Specifications

43
JOHNSON CONTROLS
Form 201.28-NM1.EN.PED/CE (0211)
5
50 MM (SEISMIC) ISOLATOR SPECIFICATIONS
12"
5"
2-3/4"
12-1/4"
8-3/8"
OPER.
HEIGHT
14"
5/8"
3/8"
Ø3/4"
TYP.(4)
3-1/2"
5/8-11UNC
TYP. (4)
2-3/4"
3/4"
7/8"
1-1/8"
3/8" GAP
5"
1/2" LIMIT
STOP &
NUT
Weight Range (kgs)* Type Colour York P/N
Up to 178 Y2 Green 029-25336-006
178 to 274 Y2 Dark Brown 029-25336-008
274 to 336 Y2 Red 029-25336-009
336 to 463 Y2 Red/Black 029-25336-010
463 to 652 Y2 Pink 029-25336-011
652 to 1018 Y2 Pink/Grey 029-25336-012
1018 to 1188 Y2 Pink/Grey/Orange 029-25336-013
1188 to 1442 Y2 Pink/Grey/Dark Brown 029-25336-014
*Values de-rated by 15%
Notes:
1. All dimensions are in inches, interpret as per ANSI Y14
2. Equipment must be bolted or welded to the top plate to meet allowable seismic ratings.
3. All springs are designed for 50% overload capacity with exception of the 029-25336-013 and 029-25336-014.
4. Consult JCI for concrete installation.