Test Report issued under the responsibility of www.nemko.com TEST REPORT IEC 60335-2-40 Safety of household and similar electrical appliances Part 2-40: Particular requirements for electrical heat pumps, air conditioners and dehumidifiers Report Reference No. ...................... : 255837 Date of issue....................................... : 2014-03-19 Total number of pages ........................ 100 pages CB/CCA Testing Laboratory Name : Nemko AS Address.....................................
Page 2 of 100 Test item description ....................... : Report No. 255837 Air-conditioner Trade Mark ......................................... : Manufacturer ...................................... : Same as applicant. Samsung Electronics Co., Ltd. Digital Air-solutions Business Team, 129, Samsung-ro, Yeongtong-gu, Suwon-si, Gyeonggi-do, 443-742 Korea, Republic of Model/Type reference ........................
Page 3 of 100 Report No. 255837 Testing procedure and testing location: CB/CCA Testing Laboratory: N/A Testing location/ address ........................ : Associated CB Laboratory: N/A Testing location/ address ........................ : Tested by (name + signature) .......: Approved by (+ signature) .............: Testing procedure: TMP Tested by (name + signature) .......: Jae Hyeon, Kim Approved by (+ signature) ..............: Jae Hong, Park Testing location/ address ........................
Page 4 of 100 Report No.
Page 5 of 100 Report No. 255837 Summary of testing: 5. This test report replaces the previous test report no. 241841 by following; - Revision on the critical component list. Refer to the Table 24.1 in main test report. 6. Heat exchanger of this appliance was tested and evaluated with the refrigerant R410A only in this test report. 7.
Page 6 of 100 Report No. 255837 Copy of marking plate: 1 / 4 Model: AM056FNLDEH (Indoor unit) The artwork below may be only a draft. The use of certification marks on a product must be authorized by the respective NCBs that own these marks. TRF No.
Page 7 of 100 Report No. 255837 Copy of marking plate: 2 / 4 Model: AM045FNLDEH (Indoor unit) The artwork below may be only a draft. The use of certification marks on a product must be authorized by the respective NCBs that own these marks. TRF No.
Page 8 of 100 Report No. 255837 Copy of marking plate: 3 / 4 Model: AM036FNLDCH (Indoor unit) The artwork below may be only a draft. The use of certification marks on a product must be authorized by the respective NCBs that own these marks. - TRF No.
Page 9 of 100 Report No. 255837 Copy of marking plate: 4 / 4 Model: AM028FNLDCH/ AM022FNLDCH (Indoor unit) The artwork below may be only a draft. The use of certification marks on a product must be authorized by the respective NCBs that own these marks. TRF No.
Page 10 of 100 Report No. 255837 Name and address of production-sites (Factories): Factories are introduced as following; No. Address Factory 1: SUZHOU SAMSUNG ELECTRONICS CO., LTD. 501, Suhong East Road, Suzhou City, Jiangsu, 215021 China Factory 2: SUZHOU SAMSUNG ELECTRONICS CO., LTD. 218 Jiepu Road, Industry Park, Suzhou City, Jiangsu, China Factory 3: SAMSUNG ELECTRONICS CO., LTD.
Page 11 of 100 Report No. 255837 Test item particulars .................................................. : Air-conditioner Classification of installation and use............................ : Fixed / Stationary appliance / Built-in duct type Supply Connection ....................................................... : Type Y attachment ...................................................................................... : ....................................................................................
Page 12 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 5 GENERAL CONDITIONS FOR THE TESTS 5.2 Result Verdict — Tests performed according to cl. 5, e.g. nature of supply, sequence of testing, etc. All the tests are conducted according to this standard. If the test of annex D has to be carried out, an additional appliance may be used (IEC 60335-1/A1) Not applicable. Tests of clause 21 carried out on separate samples.
Page 13 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 5.101 Motor-compressor subjected to relevant test of clause 19 of IEC 60335-2-34, unless (IEC 60335-2-40) Not checked in the appliance. For the relevant tests of indoor unit, the outdoor unit was installed equipped with a motor-compressor which is approved by NEMKO employing a non-flammable refrigerant of R410A. motor-compressor comply with that standard (IEC 60335-2-40) Verdict N/A N/A 5.
Page 14 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Model or type reference ...........................................: (Indoor unit) a) AM056FNLDEH; b) AM045FNLDEH; c) AM036FNLDCH; d) AM028FNLDCH; e) AM022FNLDCH Symbol 5172 of IEC 60417, for class II appliances Class I appliance. Verdict P N/A Symbol IEC 60417-5036, for the enclosure of Not intended to be connected electrically-operated water valves in external to the water mains.
Page 15 of 100 Report No. 255837 IEC 60335-2-40 Clause 7.2 7.3 Requirement – Test Result Verdict Additional warning symbol (flame symbol: B.3.2 of ISO 3864) placed on nameplate of unit near declaration of refrigerant type and charge information. Perpendicular height be at least 10 mm, and symbol need not be in colour (IEC 60335-2-40/A1) N/A Following warning also applied to appliance when flammable refrigerant employed.
Page 16 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 7.6 Correct symbols used Correct symbols are used. 7.7 7.8 Verdict P Flammable refrigerant, warning symbol B.3.2 of Intended for the use of a nonISO 3864, including colour and format, permanently flammable refrigerant. placed on appliance.
Page 17 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Instructions state that (IEC 60335-1/A2): 7.12.1 Verdict — - Appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction (IEC 60335-1/A2) Adequately described similar sentences on user manual.
Page 18 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 7.12.2 Stationary appliances not fitted with means for disconnection from the supply mains having a contact separation in all poles that provide full disconnection under overvoltage category III, the instructions state that means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules N/A 7.12.
Page 19 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 7.13 Instructions and other texts in an official language In English. P 7.14 Marking clearly legible and durable Legible. No curling. No damage. P 7.15 Marking on a main part Marked on the main part. P Marking clearly discernible from the outside, if necessary after removal of a cover Clearly discernible.
