Test Run and Troubleshooting
Test Run Precautions
Before installing the I/O wiring of the PLC and supplying power, check
the following items.
Item What to check
The connection of
the power cable
and the
I/O cables
Check if the wiring is secured.
Check if the terminal screws are tightened.
Check if the parts of connectors are properly joined.
Check if the I/O modules are firmly fixed.
Check if the power cable is securely connected.
Check if the cable size is correct.
Grounding
Check if the grounding is triple grounded and
separate from other device grounds.
Battery
Check if the battery is installed into holder on the CPU
module.
Check if the battery connector is connected to the
CPU board
Emergency
stop circuit
Check if the emergency stop circuit for problems
external to the PLC is wired accurately, and will
immediately disconnect power on demand.
Power source
Check if the power and voltage sources are within
specifications.
- For 110V ac (90 to 132V ac)
- For 220V ac (180 to 264V ac)
Check if the power to the AC input module is within
specifications.