User manual

34
Internal circuit and wiring diagram
Product name SSR output module
Catalog number NX-Y16SSR
Number of input points 16 points
Insulation method SSR
Rated load voltage 100 to 240V AC
Operating load voltage range 85 to 264V AC
Max. load current 0.5A/point
OFF state leakage current 100 µA
or less
Response time
OFF ON 1ms or less
ON OFF 0.5 CYCLE + 1ms or less
Internal current consumption (5V) 250mA or less
Fuse rating 3A
Common method 8 points/1COM
Operation indicator LED
External cable connection type
Terminal block connection (M3.5), Detachable
terminal block (20 pins)
Recommended cable size 0.5 to 1.25 mm
2
Weight Approx. 240g
Types (A) Type
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
VCC
AC100 to 240V
1
3
5
7
0
2
4
6
9
B
D
8
A
C
F
COM
F
COM