Page 20 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 8.1.2 Use of test probe 13 of IEC 61032 through openings Class I appliance. in class 0 appliances and class II appliances/ constructions: no contact with live parts N/A Test probe 13 also applied through openings in earthed metal enclosures having a non-conductive coating: no contact with live parts N/A 8.1.
Page 21 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 10 POWER INPUT AND CURRENT 10.1 Power input at normal operating temperature, rated voltage and normal operation not deviating from rated power input by more than shown in table 1 (See appended table) P Deviation of appliance with one or more rated voltage ranges (IEC 60335-1/A2) Rated: 220 – 240 V or 208 – 230 V Measured at arithmetic mean value of the rated voltage range.
Page 22 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 11.2.2 Appliance without supplementary heaters, air outlet used (IEC 60335-2-40) 11.3 Temperature rise determine by thermocouples or resistance method (IEC 60335-2-40) By thermocouple method and resistance method. P 11.4 Test performed at supply voltage between 0,94 and 1,06 times the rated voltage (IEC 60335-2-40) Tested as this clause.
Page 23 of 100 Report No. 255837 IEC 60335-2-40 Clause 13.3 14 Requirement – Test Result Leakage current measurements (IEC 60335-2-40) (See appended table) Verdict P Appliance disconnected from supply and insulation is Applied test voltages to each immediately subjected to voltage having frequency insulation as specified.
Page 24 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 15.101 Spillage test as specified (IEC 60335-2-40/A2) Not accessible to the general public. Described on the installation manual it shall be installed at a level of 2,5 m above the floor or grade level. After spillage completed, appliance withstand test of clause 16 (IEC 60335-2-40/A2) Verdict N/A N/A 16 LEAKAGE CURRENT AND ELECTRIC STRENGTH — 16.
Page 25 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result P Electronic circuits so designed and applied that a fault will not render the appliance unsafe (electric shock, fire or mechanical hazard, dangerous malfunction) (test 19.11 and 19.12) (IEC 60335-2-40) 19.2 Verdict Test of appliance with motor rotors, other than motor-compressors, operated for 15 days (360 h) or until protection device opens circuit (IEC 60335-2-40) Fan motor for indoor unit. Thermally protected.
Page 26 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 19.7 Test of air to air appliances at rated voltage or at the Results: No hazard. upper limit of the rated voltage range. Dry-bulb No severe temperature rise. temperature is 5 K below values specified by manufacturer (IEC 60335-2-40) P Test with the dry-bulb temperature 10 K over the values specified by manufacturer (IEC 60335-2-40) (see appended table) Results: No hazard. No severe temperature rise. P 19.
Page 27 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 19.11.1 Before applying the fault conditions a) to f) in 19.11.2, it is checked if circuits or parts of circuit meet both of following conditions (IEC 60335-2-40): 19.11.
Page 28 of 100 Report No. 255837 IEC 60335-2-40 Clause 19.12 Requirement – Test Result PTC’s, NTC’s and VDR’s resistors not short-circuited if used as specified by manufacturer (IEC 60335-2-40) P If safety of appliance for any of fault conditions specified in clause 19.11.
Page 29 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Possible heating test in overturned position; temperature rise does not exceed values shown in table 9 20.2 Verdict N/A Moving parts adequately arranged or enclosed as to Adequately arranged and provide protection against personal injury protected.
Page 30 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Verdict The insulation is raised to the temperature measured during the test of clause 11 (IEC 60335-1/A1) N/A The surface of the insulation is then scratched by means of a hardened steel pin, the end of which has the form of a cone with an angle of 40 °.
Page 31 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result - a statement in the instruction sheet that a disconnection incorporated in the fixed wiring is to be provided - an appliance inlet 22.3 Verdict P No appliance inlet.
Page 32 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 22.7 Adequate safeguards against the risk of excessive pressure in appliances provided with steam-producing devices No steam-producing devices. 22.8 Electrical connections not subject to pulling during cleaning of compartments to which access can be gained without the aid of a tool, and that are likely to be cleaned in normal use 22.
Page 33 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 22.14 No ragged or sharp edges creating a hazard for the user in normal use, or during user maintenance No ragged or sharp edges creating a hazard for the user in normal use. Cooling fins are allowed to be used for its function. Verdict P No exposed pointed ends of self tapping screws etc., No exposed pointed ends of liable to be touched by the user in normal use or self tapping screws etc.
Page 34 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 22.26 The insulation between parts operating at safety extra-low voltage and other live parts complies with the requirements for double or reinforced insulation N/A 22.27 Parts connected by protective impedance separated by double or reinforced insulation N/A 22.
Page 35 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 22.33 Conductive liquids that are or may become accessible in normal use are not in direct contact with live parts No conductive liquids.
Page 36 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Unless appliance can operate continuously, automatically or remotely without giving rise to a hazard, appliances for remote operation being fitted with a switch. Actuating member of switch being easily visible and accessible (IEC 60335-1/A2) Verdict N/A 22.41 No components, other than lamps, containing mercury 22.42 Protective impedance consisting of at least two separate components N/A Values specified in 8.1.
Page 37 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Manual setting and visual indication not necessary on appliances that can operate as follows, without giving rise to a hazard (IEC 60335-1/A2): Verdict — - operate continuously (IEC 60335-1/A2), N/A - operate automatically, or (IEC 60335-1/A2) N/A - be operated remotely (IEC 60335-1/A2) N/A 22.
Page 38 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Container shiw no deformation which result in a hazard (IEC 60335-2-40) Verdict N/A 22.109 Replacement of non-self-resetting thermal cut-outs does not damage other connections (IEC 60335-2-40) No non-self-resetting thermal cut-outs. N/A 22.
Page 39 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Verdict All electrical components that could be a source of ignition and which could function under normal conditions or in the event of a leak, comply with one of the following (IEC 60335-2-40/A1): — - IEC 60079-15:2001, Cl. 9 to 26, for group IIA gases Intended for the use of a nonor the refrigerant used or an applicable standard flammable refrigerant.
