Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
Use of Auto Change
Over for HR only in
Auto mode
(When setting SEG3)
Standard heating
temp. Oset
(When setting SEG3)
Standard cooling
temp. Oset
(When setting SEG3)
Standard for mode
change
Heating
Cooling
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0 5
0
Follow
product
option
0 0 0 0 0 1
1
Use Auto
Change
Over for
HR only
1 0.5 1 0.5 1 1.5
2 1 2 1 2 2
3 1.5 3 1.5 3 2.5
4 2 4 2 4 3
5 2.5 5 2.5 5 3.5
6 3 6 3 6 4
7 3.5 7 3.5 7 4.5
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
(When setting SEG3)
Standard for mode
changing Cooling
Heating mode
(When setting SEG3)
Time required for
mode change
Compensation option
for Long pipe or height
diference between
indoor units
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
1
0 1 0 5 min. 0
Use default
value
1 1.5 1 7 min.
1
1) Height
difference
1)
is more than
30m or
2) Distance
2)
is longer
than 110m
2 2 2 9 min.
3 2.5 3 11 min.
4 3 4 13 min.
2
1) Height
difference
1)
is
15~30mor
2) Distance
2)
is50~110m
5 3.5 5 15 min.
6 4 6 20 min.
7 4.5 7 30 min.
05 series installation option(Detailed)
1)
Height dierence : The dierence of the height between the corresponding indoor uint and the indoor unit installed at the lowest place.
For example, When the indoor unit is installed 40m higher than the indoor unit installed at the lowest place, select the option "1".
2)
Distance : The dierence between the pipe length of the indoor unit istalled at farthest place from an outdoor unit and the pipe length of the
corresponding indoor unit from an outdoor unit.
For example, when the farthest pipe length is 100m and the corresponding indoor unit is 40m away from an outdoor unit, select the option
"2". (100 - 40 = 60m)