User manual

71
Connecting 64-point unit (NX-X64D, NX-Y64T)
Mapping table between flat cable No. and I/O (64 points)
NC: No Connection
NX-X64D
NICD
Product name
Catalog
number
Specifications
Flat cable
(1.5m)
NX-CBLDC
DC IN 64 points
(NX-X64D)
NX-CBLTR
TR OUT 64 points
(NX-Y64T)
Flat cable Flat cable
ATTENTION
Be careful that Connector (I) and connector (II) are opposite.
Symbols
on the unit
surface
NX-X64D NX-Y64T
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
X 0
X 1
X 2
X 3
X 4
X 5
X 6
X 7
X 8
X 9
X A
X B
X C
X D
X E
X F
X 10
X 11
X 12
X 13
Y 0
Y 1
Y 2
Y 3
Y 4
Y 5
Y 6
Y 7
Y 8
Y 9
Y A
Y B
Y C
Y D
Y E
Y F
Y 10
Y 11
Y 12
Y 13
Symbols
on the unit
surface
NX-X64D NX-Y64T
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
X 14
X 15
X 16
X 17
X 18
X 19
X 1A
X 1B
X 1C
X 1D
X 1E
X 1F
NC
NC
NC
NC
COM
COM
COM
COM
Y 14
Y 15
Y 16
Y 17
Y 18
Y 19
Y 1A
Y 1B
Y 1C
Y 1D
Y 1E
Y 1F
NC
NC
NC
NC
V DC+
V DC+
V DC-
V DC-