Specifications
32
JOHNSON CONTROLS
Form 201.28-NM1.EN.PED/CE (0211)
INSTALLATION
The data shown in the tables below is applicable to selected typical confi gurations. Other confi gurations are available
through our confi guration/selection software. Please contact your nearest Johnson Controls Sales Offi ce for the chiller
confi guration that best matches your specifi c needs.
Field Wiring Lugs
Standard & Ultra Quiet Condenser Fans
Circuit Breaker Non-Fused Disconnect Switch
YVAA Model
Input Volts
Input
Frequency
Lugs per phase Lug wire range Lugs per phase Lug wire range
Frame Condenser Evaporator
054 3 B 400 50 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil
056 5 B 400 50 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil
058 8 C 400 50 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil
064 3 A 400 50 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
066 5 A 400 50 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
068 8 B 400 50 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
070 0 C 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
074 3 A 400 50 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
076 5 C 400 50 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
078 8 C 400 50 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
084 3 B 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
086 5 C 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
088 8 C 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
094 3 B 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
096 5 E 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
098 8 E 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
Field Wiring Lugs
High Airfl ow/High Static Condenser Fans
Circuit Breaker Non-Fused Disconnect Switch
YVAA Model
Input Volts
Input
Frequency
Lugs per phase Lug wire range Lugs per phase Lug wire range
Frame Condenser Evaporator
054 3 B 400 50 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
056 5 B 400 50 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
058 8 C 400 50 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil
064 3 A 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
066 5 A 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
068 8 B 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
070 0 C 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
074 3 A 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
076 5 C 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
078 8 C 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
084 3 B 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
086 5 C 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
088 8 C 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
094 3 B 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
096 5 E 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
098 8 E 400 50 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
TABLE 2 - ELECTRICAL LUG DATA