Quick Guide
English 17
Installation instructions
Step 3. Accessing the power cord connection
Remove the rear access cover and loosen the screw with a screwdriver. The
terminal block will then be accessible.
Access cover
Terminal block
Specied power-supply-cord kit rating
Range rating, watts
Specied rating
of power-supply-
cord kit, amperes
Diameter (inches) of range
connection opening
120/240
volts 3-wire
120/208
volts 3-wire
Power cord Conduit
8750 - 16500 7801 - 12500 40 or 50A 1⅜" 1⅛"
Use only a 3-conductor or a 4-conductor UL-listed range cord. These cords may be
provided with ring terminals on wire and a strain relief device.
A range cord rated at 40 amps with 125/250 minimum volt range is required.
A 50 amp range cord is not recommended but if used, it should be marked for
use with nominal 1⅜" diameter connection openings. Care should be taken to
center the cable and strain relief within the knockout hole to keep the edge from
damaging the cable.
• Because range terminals are not accessible after range is in position, exible
service conduit or cord must be used.
NOTE
• If conduit is being used, go to Step 5 on pages 19
~
20.
• If the power connection is plugged in improperly, the following message
appears on the display.
• LCD, PMOLED : Wire installation fail
• LED : bAd LinE
• Reconnect the power connection properly, and the message disappears.
ALL NEW BRANCH-CIRCUIT CONSTRUCTIONS, MOBILE HOMES,
RECREATIONAL VEHICLES AND INSTALLATIONS WHERE LOCAL
CODES DO NOT ALLOW GROUNDING THROUGH NEUTRAL, REQUIRE A
4-CONDUCTOR UL-LISTED RANGE CORD.
Install_NY63T8751S_DG68-01304A-00_EN+MES.indb 17 2020-05-08 �� 1:50:22