User manual

Operating advanced function _33
ENGLISH
Remote Controller Setting Range : Code 10
Space Cooling
• Targetwateroutlettemperature:Upperlimit(#1011,Default25ºC,Range:18~25ºC),
Lowerlimit(#1012,Default16ºC,Range:5~18ºC)
 - With this default FSV settings, user can change the target water outlet temperature within
the range of 5 ~ 25ºC for cooling
• Targetroomtemperature:Upperlimit(#1021,Default30ºC,Range:24~30ºC),
Lowerlimit(#1022,Default18ºC,Range:18~22ºC)
 - With this default FSV settings, user can change the target room temperature within the
range of 18 ~ 30ºC for cooling.
•The#1DIPswitchinthewiredremotecontrollershouldbesetto“OFF”(Default)for
cooling operation of heat pump.
•The#2DIPswitchinthewiredremotecontrollershouldbesetto“OFF”(Default)to
control the water outlet temperature.
•The#2DIPswitchinthewiredremotecontrollershouldbesetto“ON”tocontrolthe
room temperature.
•The#3DIPswitchinthewiredremotecontrollershouldbesetto“OFF”(Default)to
control the air sensor in remote controller.
•The#3DIPswitchinthewiredremotecontrollershouldbesetto“ON”tocontrolthe
external air sensor.
Space Heating
• Targetwateroutlettemperature:Upperlimit(#1031,Default55ºC,Range:37~55ºC),
Lowerlimit(#1032,Default25ºC,Range:15~37ºC)
 - With this default FSV settings, user can change the target water outlet temperature within
the range of 25 ~ 55ºC for heating.
• Targetroomtemperature:Upperlimit(#1041,Default30ºC,Range:24~30ºC),
Lowerlimit(#1042,Default16ºC,Range:16~22ºC)
 - With this default FSV settings, user can change the target room temperature within the
range of 16 ~ 30ºC for heating.
•The#2DIPswitchinthewiredremotecontrollershouldbesetto“OFF”(Default)to
control the water outlet temperature.
•The#2DIPswitchinthewiredremotecontrollershouldbesetto“ON”tocontrolthe
room temperature.
FieldSettingValue
Main Menu &
Code
Sub Menu Function Description
Sub
Code
Default Min Max Step Unit
Remote
Controller
Setting Range
Code 10
Water Out Temp for Cooling
Max 11 25 18 25 1 ˚C
Min 12 16 5 18 1 ˚C
Room Temp for Cooling
Max 21 30 24 30 1 ˚C
Min 22 18 18 22 1 ˚C
Water Out Temp for Heating
Max 31 55 37 55 1 ˚C
Min 32 25 15 37 1 ˚C
Room Temp for heating
Max 41 30 24 30 1 ˚C
Min 42 16 16 22 1 ˚C
DHW Tank Temp
Max 51 50 50 70 1 ˚C
Min 52 40 30 40 1 ˚C
DHW Heating
• TargetDHWtanktemperature:Upperlimit(#1051,Default50ºC,Range:50~80ºC),
Lowerlimit(#1052,Default40ºC,Range:30~40ºC)
 - With this default FSV settings, user can change the target tank temperature within the
range of 40 ~ 50ºC for DHW heating.
TheFSV#3011inthewiredremotecontrollershouldbesetto“1(Yes)”touseDHW
function.
IB_EN DB98-32660-06_20140917.indd 33 2014/9/22 15:38:20