capacity index) 100 90 80 TC : Total capacity, PI : Power input Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 Indoor temperature (ºC, WB) 14 16 18 19 20 22 24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW 20.5 20.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 27 TC : Total capacity, PI : Power input Combination, %(Capacity index) 70 60 50 Outdoor temperature (ºC, DB) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 42 44 46 Indoor temperature (ºC, WB) 14 16 18 19 20 22 24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW 14.34 14.34 14.34 14.34 14.34 14.34 14.34 14.34 14.34 14.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 28 IV. Outdoor unit 4. Capacity table (2) Heating 1) ✻✻050✻✻ Combination, %(Capacity index) 100 90 80 TC : Total capacity, PI : Power input Indoor temperature (ºC, DB) Outdoor temperature ºC, DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 ºC, WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 29 2) ✻✻060✻✻ Combination, %(Capacity index) 100 90 80 TC : Total capacity, PI : Power input Indoor temperature (ºC, DB) Outdoor temperature ºC, DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 ºC, WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 30 IV. Outdoor unit 4. Capacity table 3) ✻✻100✻✻ Combination, %(Capacity index) 100 90 80 TC : Total capacity, PI : Power input Indoor temperature (ºC, DB) Outdoor temperature ºC, DB -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 -15 -12 -10 -7 -5 -3 0 3 5 7 9 11 13 15 ºC, WB -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.8 12 14 -14 -13 -11 -8 -6 -4 -1 2.2 4.1 6 7.9 9.
DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 31 5. Dimension 5-1.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:39 PM Page 32 IV. Outdoor unit 5. Dimension 5-2.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 33 5-3.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 34 IV. Outdoor unit 5. Dimension 5-4.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 35 6. Refrigerant system diagram 6-1.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 36 IV. Outdoor unit 6.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 37 (3) Main parts status 1) Digital scroll compressor The variable capacity type compressor to control the capacity up to 10 ~ 100% with 19 steps. 2) Accumulator To prevent the incoming of the liquid refrigerant to the compressor (prevention of liquid back). 3) Receiver To reduce the noise by flowing the high pressure liquid refrigerant to the high pressure pipe and to control the amount of refrigerant during the individual operation of indoor unit.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 38 IV. Outdoor unit 6. Refrigerant system diagram 6-2.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 39 (2) ✻✻080/100✻✻ fan motor solenoid valve (HGBV) capillary tube temperature sensor high pressure switch 4-way valve (4-W/V) heat exchanger electronic expansion valve(EEV) oil separator filter temperature sensor fixed scrool compressor cond out sensor temper- solenoid valve ature digital sensor (PWM) scroll compressor low pressure switch check valve (C/V) solenoid valve (VBV) solenoid valve (LBV) oil sensor suction sensor capillary tube a
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 40 IV. Outdoor unit 6. Refrigerant system diagram (3) Main parts status 1) Digital scroll compressor The variable capacity type compressor to control the capacity up to 10 ~ 100% with 19 steps 2) Accumulator To prevent the incoming of the liquid refrigerant to the compressor (prevention of liquid back).
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 41 11) Temperature sensor (OATS, Outdoor Air Temperature Sensor) To measure the outdoor temperature which is used for the determination of start method. 12) Fixed scroll compressor The fixed capacity type compressor. 13) 4-way valve (4-W/V) It enables the change between cooling and heating by reversing the flow direction of refrigerant.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 42 IV. Outdoor unit 7. Electric circuit diagram 7-1.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 43 (2) ✻✻080/100✻✻ IV 43
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 44 IV. Outdoor unit 7. Electric circuit diagram 7-2.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 45 (2) ✻✻080/100✻✻ IV 45
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 46 IV. Outdoor unit 8. Consideration for outdoor unit selection 8-1.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 47 8-2.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 48 IV. Outdoor unit 9. Noise level ✻✻035✻✻ Sound pressure level (dB, ref.2xE-5) 80.0 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 10.0 NC-25 NC-20 Front Back NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) ✻✻075✻✻ Sound pressure level (dB, ref.2xE-5) 80.0 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 10.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 49 ✻✻060✻✻ Sound pressure level (dB, ref.2xE-5) 80.0 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 10.0 NC-25 NC-20 Front Back NC-15 0.0 63 125 250 500 1000 2000 4000 8000 Octave band center freqency(Hz) ✻✻080/100✻✻ Sound pressure level (dB, ref.2xE-5) 80.0 70.0 NC-65 60.0 NC-60 50.0 NC-55 NC-50 40.0 NC-45 NC-40 30.0 NC-35 NC-30 20.0 10.0 NC-25 NC-20 Front Back NC-15 0.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 50 IV. Outdoor unit 10. Options Design Optional Items Capacity Discharge Interface Centralized (HP) SVM-SNET Refnet kit duct module controller 5.0 ~ 7.5 MDF-45A (2 FAN) 5.0 ~ 6.0 MDF-46A (2 FAN) MIM-B00 MCM-A200 - 8.0 ~ 10.0 ??? (1 FAN) MIM-B00 MCM-A200 - 7.5 ~ 10 (Supper cooler) MDF-45A (1 FAN) MIM-B00 MCM-A200 ❋ The discharge duct shall be bought suitable for the quantities of Fan.
DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM V Page 51 Installation 1. Product 1-1. Preparation for installation 1-2. Deciding on where to install the air conditioner 1-3. Space requirements for the air conditioner 1-4. Accessories 1-5. Installation 2. 2 3 4 8 11 Panel 2-1. 1-way cassette type 2-2. 4-way cassette type 2-3. Duct type (Built-in) 13 15 16 3. Connecting the indoor unit refrigerant pipe 4. Drain hose installation 5. Drain pump installation 5-1. Accessories 5-2. Installation 6.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 2 V. Installation 1. Product 1-1. Preparation for installation When deciding on the location of the air conditioner with the owner, the following restrictions must be taken into account.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 3 1-2. Deciding on where to install the air conditioner. (1) Indoor unit ◆ There must be no obstacles near the air inlet and outlet. ◆ Install the indoor unit on a ceiling that can support its weight. ◆ Maintain sufficient clearance around the indoor unit. ◆ Make sure that the water dripping from the drain hose runs away correctly and safely. ◆ The indoor unit must be installed in this way, that they are out of public access.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 4 V. Installation 1. Product 1-3. Space requirements for the air conditioner (1) Indoor unit 1) 1-way cassette type re m or mo m 00 15 15 00 mm or 15 00 mo re mm or mo re mm 00 15 re mo or 2) 4-way cassette type 3) Duct type (Low silhouette) m 0m or re mo 15 15 00 mm or mo 00 mm re mm 00 15 or 5mm min 0 15 mo re You must have 5mm or more space between the ceiling and the bottom of indoor unit.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 5 4) Duct type (Built-in) re m 0m or mo 0 15 5mm min 15 00 mm or 15 00 mo re mm or mo re mm 00 15 re mo or You must have 5mm or more space between the ceiling and the bottom of indoor unit. Otherwise, the noise from the vibration of indoor unit may bother the user.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 6 V. Installation 1.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 7 (2) Outdoor unit 1) If there is no obstacle around the outdoor unit... Unit : mm 300 or more 100 or more Front 500 or more 300 or more 100 or more 100 or more Front 500 or more 100 or more 100 or more 100 or more Front 100 or more 300 or more 100 or more 500 or more 100 or more 100 or more 500 or more 200 or more 200 or more 100 or more Front ❋ Max.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 8 V. Installation 1. Product 1-4.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 9 (4) Duct type (Built-in) Pattern sheet (1) Insulation cover drain (1) Insulation (2) Insulation Insulation pipe cover band (1) (2) Cable-tie (5) Flexible hose (1) Insulation drain sub (1) Owner’s Instructions (1) Installation manual (1) Insulation B (2) Drain Socket (1) Owner’s Instructions (1) Insulation drain hose (2) (5) Duct type (High pressure) Pattern sheet (1) Insulation A (2) (6) Wall-mounted type Installation plate (1) Cement nai
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 10 V. Installation 1.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 11 1-5. Installation (1) Indoor unit (Example; 4-way cassette type) 1) Place the pattern sheet on the ceiling at the spot where you want to install the indoor unit. Note ◆ Since the diagram is made of paper, it may shrink or stretch slightly due to temperature or humidity. For this reason, before drilling the holes maintain the correct dimensions between the markings.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 12 V. Installation 1. Product (2) Outdoor unit The outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration, particularly if the outdoor unit is to be installed in a location exposed to strong winds or at a height, the unit must be fixed to an appropriate support(wall or ground). 1) Fix the outdoor unit with anchor bolts. ◆ The anchor bolt must be 20mm or higher from the base surface.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 13 2. Panel 2-1. 1-way cassette type (1) Accessories M4x12 tapped screw (6) M5x16 bolt (4) Wireless remote controller (1) Battery (2) STS 2S-2x10 tapped screw (2) Remote control Owner’s holder (1) instructions (1) (2) Installation 1) Open the front grille by pushing tabs on the grille. 