Heat Pump User Manual

34_ Operating advanced function
Operating advanced function
FIELD SETTING MODE
Water Law & Room Thermostat : Code 20✴✴
Ts
Heating WL
Cooling WL
Shift Value

Ta


#2021/2031
#2022/2032
#2061/2071
#2062/2072
#2011 #2012 #2051 #2052
Floor FCU
Field Setting Value
Main Menu &
Code
Sub Menu Function Description
Sub
Code
Default Min Max Step Unit
Water Law
Code 20✴✴
Outdoor Temp for Water Law
(Heating)
Point
✴✴11 -10 -20 5 1 ˚C
Point
✴✴12 15 10 20 1 ˚C
Water Out Temp for WL1 Heating
(WL1-Floor)
Point
✴✴21 40 40 55 1 ˚C
Point
✴✴22 25 17 37 1 ˚C
Water Out Temp for WL2 Heating
(WL2-Fan Coil Unit)
Point
✴✴31 50 40 55 1 ˚C
Point
✴✴32 35 17 37 1 ˚C
Heating Water Law for Auto Mode WL Type
✴✴41 1(WL1) 1
2(WL2)
- -
Outdoor Temp for Water Law
(Cooling)
Point
✴✴51 30 25 35 1 ˚C
Point
✴✴52 40 35 45 1 ˚C
Water Out Temp for WL1 Cooling
(WL1-Floor)
Point
✴✴61 25 18 25 1 ˚C
Point
✴✴62 18 5 18 1 ˚C
Water Out Temp for WL2 Cooling
(WL2-Fan Coil Unit)
Point
✴✴71 18 18 25 1 ˚C
Point
✴✴72 5 5 18 1 ˚C
Cooling Water Law for Auto Mode WL Type
✴✴81 1(WL1) 1
2(WL2)
- -
External Thermostat Application
#1(Floor) ✴✴91 0(No) 0 1(Yes) - -
#2(FCU) ✴✴92 0(No) 0 1(Yes) - -
Water Law for Heating
Outdoor air temperature range : Lower limit
(#2011, Default -10˚C, Range : -20 ~ 5˚C),
Upper limit
(#2012, Default 15˚C, Range : 10 ~ 20˚C)
- With this default settings, the water outlet temperature by heating water law can be
changed within the outdoor temperature range of -10 ~ 15˚C.
Water out temperature range for floor/FCU applications respectively :
Upper limit
(#2021/2031, Default 40/50˚C, Range : 40 ~ 55˚C), Lower limit
(#2022/2032,
Default 25/35˚C, Range : 17 ~ 37˚C)
- With this default settings, the water outlet temperature by heating water law can be
changed within the range of 25/35 ~ 40/50˚C.
Type of water law for according to heating devices(floor/FCU) : #2041(Default “1”(WL1 for
floor)), “2”(WL2 for FCU or radiator)
The #2 DIP switch in the wired remote controller should be set to “OFF”(Default) to
control the water outlet temperature.
The operation mode of the wired remote controller should be set to “AUTO”(
) to use
the weather dependent water law scheme.
Ts : Target Temp.
Ta : Ambient Temp.