User manual

36_ Operating advanced function
Operating advanced function
FIELD SETTING MODE
DHW Heating : Code 30
T(C)
T
U
> T
HP MAX
T
HP MAX
T
HP OFF
T
HP ON
T
U
#3021
#3022
#3023
T(C)
T
U
< T
HP MAX
T
HP MAX
T
U
=T
HP OFF
T
HP ON
#3021
#3023
1
t
0
1
0
DHW
request
Heating
request
DHW(H/P)
operation
#3024
#3025 #3026
1
0
FieldSettingValue
Main Menu &
Code
Sub Menu Function Description
Sub
Code
Default Min Max Step Unit
DHW
Code 30
Domestic Hot Water
Tank
Application 11 0(No) 0 1(Yes) - -
Heat Pump Max Temp 21 50 45 55 1 ˚C
Stop 22 2 2 10 1 ˚C
Start 23 5 1 20 1 ˚C
Min Operation 24 5 0 20 1 min
Max Operation 25 30 5 95 5 min
Interval 26 3 0 10 0.5 hour
Booster Heater Application 31 1(On) 0(Off) 1 - -
Delay Time 32 20 20 95 5 min
Overshoot 33 0 0 4 1 ˚C
Compensation Temp 34 10 0 20 1 ˚C
Disinfection Application 41 1(On) 0(Off) 1 - -
Interval 42 Fri Mon Sun 1(All) day
Start Time 43 23 0 23 1
o'clock
Target Temp 44 70 40 70 5 ˚C
Duration 45 10 5 60 5 min
Power DHW by User
Input
Timer OFF Function 51 0(Off) 0 1 - -
Timer Duration 52 60 30 300 10 min
Solar Panel H/P Combination 61 0(No) 0(No) 1(Yes) - -
Tu:Usersettemp.
T(C):Temp.(Celcius)
IB_EN DB98-32660-06_20140917.indd 36 2014/9/22 15:38:21