2) Remove safety clips to open the grille completely.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 14 V. Installation 2. Panel 4) Install the air flow blade. ① ➁ 4-1 Fix the right part of the blade to the indoor unit. 4-2 Fix the other side of the blade. IMPORTANT ◆ If the direction is incorrect, the blade will not be inserted smoothly. Check that prominence of the right side has a small rectangular groove. ➂ 4-3 Fix the middle part of the blade by pushing slightly the middle tab in the indoor unit.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 15 2-2. 4-way cassette type (1) Accessories Wireless remote controller (1) Battery (2) 4x12 Tapped screw (2) Bolt (4) Owner’s Owner’s Remote control instructions (1) instructions (1) holder (1) Air blocking kit (1) Must be separately purchased (2) Installation 1) Open the electrical component box cover removing the screws. 2) Install the panel using two hooks on the both sides of the indoor unit.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 16 V. Installation 2. Panel 2-3. Duct type (Built-in) (1) Accessories Tapped screw (6) Fixing bracket (1 or 2) (2) Installation 1) Separate the front grille from the panel. 1-1 Push the lever of front grille right and left to lift it up and then open it. 1-2 Take out the safety clip at the both sides of front grille and separate the front grille. 2) Insert panel fixing screws(4EA or 5EA) and tighten them temporarily. Leave space of approx.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 17 3) Attach the panel to the indoor unit, then push it to right or left to secure the panel. Narrow side of hole on the panel must be inserted between the screw and the indoor unit. 4) Adjust the location of panel so that there is no gap between the panel and ceiling, then tighten the screw completely. 5) Install the fixing bracket. Each air filter needs its own bracket.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 18 V. Installation 3. Connecting the indoor unit refrigerant pipe There are two refrigerant pipes of differing diameters: ◆ A smaller one for the liquid refrigerant ◆ A larger one for the gas refrigerant ◆ The inside of copper pipe must be clean & has no dust. 1) Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe, tightening the nuts, first manually and then with a wrench, a spanner applying the following torque.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 19 Cutting/Flaring the Pipes 1) Make sure that you have the required tools available (pipe cutter, reamer, flaring tool and pipe holder). 2) If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle with the side of the pipe. Refer to the illustrations below for examples of edges cut correctly and incorrectly.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 20 V. Installation 4. Drain hose installation (Example;4-way cassette type) Care must be taken when installing the drain hose for the indoor unit to ensure that any condensate water is correctly drained outside. 1) Insert the flexible hose to the drain hose port. Note ◆ Attach the drain hose to the drain hose port with an adhesive for PVC and tape to prevent water leaks, then secure the hose with a band etc..
DVM E-D/B(chapter5)-E<03759 Note 3/21/02 7:40 PM Page 21 ◆ If a concentrated drain hose is installed, refer to the figure below. Drain clamp 1/100 or more slope 100mm or more Air ventilation Concentrated drain hose Testing the drainage You should test the drainage after completing the installation. Prepare a little water about 2.0 liter. 1) Remove two screws on the cover water supply intake and pull out the cover. Cover water supply intake 2) Pour water into the indoor unit as shown in figure.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 22 V. Installation 5. Drain pump installation-optional (Example;Low-silhouette duct type) 5-1. Accessories Drain pump & Float switch (1) M4x12 Tapped screw (4) Cable-tie (2) Cable clamp (2) 5-2. Accessories (1) Connect the cable to the electrical component box as shown at the figure. ◆ Connect the drain pump cable to yellow terminal(CN74) and the float switch to black terminal(CN51).