Page 40 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 23 INTERNAL WIRING 23.1 Wireways smooth and free from sharp edges Wireways are smooth and free from sharp edges. P Wires protected against contact with burrs, cooling fins etc. Wires not in contact with cooling fins. P Wire holes in metal well rounded or provided with bushings Well rounded.
Page 41 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result clamping means so constructed that there is no risk of bad contact due to cold flow of the solder Verdict N/A 23.10 The insulation and sheath of internal wiring, incorporated in external hoses for the connection of an appliance to the water mains, at least equivalent to that of light polyvinyl chloride sheathed flexible cord (60227 IEC 52) (IEC 60335-1/A1) 24 COMPONENTS 24.
Page 42 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 24.1.4 Automatic controls complying with IEC 60730-1 with relevant part 2. The number of cycles of operation being: 24.1.6 Verdict — - thermostats: ................................................. 10 000 N/A - temperature limiters: ...................................... 1000 N/A - self-resetting thermal cut-outs (IEC 60335-2-40): ........................................................................ 3000 24.1.
Page 43 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 24.1.7 Remote operation of appliance via telecommunication network, relevant standard for telecommunication interface circuitry in appliance is IEC 62151 (IEC 60335-1/A2) No such remote operation. N/A 24.1.8 Standard for thermal links IEC 60691 (IEC 60335-1/A2) Incorporated with terminal block. Complying with IEC 60691.
Page 44 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 24.7 Hose-sets for connection of appliances to the water mains, complying with IEC 61770 and supplied with the appliance (IEC 60335-1/A1) Not intended to be connected to the water mains. N/A 24.101 Replaceable parts of thermal control devices identified by marking (IEC 60335-2-40) Not considered. N/A 25 SUPPLY CONNECTION AND EXTERNAL FLEXIBLE CORDS — 25.
Page 45 of 100 Report No. 255837 IEC 60335-2-40 Clause 25.4 25.
Page 46 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Supply cords for outdoor use not lighter than polychloroprene sheathed flexible cord (60245 IEC 57) (IEC 60335-2-40) Interconnection cord for connecting the indoor unit into the outdoor unit. Not lighter than the code designation as following; 60245 IEC 57 (IEC) H05RN-F (CENELEC) P 25.8 Nominal cross-sectional area of supply cords according to table 11; rated current (A); cross-sectional area (mm²) ....................
Page 47 of 100 Report No. 255837 IEC 60335-2-40 Clause 25.15 25.16 Requirement – Test Result Verdict - separation of the conductor from its terminal N/A - loosening of any cord guard N/A - damage, within the meaning of the standard, to the cord or the cord guard N/A - broken strands piercing the insulation and becoming accessible N/A Conductors of the supply cord relieved from strain, twisting and abrasion by use of cord anchorage Adequate cord anchorages are used.
Page 48 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Conductors not moved more than 1 mm in terminals Verdict N/A 25.17 Adequate cord anchorages for type Y and Z attachment Type Y attachment. P 25.18 Cord anchorages only accessible with the aid of a tool, or Accessible with a tool only. P so constructed that the cord can only be fitted with the aid of a tool 25.19 Type X attachment, glands not used as cord anchorage in portable appliances P Type Y attachment.
Page 49 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Terminals only accessible after removal of a non-detachable cover Accessible after the cover detached with a tool. However, earthing terminals may be accessible if a Earthing terminal of indoor unit. tool is required to make the connections and means are provided to clamp the wire independently from its connection (IEC 60335-1/A1) 26.2 26.
Page 50 of 100 Report No. 255837 IEC 60335-2-40 Clause 26.
Page 51 of 100 Report No. 255837 IEC 60335-2-40 Clause 27.
Page 52 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 27.6 Printed conductors of printed circuit boards not used Stationary appliance. to provide earthing continuity in hand held appliances (IEC 60335-1/A2) N/A In other appliance provide earthing continuity, if at least two tracks used with independent soldering points and appliance complies with requirements of clause 27.5 for each circuit (IEC 60335-1/A2) N/A 28 SCREWS AND CONNECTIONS 28.
Page 53 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Thread-cutting (self-tapping) screws and thread rolling screws only used for electrical connections if they generate a full form standard machine screw thread (IEC 60335-1/A2) However, thread-cutting (self-tapping) screws not used if they likely to be operated by user or installer (IEC 60335-1/A2) N/A Not intended to be operated by users.
Page 54 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result For motor-compressor not complying with IEC 60335-2-34, additions and modifications as specified (IEC 60335-2-40) 29.
Page 55 of 100 Report No. 255837 IEC 60335-2-40 Clause 29.1.5 29.2 Requirement – Test Result Clearance between surfaces of PTC heating elements may be reduced to 1 mm No PTC heating elements.
Page 56 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 29.2.3 Creepage distances of reinforced insulation at least double as specified for basic insulation in table 17 P 29.2.
Page 57 of 100 Report No. 255837 IEC 60335-2-40 Clause 30.2 Requirement – Test Result External parts: at 40 °C plus the maximum temperature rise determined during the test of clause 11, or at 75 °C, whichever is the higher; temperature (°C).......................................................: (See appended table) P Parts supporting live parts: at 40 °C plus the maximum temperature rise determined during the test of clause 11, or at 125 °C, whichever is the higher; temperature (°C) ..............
Page 58 of 100 Report No.
Page 59 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result 30.2.4 Base material of printed circuit boards subjected to needle-flame test of annex E (IEC 60335-1/A2) Tested in accordance with Annex E. Test not carried out by specified items ....................: 31 — Adequately protected.
Page 60 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Verdict If the appliance incorporates inductive coupling between two parts that are detachable from each other, the appliance is supplied from the supply mains with the detachable part removed N/A 3.6.2 Part to be removed in order to discard the battery is not considered to be detachable N/A 5.101 Appliances supplied from the supply mains tested as specified for motor-operated appliances N/A 7.
Page 61 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Verdict After the test, the requirements of 8.1, 15.1.1, 16.3 and clause 29 are met N/A 22.3 Appliances having pins for insertion into socket-outlets tested as fully assembled as possible N/A 25.13 An additional lining or bushing not required for interconnection cords operating at safety extra-low voltage N/A 30.2 For parts of the appliance connected to the supply mains during the charging period, 30.2.
