Product specifications

4-23 Samsung Electronics
4-5-13 Compressor start error
1. Checklist :
1) Is the connection of cable for the compressor and power?
2) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Restart after power off
Is the restart error occurred again?
Is the interphase resistance value of compressor
(u v, v w, w u) normal?
Is the compressor body and interphase
resistance insulated?
Is the connection cable for thecompressor and
power terminal normal?
Exchange the PCB
Terminate the service
Exchange the compressor
Exchange the compressor
Correct the cable connection
No
No
No
No