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 23 6. Wiring ■ Caution ● All wiring and parts shall be the rated ones. ● For details of wiring, refer to the circuit diagram attached onto the outdoor unit. ● The electrical work shall be performed by the qualified electrical worker. ● The circuit diagram for wiring shows only the concept and so the details for actual work is not described.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 24 V. Installation 6. Wiring 6-2. Cable specification for outdoor unit Power supply Outdoor unit 3 phase Power supply Max/Min (V) MCCB 5.0HP 380V/60Hz Frame:30A ± 10% V Trip:20A or less 380-415V/50Hz single phase ELB 20A power cable wire length Power supply Max/Min (V) MCCB power cable ELB 3.5mm2, less than CV, 3wires 16m 1.6mm, IV, 1wire 5.5mm2, 16~26m CV, 3wires 5.5mm , less than CV, 3wires 18m 2 3 6.0~8.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 25 6-5. Connection cord wiring diagram Indoor unit 1 Indoor unit 2 Indoor unit 3 Outdoor unit ● The communication cable shall be wired as follows: ● When the communication cable exceeds the specified length, the operation of air conditioner may be impossible due to the trouble of communication between indoor and outdoor unit.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 26 V. Installation 6. Wiring 6-7.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 27 (2) Typical wiring error 1) Star wiring connection to some of the indoor units Outdoor unit Indoor unit F1 F2 V 27 Wired remote controller F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 28 V. Installation 6.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 29 3) Reverse wiring between indoor and outdoor units Outdoor unit Indoor unit F1 F2 Wired remote controller F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 Reverse V 29
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 30 V. Installation 6.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 31 5) Reverse wiring between indoor units Outdoor unit Indoor unit F1 F2 Reverse V 31 Wired remote controller F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 32 V. Installation 6.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 33 7. Piping and refnet joint selection 7-1.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 34 V. Installation 7. Piping and refnet joint selection 7-3. Refnet joint selection (1) Selection method of first refnet joint from the outdoor unit The first refnet joint (joint A) from the outdoor unit shall be selected according to the outdoor unit model. Refnet joint model Length (mm) Diameter (mm) A B C D E F G H I J K MXJ-0906A 420 80 9.7 - - 9.7 6.5 - 9.7 6.5 - MXJ-1206A 420 80 12.8 - - 12.8 9.7 6.5 12.8 9.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 35 8. Charge/recovery of refrigerant 8-1. Refrigerant charging (1) Outdoor unit is charged with refrigerant when being delivered but additional refrigerant shall be charged for some part of system. (2) After completion of vacuum, keep the following instructions to fill the refrigerant into the service port. 1) Check whether the stop valve of liquid and gas side are completely closed.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 36 V. Installation 8. Charge/recovery of refrigerant 8-2. Additional refrigerant amount calculation method (1) The amount of refrigerant filled in the outdoor when the product is delivered (on the base of piping 10 m) (2) Additional amount of refrigerant as per the pipe diameter and length (liquid pipe based) Pipe diameter (mm) 6.35 9.52 12.70(✻✻040✻✻~ ✻✻075✻✻) 12.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 37 8-3. Recovery of refrigerant (1) Close the service valve of liquid side and then press the refrigerant recovery button on outdoor PCB. (2) When the low pressure is getting lower enough, close the service valve to press the refrigerant recovery button again or press key 3. Pressing the button stops the compressor.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 38 V. Installation 9. Testing operation ■ Cautions for operation ● Put the power 6 hours before initial operation so that the crank case heater may be heated. ● When doing the retry of initial operation after main power off, start the operation 2 and half hours after power on. ● If the heater is not heated, the operation can not be started for 2 hours after power on for the protection of compressor. (Ch displays on the PCB display part at the time.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 39 (7) If Ch displays on the PCB display after tracking, it is the state of compressor not preheated, which means the operation is possible after 2 and half hours. (Supply the power and preheat the compressor). (8) If the preheating of compressor is completed, the communication is performed between indoor unit connected and options. It is the normal at the time when the address on the right display is shown as many as shown on the left side display.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 40 V. Installation 10. Cautions for refrigerant leaks 10-1. Introduction The DVM system, like most other air conditioning systems, uses R-22 as its refrigerant.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 41 10-2. Procedure for checking dangerous ■ Concentration Check the dangerous concentration in accordance with steps 1~4 below and take whatever action is necessary. (1) Calculate the amount of refrigerant(kg) charged to each system separately.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 42 V. Installation 10. Cautions for refrigerant leaks 3) Where there is a gas leak detection alarm device linked to a mechanical ventilator in the smallest room then the next smallest room will become the measurement target. Outdoor unit Ventilator Indoor unit Smallest room Second smallest room (3) Calculate the refrigerant density using the results of the calculations in steps 1 and 2 above.
DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 43 (4) Dealing with situations where the result exceeds the dangerous concentration level. Where the installation of a facility results in a concentration in excess of the dangerous concentration level then it may be necessary to revise the system design to some extent or else take one of the following courses of action: Making openings which will allow the air to flow freely into the room.
DVM E-D/B(cover)-E<03759 3/21/02 6:48 PM Page 1 S A M S U N G DVM Air Conditioner Technical Manual DB98-03759A(1) 2002.03.