4-5 Fault Diagnosis by Symptom
4-5-1 No Power(completely dead) - Initial diagnosis
1. Checklist :
1) Is Power source voltage normal?
2) Is AC power linked correctly? ( miss-wiring, wire detaching etc. )
3) Is any LED on the MAIN PCB of Outdoor unit lit?
4) Is terminal voltage for indoor unit normal? (230Vac nominal)
5) Is Wired remote controller installed correctly?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Check outdoor unit terminal
block voltage on each N-R,N-S,N-T
(230Vac nominal)
Check outdoor unit terminal
block voltage on L-N for indoor unit
(230Vac nominal)
Check indoor unit terminal
block voltage on L-N
(230Vac nominal)
Check indoor unit terminal
block voltage on V1-V2
(12Vdc nominal)
Press the On/Off button on
the wired remote controller to operate the
air conditioner
Check DC power voltage of remote
controller(V1,V2)
Check DIP SW in the wired remote controller
Is there any error display on the wired
remote controller
Turn off the breaker and turn it on after 30 seconds
Check AC power source. Reconnect wires correctly.
Check Inner wiring of outdoor unit.
Check cable and connection of wire between
indoor and outdoor unit.
Check Indoor control PCB, Transformer,
and FUSE on PCB and replace one which is broken.
Check cable and connection of wire between
remote controller and indoor unit.
Replace wired remote controller.
Set DIP SW correctly.
Check each item according to error code list.
Check the setting temperature
No
No
No
No
No
No
No
No