Page 62 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test F ANNEX F (NORMATIVE) CAPACITORS — Capacitors likely to be permanently subjected to the supply voltage, and used for radio interference suppression or voltage dividing, comply with the following clauses of IEC 60384-14, with the following modifications: — 1.5 Terminology — 1.5.3 Class X capacitors tested according to subclass X2 1.5.4 This subclause is applicable 1.6 Marking Items a) and b) are applicable 3.
Page 63 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 4.18 Active flammability test Result This subclause is applicable G Verdict — N/A ANNEX G (NORMATIVE) SAFETY ISOLATING TRANSFORMERS — The following modifications to this standard are applicable for safety isolating transformers: — 7 Marking and instructions — 7.
Page 64 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test 15.3 Applicable for full disconnection and micro-disconnection 17 Endurance 20 Result N/A — Compliance is checked on three separate appliances or switches N/A For 17.2.4.4, the number of cycles is 10 000, unless otherwise specified in 24.1.
Page 65 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test K ANNEX K (NORMATIVE) OVERVOLTAGE CATEGORIES M Verdict — The information on overvoltage categories is extracted from IEC 60664-1 Considered. P Overvoltage category is a numeral defining a transient overvoltage condition Considered.
Page 66 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Result Degrees of pollution in the microenvironment — For evaluating creepage distances, the following degrees of pollution in the microenvironment are established: — - pollution degree 1: no pollution or only dry, non-conductive pollution occurs.
Page 67 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test O ANNEX O (INFORMATIVE) SELECTION AND SEQUENCE OF THE TESTS OF CLAUSE 30 — Description of tests for determination of resistance to Considered.
Page 68 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test Q ANNEX Q (INFORMATIVE) SEQUENCE OF TESTS FOR THE EVALUATION OF ELECTRONIC CIRCUITS — Description of tests for appliances incorporating electronic circuits (IEC 60335-1/A2) P ANNEX R (NORMATIVE) SOFTWARE EVALUATION — Software evaluated in accordance with the following clauses of annex H of IEC 60730-1, as modified: — R H.2 H.7 H.11.12 H.11.12.7 Definitions Result Not considered. Verdict N/A Only definitions H.2.
Page 69 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test AA ANNEX AA (INFORMATIVE) (IEC 60335-2-40) EXAMPLES FOR OPERATING TEMPERATURES OF THE APPLIANCE — BB ANNEX BB (NORMATIVE) (IEC 60335-2-40) SELECTED INFORMATION ABOUT REFRIGERANTS — CC ANNEX CC (INFORMATIVE) (IEC 60335-2-40/A1) TRANSPORTATION, MARKING AND STORAGE FOR UNITS THAT EMPLOY FLAMMABLE REFRIGERANTS — CC.1 Transport of equipment containing flammable refrigerants (IEC 60335-2-40/A1) CC.
Page 70 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test DD.14 Recovery (IEC 60335-2-40/A1) EE ANNEX EE (NORMATIVE) (IEC 60335-2-40/A1) PRESSURE TESTS EE.1 General (IEC 60335-2-40/A1) Result Verdict N/A — Test location: Considered heat exchangers of indoor unit. P Test result: No leakage. No hazard. EE.2 Pressure test value determined under testing carried out in clause 11 (IEC 60335-2-40/A1) N/A EE.
Page 71 of 100 Report No. 255837 IEC 60335-2-40 Clause Requirement – Test GG.7 The appliance shall then be tested with a maximum water flow under the conditions described in g) (IEC 60335-2-40/A1) Result Verdict N/A ANNEX EMF (EN 62233) The Tested product also complies to the requirements of EN 62233:2008 — Measuring distance (cm)..........................................: 30 cm, Around. P Background noise level (%) .....................................: Less than 0.
Page 72 of 100 10.1 TABLE: Power input deviation 1) P P rated (W) P measured (W) ∆P (%) Required ∆P (%) Remark 220V~ 50Hz 95 88.66 -6.7 +20 Pass 230V~ 50Hz 95 94.62 -0.4 +20 Pass 240V~ 50Hz 95 100.86 +6.2 +20 Pass Input deviation of/at: 10.2 Report No. 255837 TABLE: Current deviation 1) P I rated (A) I measured (A) ∆I (%) Required ∆I (%) Remark 220V~ 50Hz 0.53 0.490 -7.5 +20 Pass 230V~ 50Hz 0.53 0.529 -0.2 +20 Pass 240V~ 50Hz 0.53 0.562 +6.
Page 73 of 100 10.1 TABLE: Power input deviation 1) P P rated (W) P measured (W) ∆P (%) Required ∆P (%) Remark 220V~ 50Hz 90 83.24 -7.5 +20 Pass 230V~ 50Hz 90 90.69 +0.8 +20 Pass 240V~ 50Hz 90 96.26 +7.0 +20 Pass Input deviation of/at: 10.2 Report No. 255837 TABLE: Current deviation 1) P I rated (A) I measured (A) ∆I (%) Required ∆I (%) Remark 220V~ 50Hz 0.52 0.484 -6.9 +20 Pass 230V~ 50Hz 0.52 0.520 0.0 +20 Pass 240V~ 50Hz 0.52 0.548 +5.
Page 74 of 100 10.1 TABLE: Power input deviation 1) P P rated (W) P measured (W) ∆P (%) Required ∆P (%) Remark 208V~ 60Hz 75 70.3 -6.3 +20 Pass 220V~ 60Hz 75 75.6 +0.8 +20 Pass 230V~ 60Hz 75 79.2 +5.6 +20 Pass Input deviation of/at: 10.2 Report No. 255837 TABLE: Current deviation 1) P I rated (A) I measured (A) ∆I (%) Required ∆I (%) Remark 208V~ 60Hz 0.35 0.326 -6.9 +20 Pass 220V~ 60Hz 0.35 0.352 +0.6 +20 Pass 230V~ 60Hz 0.35 0.373 +6.
