User manual

88
Timer, Counter and Shift Register
Instructions
Mnemonic Name
Ladder
Symbol
Description Remarks
TIM On Delay Timer
Turns on after set delay
time from input on
Time base: Ch 0 to 63 = 0.01s
Ch 64 to 255 = 0.1s
Setting range: SV = 0 to 65535
Contact indicator: TC + channel
number
TOF Off Delay Timer
Turns off after set delay
time from input off
Time base: Ch 0 to 63 = 0.01s
Ch 64 to 255 = 0.1s
Setting range: SV = 0 to 65535
Contact indicator: TC + channel
number
SST
Single Shot
Timer
Turns off after set delay
time from input on
Time base: Ch 0 to 63 = 0.01s
Ch 64 to 255 = 0.1s
Setting range: SV = 0 to 65535
Contact indicator: TC + channel
number
UC
Up Counter
Up counter
Channel range: Ch 0 to 255
(Shared with timer)
Setting range: SV = 0 to 65535
Contact indicator: TC + channel
number
DC Down Counter
Down counter
Channel range: Ch 0 to 255
(Shared with timer)
Setting range: SV = 0 to 65535
Contact indicator: TC + channel
number
RCT Ring Counter
Ring counter
Channel range: Ch 0 to 255
(Shared with timer)
Setting range: SV = 0 to 65535
Contact indicator: TC + channel
number
UDC
Up-Down
Counter
Up-Down counter
Channel range: Ch 0 to 255
(Shared with timer)
Setting range: SV = 0 to 65535
Contact indicator: TC + channel
number
SR Shift Register
Shift Register
Usable address areas for Sb and
Eb : M, K
1 bit shift on each p input.
Stores the status value I in Sb for
every P input.
Max. number of instructions: 256
SST
Ch=00100
SV=00005
Input
Output
TIM
Ch=00010
SV=00050
Input
Output
TOF
Ch=00064
SV=00005
UC
U Ch=020
SV=004
R
DC
D Ch=021
SV=005
R
RCT
T Ch=022
SV=004
R
UDC
U Ch=023
SV=003
D
R
SR
I Sb=K1.4
Eb=K2.5
P
R
Input
Output
Input
Current
value
Output
Reset
Set
value
Input
Current
value
Output
Reset
Set value
Input
Current
value
Output
Reset
Set value
U Input
D Input
Current
value
Reset
Set value
value