3-6. Indoor fan control in the heating mode
Indoor fan is controlled depending on the temperature of indoor heat exchanger in the heating mode.
The temperature of indoor heat exchanger Indoor fan speed
below 28˚Coff
28˚C ~ below 34˚C LL speed
34˚C ~ below 40˚C L speed
above 40˚C setting speed
The temperature of indoor heat exchanger Indoor fan speed
above 20˚C UL speed
below 20˚Coff
after 10 minutes when compressor stops operating off
When compressor is on
40˚C
34˚C
28˚C
20˚C
Setting speed
L speed
LL speed
OFF
Compressor
OFF OFF
UL
ON
When compressor is off
INDOOR FAN CONTROL
When compressor begins operating
When compressor stops operating