Page 75 of 100 10.1 TABLE: Power input deviation 1) P P rated (W) P measured (W) ∆P (%) Required ∆P (%) Remark 208V~ 60Hz 60 55.2 -8.0 +20 Pass 220V~ 60Hz 60 59.6 -0.7 +20 Pass 230V~ 60Hz 60 63.2 +5.4 +20 Pass Input deviation of/at: 10.2 Report No. 255837 TABLE: Current deviation 1) P I rated (A) I measured (A) ∆I (%) Required ∆I (%) Remark 208V~ 60Hz 0.34 0.314 -7.7 +20 Pass 220V~ 60Hz 0.34 0.341 +0.4 +20 Pass 230V~ 60Hz 0.34 0.362 +6.
Page 76 of 100 10.1 TABLE: Power input deviation 1) P P rated (W) P measured (W) ∆P (%) Required ∆P (%) Remark 208V~ 60Hz 47 44.2 -6.1 +20 Pass 220V~ 60Hz 47 47.3 +0.7 +20 Pass 230V~ 60Hz 47 49.8 +6.0 +20 Pass Input deviation of/at: 10.2 Report No. 255837 TABLE: Current deviation 1) P I rated (A) I measured (A) ∆I (%) Required ∆I (%) Remark 208V~ 60Hz 0.32 0.300 -6.4 +20 Pass 220V~ 60Hz 0.32 0.319 -0.3 +20 Pass 230V~ 60Hz 0.32 0.339 +6.
Page 77 of 100 11.8 Report No. 255837 TABLE: Heating test, thermocouples P Test voltage (V) ........................................................: 254,4V (=1,06 x 240V) 50Hz 243,8V (=1,06 x 230V) 60Hz Ambient, t 1 (°C) ........................................................: Indoor (DB / WB): 27 / 19 Outdoor (DB / WB): 35 / 24 Ambient, t 2 (°C) ........................................................
Page 78 of 100 11.8 Report No. 255837 TABLE: Heating test, thermocouples P Test voltage (V) ........................................................: 254,4V (=1,06 x 240V) 50Hz 243,8V (=1,06 x 230V) 60Hz Ambient, t 1 (°C) ........................................................: Indoor (DB / WB): 29 / 19 Outdoor (DB / WB): 46 / 24 Ambient, t 2 (°C) ........................................................
Page 79 of 100 11.8 Report No. 255837 TABLE: Heating test, thermocouples P Test voltage (V) ........................................................: 254,4V (=1,06 x 240V) 50Hz 243,8V (=1,06 x 230V) 60Hz Ambient, t 1 (°C) ........................................................: Indoor (DB / WB): 20 / 15 Outdoor (DB / WB): 7 / 6 Ambient, t 2 (°C) ........................................................: Indoor (DB / WB): 20 / 15 Outdoor (DB / WB): 7 / 6 Thermocouple locations T (°C) Max.
Page 80 of 100 13.2 Report No. 255837 TABLE: Leakage current P Heating appliances: 1,15 x rated power input ...... : - Motor-operated and combined appliances: 1,06 x rated voltage ............................................... : 254,4V (=1,06 x 240V) Leakage current between Stand-by mode I (mA) Max. allowed I (mA) -- -- Live line to heat exchanger (Stand-by) 0.60 10.0 1) Neutral line to heat exchanger (Stand-by) 0.60 10.
Page 81 of 100 16.2 Report No. 255837 TABLE: Leakage current P Single phase appliances: 1,06 x rated voltage ..... : 254,4V (=1,06 x 240V) Three phase appliances 1,06 x rated voltage divided by √3: ......................................................... : - Leakage current between I (mA) Lines to heat exchanger 0.90 Lines to metal foil of non-metallic part 0.01 Max. allowed I (mA) 10.0 1) 0.
Page 82 of 100 19.5 Report No. 255837 TABLE: Abnormal operation Test voltage (V)........................................................ : P 240V 50/60Hz Ambient, t 1 (°C) ........................................................ : Indoor (DB / WB): 23 / (15) Outdoor (DB / WB): 23 / (15) Ambient, t 2 (°C) ........................................................ : Indoor (DB / WB): 23 / (15) Outdoor (DB / WB): 23 / (15) Thermocouple locations T (°C) Max.
Page 83 of 100 19.5 Report No. 255837 TABLE: Abnormal operation Test voltage (V)........................................................ : P 240V 50/60Hz Ambient, t 1 (°C) ........................................................ : Indoor (DB / WB): 23 / (15) Outdoor (DB / WB): 23 / (15) Ambient, t 2 (°C) ........................................................ : Indoor (DB / WB): 23 / (15) Outdoor (DB / WB): 23 / (15) Thermocouple locations T (°C) Max.
Page 84 of 100 19.7 Report No. 255837 TABLE: Abnormal operation P Test voltage (V) ........................................................: 240V 50/60Hz Ambient, t 1 (°C) ........................................................: Indoor (DB / WB): 39 / (29) Outdoor (DB / WB): 56 / (34) Ambient, t 2 (°C) ........................................................: Indoor (DB / WB): 39 / (29) Outdoor (DB / WB): 56 / (34) Thermocouple locations T (°C) Max.
Page 85 of 100 19.10 Report No. 255837 TABLE: Abnormal operation P Test voltage (V) ........................................................: 240V 50/60Hz Ambient, t 1 (°C) ........................................................: Indoor (DB / WB): 29 / 19 Outdoor (DB / WB): 46 / 24 Ambient, t 2 (°C) ........................................................: Indoor (DB / WB): 29 / 19 Outdoor (DB / WB): 46 / 24 Thermocouple locations T (°C) Max. T (°C) Enclosure of indoor fan motor 98.
Page 86 of 100 19.10 Report No. 255837 TABLE: Abnormal operation P Test voltage (V) ........................................................: 240V 50/60Hz Ambient, t 1 (°C) ........................................................: Indoor (DB / WB): 29 / 19 Outdoor (DB / WB): 46 / 24 Ambient, t 2 (°C) ........................................................: Indoor (DB / WB): 29 / 19 Outdoor (DB / WB): 46 / 24 Thermocouple locations T (°C) Max. T (°C) Enclosure of indoor fan motor 45.
