Quick Guide

English 17
Installation instructions
Step 3. Accessing the power cord connection
Remove the rear access cover and loosen the screw with a screwdriver. The
terminal block will then be accessible.
Access cover
Terminal block
Specied power-supply-cord kit rating
Range rating, watts
Specied rating
of power-supply-
cord kit, amperes
Diameter (inches) of range
connection opening
120/240
volts 3-wire
120/208
volts 3-wire
Power cord Conduit
8750 - 16500 7801 - 12500 40 or 50A 1⅜" 1⅛"
Use only a 3-conductor or a 4-conductor UL-listed range cord. These cords may be
provided with ring terminals on wire and a strain relief device.
A range cord rated at 40 amps with 125/250 minimum volt range is required.
A 50 amp range cord is not recommended but if used, it should be marked for
use with nominal 1⅜" diameter connection openings. Care should be taken to
center the cable and strain relief within the knockout hole to keep the edge from
damaging the cable.
Because range terminals are not accessible after range is in position, exible
service conduit or cord must be used.
NOTE
If conduit is being used, go to Step 5 on pages 19
~
20.
If the power connection is plugged in improperly, the following message
appears on the display.
LCD, PMOLED : Wire installation fail
LED : bAd LinE
Reconnect the power connection properly, and the message disappears.
ALL NEW BRANCH-CIRCUIT CONSTRUCTIONS, MOBILE HOMES,
RECREATIONAL VEHICLES AND INSTALLATIONS WHERE LOCAL
CODES DO NOT ALLOW GROUNDING THROUGH NEUTRAL, REQUIRE A
4-CONDUCTOR UL-LISTED RANGE CORD.