User Manual

26
AA
Setting an indoor unit address and installation option
Changing a particular option
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
The option mode
you want to change
The tens digit of an
option SEG you will
change
The unit digit of an
option SEG you will
change
Changed value
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0 D
Option
mode
1~6
Tens digit
of SEG
0~9
Unit digit
of SEG
0~9
The
changed
value
0~F
You can change each digit of set option.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
The option mode you
want to change
The tens digit of an
option SEG you will
change
The unit digit of an
option SEG you will
change
Changed value
Indication 0 D 2 1 7 1
• Whenchangingadigitofanindoorunitaddresssettingoption,settheSEG3asA’.
• Whenchangingadigitofindoorunitinstallationoption,settheSEG3as‘2’.
Ex) When setting the ‘buzzer control’ into disuse status.
Note
SEG 3, 4, 5, 6, 8, 9 additional information
When the SEG 3 is set as "1" and follow Auto Change Over for HR only operation, it will operate as follows.
Cooling/Heating mode can be changed when Thermo O status is maintained during the time with SEG9.
A : Set with SEG4(˚C)
B : Set with SEG5(˚C)
C : Set with SEG6(˚C)
D : Set with SEG8(˚C)
Cooling Thermo O
Heating Thermo O
Cooling Thermo On
Heating Thermo On
B C
D
Ts
A
c
a
Temp.
d
b
Standard temp.
for Heating
Standard temp.
for Cooling
Standard temp. for
Heating
Cooling
Standard temp.
for Cooling
Heating
Set temp.
for Auto mode