Page 87 of 100 19.11 Report No. 255837 TABLE: abnormal operation The following fault conditions are introduced: Test input (V) P 240V 50/60Hz (at upper rated voltage) Component Fault condition Result Short circuit Open circuit Electrolytic capacitor (CE105) S-c - - Max. temp. of IC101: 37.3°C - No excessive temperature rises. - No hazard. Electrolytic capacitor (CE107) S-c - - Max. temp. of IC101: 40.2°C - No excessive temperature rises. - No hazard. Diode (D101) S-c - - Max. temp.
Page 88 of 100 24.1 Report No. 255837 TABLE: Components P Object / part No. Manufacturer/ trademark Type / model Technical data Standard Mark(s) of 1) conformity Fan motor for indoor unit Changzhou Regal Beloit Sinya Motor Co., Ltd YSK110-504SM 220 – 240V~ 50Hz, 50W Cu winding, Cl. B (Cl. 130) IEC 60335-1 IEC 60335-2-40 Checked in the appliance Thermal protector (sel-resetting thermal cut-out) Sensata Technologies 17AM 250V~ Open: 135 °C IEC 60730-1 IEC 60730-2-2 DEKRA (KEMA) Alt.
Page 89 of 100 24.1 Report No. 255837 TABLE: Components Object / part No. Manufacturer/ trademark P Type / model Technical data Standard Mark(s) of 1) conformity 17AM 250V~ Open: 135 °C IEC 60730-1 IEC 60730-2-2 VDE 450V, 3.0uF, 50/60Hz P2, T85 IEC 60335-1 IEC 60335-2-40 IEC 60252-1 Checked in the appliance VDE Alt. Anhui Feida CBB61-P Industry Stock Co., Ltd. 450V, 3.0uF, 50/60Hz P2, T85 IEC 60335-1 IEC 60335-2-40 IEC 60252-1 Checked in the appliance TUV Rh Alt. Nuintek Co., Ltd.
Page 90 of 100 24.1 Report No. 255837 TABLE: Components Object / part No. Manufacturer/ trademark Alt. Dong-A Bestech Co., Ltd. P Type / model Technical data Standard Mark(s) of 1) conformity DAF-4P 300V, 25A IEC 60335-1 IEC 60335-2-40 IEC 60998-1 Checked in the appliance VDE Thermal link incorporated with terminal block Tamura Thermal Device Corp. N1F 250V~ 1A Tf: 86°C IEC 60691 VDE EEV (Electronic expansion valve) Zhejiang Sanhua Co., Ltd DPF(O)3.2C08 12Vd.c.
Page 91 of 100 24.1 Report No. 255837 TABLE: Components Object / part No. Manufacturer/ trademark P Technical data Standard Mark(s) of 1) conformity Varistor Thinking Electronic TVR 14561 (VA101, VA102, Industrial Co., Ltd VA103) 560V 4500A 350Vrms T85 IEC 60335-1 IEC 60335-2-40 IEC 61051-1 IEC 61051-2/ -2-2 CECC 42200 CECC 42201 Checked in the appliance VDE Alt. Amotech Co.
Page 92 of 100 24.1 Report No. 255837 TABLE: Components P Object / part No. Manufacturer/ trademark Type / model Technical data Standard Mark(s) of 1) conformity SSR (SSR901) Xiamen Hongfa Electroacoustic Co., Ltd HF5427-12D240A3P Input control: 9.6 – 14.4 Vd.c. Output load: 75 – 264V~ 3A T-operating: 85°C IEC 60335-1 IEC 60335-2-40 IEC 62314 Checked in the appliance TUV Rh Surge absorber (DSA101) Mitsubish Materials Corp. DSA-332M 3300V ±20% Insulation resistance: Min.
Page 93 of 100 24.1 TABLE: Components Object / part No. Manufacturer/ trademark Photocoupler (PC102) Bridge diode (BD101) Report No. 255837 P Type / model Technical data Standard Mark(s) of 1) conformity Alt. NEC Corporation PS2565-1 -55 – 100°C Viso= 3750Vrms IEC 60335-1 IEC 60335-2-40 EN 60747-5-2 Checked in the appliance VDE Alt. Toshiba Corporation TLP351 -40 – 100°C Viso= 3750Vrms IEC 60335-1 IEC 60335-2-40 EN 60747-5-2 Checked in the appliance VDE Alt. SHARP Corp.
Page 94 of 100 24.1 Report No. 255837 TABLE: Components Object / part No. Manufacturer/ trademark Alt. Tyco Electronics (Shenzhen) Co., Ltd. P Type / model Technical data OJ-SS-112DM 250V~, 5A, T70, 6E4 Standard Mark(s) of 1) conformity IEC 60335-1 IEC 60335-2-40 IEC 61810-1 Checked in the appliance VDE, TUV Rh Alt. In & Out Electronic GC-12VDCCorporation A45 250V~, 5A, T75, 1E5 IEC 60335-1 IEC 60335-2-40 IEC 61810-1 Checked in the appliance VDE Alt.
Page 95 of 100 24.1 Report No. 255837 TABLE: Components Object / part No. Manufacturer/ trademark Alt. Hangzhou Ruikai Electronics Co., Ltd. 1) P Type / model Technical data DB26-00131A - 0.55mH - Core: EE2218,C - Bobbin: Phenolic, V-0 - Winding: 2UEW - Cl. B (Cl. 130) Standard Mark(s) of 1) conformity IEC 60335-1 IEC 60335-2-40 IEC 61558-1 IEC 61558-2-16 Checked in the appliance An asterisk indicates a mark which assures the agreed level of surveillance supplementary information: TRF No.
