Specifications

36
JOHNSON CONTROLS
Form 201.28-NM1.EN.PED/CE (0211)
TECHNICAL DATA
CONTROL ENTRY
114 mm WIDE X 330 mm HIGH
4.5” WIDE X 13.0” HIGH
POWER ENTRY
254 mm WIDE X 356 mm HIGH
10.0” WIDE X 14.0” HIGH
VIEW A-A
VIEW B-B
56 mm
2.3”
286 mm
11.3”
38 mm
1.5”
102 mm
4.0”
2401 mm
94.5”
A” PIPE WATER OUTLET A” PIPE WATER INLET
2241 mm
88.3”
B
B
B
C
YVAA Model A B C D E
Frame Cond. Evap. Pipe Diameter (in) in mm in mm in mm in mm
054 3 B 6 15.5 394 11.4 290 8.9 227 203.3 5162
056 5 B 6 15.5 394 11.4 290 31.0 797 247.0 6274
058 8 C 6 15.5 394 11.4 290 50.1 1272 291.2 7397
064 3 A 6 14.5 368 11.4 290 19.3 488 247.0 6274
065 5 A 6 14.5 368 11.4 290 63.2 1605 291.2 7397
068 8 B 6 15.5 394 11.4 290 119.2 3028 335.2 8514
070 0 C 6 15.5 394 11.4 290 8.9 227 203.3 5162
074 3 A 6 14.5 368 11.4 290 63.2 1605 291.2 7397
076 5 C 6 15.5 394 11.4 290 37.4 951 291.2 7397
078 8 C 6 15.5 394 11.4 290 94.1 2389 335.2 8514
084 3 B 6 15.5 394 11.4 290 75.2 1910 291.2 7397
086 5 C 6 15.5 394 11.4 290 94.1 2389 335.2 8514
088 8 C 6 15.5 394 11.4 290 138.1 3506 379.1 9631
094 3 B 6 15.5 394 11.4 290 119.2 3028 335.2 851 4
096 5 E 8 15.8 400 14.0 355 44.4 1128 335.2 8514
098 8 E 8 15.8 400 14.0 355 88.3 2242 379.1 9631
DIMENSIONS
The data shown in this table is applicable to selected typical con gurations. Other con gurations are available through
our con guration/selection software. Please contact your nearest Johnson Controls Sales Of ce for the chiller con gu-
ration that best matches your speci c needs.
FIGURE 14 - DIMENSIONS