Output module specifications
Internal circuit and wiring diagram
NX-Y16R: No varistor
NX-Y16RV: Varistor
Product name RELAY output module
Catalog number NX-Y16R NX-Y16RV
Number of output points 16 points
Insulation method Photocoupler
Rated load voltage 2A 250V AC, 2A 30V DC
Response time
OFF ON 10ms or less
ON OFF 10ms or less
Life time
Mechanical 30 million times
Electric 200 thousand times
External power supply 24V 150mA or less
Surge protection N/A Varistor
Internal current consumption (5V) 120mA or less
Common method 8 points/1COM
Operation indicator LED
External cable connection type
Terminal block connection (M3.5), Detachable
terminal block (20 pins)
Recommended cable size 0.5 to 1.25 mm
2
Capacity 225g 235g
Types (A) Type
250V AC
30V DC
24V DC
Varistor