Page 96 of 100 28.1 Report No. 255837 TABLE: Threaded part torque test P Threaded part identification Diameter of thread (mm) Column number (I, II, or III) Applied torque (Nm) Metal screws - for interconnection cord connection on terminal block >3,6 and ≤ 4,1 (Measured: 3,9) II 1,2 Metal screws - for earthing provision >3,6 and ≤ 4,1 (Measured: 3,9) II 1,2 supplementary information: 29.1 P TABLE: Clearances Overvoltage category ......
Page 97 of 100 29.2 Report No.
Page 98 of 100 29.2 Report No.
Page 99 of 100 29.2 Report No. 255837 TABLE: Creepage distances, basic, supplementary and reinforced insulation Working voltage (V) Verdict / Remark Creepage distance (mm) Pollution degree 2 3 Material group Material group 1 I II IIIa/IIIb I II IIIa/IIIb ≤50 0,2 0,6 0,8 1,1 1,4 1,6 1,8 P (min. 1,1) >50 and ≤125 0,3 0,7 1,0 1,4 1,8 2,0 2,2 N/A >125 and ≤250 0,4 1,0 1,4 2,0 2,5 2,8 3,2 P (min. 2,0) >250 and ≤400 0,8 1,6 2,2 3,2 4,0 4,5 5,0 P (min.
Page 100 of 100 30.1 Report No. 255837 TABLE: Ball pressure Part P Test temperature (°C) Impression diameter (mm) Allowed impression diameter (mm) 75 < 1,4 2,0 X-capacitor 125 1,5 2,0 Switching transformer bobbin 125 1,4 2,0 Choke coil bobbin 125 1,6 2,0 Relay 125 1,6 2,0 Capacitor for fan motor 125 1,5 2,0 PCB 125 < 1,4 2,0 Terminal block 125 < 1,4 2,0 AC connector 125 1,5 2,0 Cord anchorage supplementary information: 30.
Page 1 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 ATTACHMENT TO TEST REPORT IEC 60335-2-40 EUROPEAN GROUP DIFFERENCES AND NATIONAL DIFFERENCES Part 2-40: Particular requirements for electrical heat pumps, air conditioners and dehumidifiers Differences according to ............... : EN 60335-2-40:2003 (incl. Corr.:2006) + A11:2004 + A12:2005 + A1:2006 + A2:2009 with EN 60335-1:2002 + A11:2004 + A1:2004 + A12:2006 + A2:2006 + A13:2008 Attachment Form No. ....................
Page 2 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause 15.1.2 Requirement – Test 16.2 Verdict No such water valves. Water valves containing in external hoses for connection of an appliance to water mains, subjected to the test as specified for IPX7 appliances (EN 60335-2-40/A2) N/A Hand-held appliance turned continuously through most unfavourable positions during test N/A Built-in appliances installed according instructions (EN 60335-2-40/A2) 15.
Page 3 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause Requirement – Test 24.1.7 No such remote operation. Remote operation via telecommunication network, relevant standards for telecommunication interface circuitry in appliance EN 41003 and EN 60950-1:2006, Subclause 6.3 (EN 60335-1/A13) N/A 25.
Page 4 of 13 Report No.
Page 5 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause Requirement – Test 25.6 Supply cords of single-phase portable appliances having a rated current not exceeding 13 A provided with a plug according to following: - Class I appliances: Section 107-2-D1, ed.3 1998, standard sheet DK 2-1a Result – Remark No plugs.
Page 6 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause Requirement – Test Result – Remark Verdict National Differences / Deviations for Finland ZA ANNEX ZA (NORMATIVE), SPECIAL NATIONAL CONDITIONS (EN 60335-1, EN 60335-2-40) 25.6 Plugs according to standard sheet C3b not allowed No plugs.
Page 7 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause Requirement – Test Result – Remark Verdict National Differences / Deviations for Iceland ZA ANNEX ZA (NORMATIVE), SPECIAL NATIONAL CONDITIONS (EN 60335-1, EN 60335-2-40) 25.6 Plugs according to standard sheet C3b not allowed No plugs.
Page 8 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause Requirement – Test Result – Remark Verdict National Differences / Deviations for Italy ZA ANNEX ZA (NORMATIVE), SPECIAL NATIONAL CONDITIONS (EN 60335-1, EN 60335-2-40) 25.6 Plugs according to standard sheet C3b not allowed No plugs.
Page 9 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause Requirement – Test Result – Remark Verdict National Differences / Deviations for Norway ZA ANNEX ZA (NORMATIVE), SPECIAL NATIONAL CONDITIONS (EN 60335-1, EN 60335-2-40) 22.2 Second paragraph of this subclause, dealing with single-phase, permanently connected class I appliances having heating elements, not applicable due to supply system No heating elements. N/A 25.
Page 10 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause Requirement – Test Result – Remark Verdict National Differences / Deviations for Sweden ZA ANNEX ZA (NORMATIVE), SPECIAL NATIONAL CONDITIONS (EN 60335-1, EN 60335-2-40) 25.6 Plugs according to standard sheet C2b not allowed No plugs.
Page 11 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause Requirement – Test Result – Remark Verdict National Differences / Deviations for United Kingdom ZA ANNEX ZA (NORMATIVE), SPECIAL NATIONAL CONDITIONS (EN 60335-1, EN 60335-2-40) 25.6 Plugs according to standard sheet C2b not allowed 25.8 No plugs.
Page 12 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause Requirement – Test Result – Remark According to guideline 1/39 of the directive, this exclusion applies to both components and assemblies (refrigerant circuits). This applies to appliances containing vessels (e.g.
Page 13 of 13 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 1 EN 60335-1, EN 60335-2-40 Clause Requirement – Test Result – Remark Verdict The numerical designation designates the size common to all components in the piping system (EN 60335-2-40/A11) N/A If any component exceeds the limits given above, the appliance has to comply with the directive.
Page 1 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test Result - Remark Verdict ATTACHMENT TO TEST REPORT IEC 60335-1 EUROPEAN GROUP DIFFERENCES AND NATIONAL DIFFERENCES Household and similar electrical appliances – Safety – Part 1: GENERAL REQUIREMENTS Differences according to : EN 60335-1:2002 + A11:2004 + A1:2004 + A12:2006 + A2:2006 + A13:2008 + A14:2010 + A15:2011 EN 50366:2003 + A1:2006 or EN 62233:2008 Attachment Form No.
Page 2 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test Result - Remark Where the relevant standard for lampholders and No such components. starterholders specifies gauging and interchangeability requirements at elevated temperatures, the temperature measured during the tests of Clause 11 are used 24.1.
Page 3 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test Result - Remark Verdict - halogen-free thermoplastic compound sheathed cords (H05Z1Z1H2-F, H05Z1Z1-F), for other appliances N/A Cross-linked halogen-free compound sheathed supply cords have properties at least those of cross-linked halogen free compound sheathed cords (H07ZZ-F) N/A 26.
Page 4 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test ZA ANNEX ZA (NORMATIVE), SPECIAL NATIONAL CONDITIONS (EN) — Denmark — 7.12 Requirements regarding marking tag of power supply cord and connection of earthing wire for class I appliances delivered without a plug Result - Remark No plugs. The manufacturer, service agent or similarly qualified person shall use a proper cross sectional area of supply cord and interconnection cord referring to an installation manual.
Page 5 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test Result - Remark — Austria, Finland, Germany, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom 25.6 Plugs according to standard sheet C3b not allowed No plugs. The manufacturer, service agent or similarly qualified person shall use a proper cross sectional area of supply cord and interconnection cord referring to an installation manual. Denmark 25.
Page 6 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test Result - Remark N/A The current for the plug not exceeding the values specified; standard sheet (no.); current (A) : — Ireland 25.6 Only plugs according to Standard Sheets B2 and C5 allowed No plugs. The manufacturer, service agent or similarly qualified person shall use a proper cross sectional area of supply cord and interconnection cord referring to an installation manual.
Page 7 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test Result - Remark — Switzerland 25.6 Supply cords of portable household and similar electrical appliances having a rated current not exceeding 10 A, provided with a plug complying with SEV 1011 or IEC 60884-1 and one of the following dimension sheets: No plugs.
Page 8 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test Result - Remark — Italy 7.1 The voltage is 220 V/380 V 220-240 V~ 50 Hz 230 V covered. These regulations apply to all plugs for domestic use at a voltage of not less than 200 V and allow only plugs complying with I.S. 401:1997, or equivalent, to be fitted to domestic appliances. No plugs.
Page 9 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test ZE ANNEX ZE (INFORMATIVE) SPECIFIC ADDITIONAL REQUIREMENTS FOR APPLIANCES AND MACHINES INTENDED FOR COMMERCIAL USE P 7.1 Business name and full address of the manufacturer and, where applicable, his authorized representative ........................................................: P Model or type reference.........................................: P Serial number, if any..........................................
Page 10 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause 7.12.
Page 11 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test 19.11.4.8 The appliance continues to operate, without causing any hazard to the user, from the same point in its operating cycle at which the voltage fluctuation occurred, or P a manual operation is required to restart it P 20.1 Appliances and their components and fittings have adequate mechanical stability during transportation, assembly, dismantling and any other action involving the appliance P 20.
Page 12 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test 22.ZE.
Page 13 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause 22.ZE.
Page 14 of 14 Report No. 255837 IEC60335_1S – ATTACHMENT 2 Clause Requirement - Test Result - Remark Verdict Result - Remark Verdict Annex EN 50366:2003 + A1:2006 Clause Requirement + Test EMF- ELECTROMAGNETICS FIELDS The tested product also complies with the requirements of EN 50366:2003 + A1:2006 Limit ……………100% See below.
Page 1 of 4 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 3 ATTACHMENT TO TEST REPORT IEC 60335-2-40 National Difference of Australia (AU) in the IECEE Online Bulletin Part 2-40: Particular requirements for electrical heat pumps, air conditioners and dehumidifiers This attachment is based on the fact as following; National Difference of Australia (AU) in the IECEE Online Bulletin. (http://www.iecee.org) No.
Page 2 of 4 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 3 National Difference of Australia (AU) AS/NZS 60335.1:2002 corresponding to IEC 60335-1:2002; am1; am2 Clause Requirement – Test Result 5.2 Replace the last paragraph of NOTE 1 with the following variation: If the tests of annex H are carried out, one switch or one additional appliance is needed. 5.8.1 Replace with the following variation: Appliances for a.c. only are tested with a.c. at 50 Hz, and those for a.c. and d.c. are tested at a.c.
Page 3 of 4 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 3 National Difference of Australia (AU) AS/NZS 60335.1:2002 corresponding to IEC 60335-1:2002; am1; am2 Clause Requirement – Test Result – a rated voltage range that includes: 230 V for single phase appliances; 400 V for polyphase appliances. Rated: 220-240V~ 50Hz Verdict P 7.13 In English. Replace the requirement with the following variation: Instructions and other text required by this standard shall be written in English.
Page 4 of 4 Report No.: 255837 IEC60335_2_40F – ATTACHMENT 3 National Difference of Australia (AU) AS/NZS 60335.1:2002 corresponding to IEC 60335-1:2002; am1; am2 Clause Requirement – Test 24.1 Before Note 1, insert the following variation. NOTE 201 The relevant IEC standard may be replaced with the relevant Australia/New Zealand standard where applicable. 24.1.
Page 1 of 4 IEC60335_2_40F – ATTACHMENT 3 ATTACHMENT TO TEST REPORT IEC 60335-2-40 Schematic wiring diagram/ Circuit diagram Report No.
Page 2 of 4 Report No.
Page 3 of 4 Report No.
Page 4 of 4 Report No.
Page 1 of 7 IEC60335_2_40F – ATTACHMENT 4 ATTACHMENT TO TEST REPORT IEC 60335-2-40 Photos of appliance Report No.
Page 2 of 7 Report No.
Page 3 of 7 Report No.
Page 4 of 7 Report No.
Page 5 of 7 Report No.
Page 6 of 7 Report No.
Page 7 of 7 Report No.