• 15P0177B100 • SUNWAY M XS 2200TL – 3000TL – 3800TL SINGLE-PHASE SOLAR INVERTER USER MANUAL -Installation and Programming InstructionsIssued 10/04/2012 R.00.1 Inverter Software Version: 1.055 Display Software Version: 1.3.3 • • • • • • • • This manual is integrant and essential to the product. Carefully read the instructions contained herein as they provide important hints for use and maintenance safety. This device is to be used only for the purposes it has been designed to.
SUNWAY M XS 2200 TL 3000 TL 3800 TL
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 0. TABLE OF CONTENTS 0. TABLE OF CONTENTS............................................................................................ 3 0.1. INDEX OF FIGURES ............................................................................................... 5 0.2. INDEX OF TABLES.................................................................................................. 7 1. SCOPE OF THIS MANUAL ...............................................
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS 4.1. NAVIGATING IN THE GRAPHIC INTERFACE ...................................................... 56 4.1.1. NAVIGATION BAR .................................................................................................................. 58 4.1.2. MENU AREA ............................................................................................................................ 58 4.1.3. STATUS BAR AREA .....................................
INSTALLATION AND PROGRAMMING INSTRUCTIONS 0.1. SUNWAY M XS 3000TL Index of Figures Figure 1: Block diagram of the SUNWAY M XS ................................................................................................ 9 Figure 2: Packaging of the SUNWAY M XS .................................................................................................... 13 Figure 3: Dataplates of the SUNWAY M XS....................................................................................................
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS Figure 60: Screen of the inverter Status menu ................................................................................................ 60 Figure 61: Example of a measure graph ......................................................................................................... 61 Figure 62: Example of an alphanumeric keypad window ................................................................................
INSTALLATION AND PROGRAMMING INSTRUCTIONS 0.2. SUNWAY M XS 3000TL Index of Tables Table 1: Environmental requirements.............................................................................................................. 19 Table 2: Dimensioning of the MCCB and cable specifications ........................................................................ 25 Table 3: Specifications of the PV field ......................................................................................................
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS 1. SCOPE OF THIS MANUAL Elettronica Santerno is committed to update its User Manuals available for download from santerno.com with the latest software version officially released. Please contact Elettronica Santerno if you require technical documents related to previous software versions. 2. GENERAL INFORMATION 2.1.
INSTALLATION AND PROGRAMMING INSTRUCTIONS 2.3. SUNWAY M XS 3000TL Operating Principle The power conversion system (inverter) is connected directly to the PV field. By using an IGBT bridge associated with a high-frequency voltage booster, the DC current coming from the PV field is converted into AC at the grid frequency.
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS Automatic Disconnecting Means: This device automatically disconnects the self-generation plant from the grid when parallel operation is no longer possible. This typically occurs when the grid “opens” due to maintenance needs or to safety circuit tripping.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3. BASIC INSTALLATION The basic installation consists in connecting the basic elements for the system operation (grid and PV generator). Advanced configurations of the SUNWAY M XS inverter are covered in section 4. Fully read the basic installation instructions before carrying out the advanced configurations. 3.1. Caution Statements This section covers safety statements.
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS CONNECTION TO THE PV FIELD – When exposed to solar radiation, the photovoltaic panels produce DC voltage that is applied to the inverter. DANGER ELECTRIC SHOCK HAZARD – Do not touch the electric parts of the inverter and do not operate on the inverter when it is powered.
INSTALLATION AND PROGRAMMING INSTRUCTIONS 3.2. SUNWAY M XS 3000TL Checking the Product on Delivery On receiving delivery of the equipment, make sure that the packaging shows no signs of damage. Check that it complies with your order by referring to the dataplates described below. In the event of any damage, please contact the relative insurance company or the supplier. If the delivery does not match your order, contact the supplier immediately.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.2.1. Dataplate The product is described and identified by two dataplates placed on its side, as shown in Figure 3. Figure 3: Dataplates of the SUNWAY M XS The dataplate measures 60mm x 30mm.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Purchase code of the product: ZZ01770 PP 1 2 3 D A C U W X Y Z 4 5 6 7 8 9 10 11 1 Fixed figures of the purchase code: ZZ01770 for the SUNWAY M XS series 2 Size (two figures): 22 = 2200 (2200 W rated power for 230 V grid) 30 = 3000 (3000 W rated power for 230 V grid) 38 = 3800 (3800 W rated power for 230 V grid) 3 Blank field 4 5 6 DC disconnect switch (optional): 0 = Not fitted 1 = Fitted Unused field: 0 = Default C
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Figure 4: Label placed on the metal enclosure of the product The basic configuration of the SUNWAY M XS inverter comprises the following: • N. 1 SUNWAY M XS inverter • N. 1 Wall-mounting bracket • N.1 PV field connectors kit • N.1 Grid connector • N.1 Wi-Fi connector with adapter • N. 1 Quick start Guide • N. 1 Authentication form • N.
INSTALLATION AND PROGRAMMING INSTRUCTIONS 3.3. SUNWAY M XS 3000TL Transport and Handling State-of-the-art packing is provided when shipping the SUNWAY M XS. Handling should be done using a transpallet or a lift truck with a carrying capacity of at least 50 kg, in order not to damage the product. Get near the installation place, then unpack following the instructions provided below. CAUTION The whole original packing is to be kept for the full duration of the warranty period.
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS 2. Remove the SUNWAY M XS from its packing by lifting it from its sides. To avoid damaging the packing, lift the product keeping it horizontal to the floor (see Figure 6). Figure 6: Procedure for removing the SUNWAY M XS from its packing 3. Put all the packing elements in the box and store it in a dry place (see Figure 7).
INSTALLATION AND PROGRAMMING INSTRUCTIONS 3.4. SUNWAY M XS 3000TL Installation NOTE 3.4.1. Do not remove the inverter lid during installation. Removing the lid may affect the IP rating of the inverter and may damage the internal parts. Removing the lid voids the inverter warranty. Environmental Requirements for the Equipment Storage, Installation and Operation SUNWAY M XS Model IP Rating (*) 2200TL 3000TL 3800TL IP65 IP65 IP65 (*) Mechanical dimensions (mm) 380 x 570 x 218 Weight (kg) 17.
SUNWAY M XS 3000TL 3.4.2. INSTALLATION AND PROGRAMMING INSTRUCTIONS Wall Mounting The SUNWAY M XS is provided with a bracket that can be used for wall mounting. The inverter is to be installed in upright position. Make sure that the wall can withstand the weight of the product. 20/124 CAUTION Do not install the SUNWAY M XS in direct sunlight or above heat sources. NOTE The installation place for the SUNWAY M XS is to be chosen on the basis of its degree of protection.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Do the following to mount the inverter: 1. Find an installation site suitable for the inverter, allowing adequate clearance as mentioned in Figure 8. The clearance below allow easy mounting and proper ventilation. Figure 8: Minimum clearance (in mm) to respect for proper ventilation of the SUNWAY M XS 2. N.
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS 3. Place the inverter upright in contact with the wall in the proximity of the fixing point. The inverter is equipped with feet for upright installation. Figure 10: The SUNWAY M XS in upright position 4. Fasten the SUNWAY M XS to the bracket by lifting it from the two side handles.
INSTALLATION AND PROGRAMMING INSTRUCTIONS DANGER SUNWAY M XS 3000TL Make sure that the product is properly fastened to the wall bracket before loosening your grip on the product. 5. Make sure that the SUNWAY M XS is firmly fixed to the wall. Make sure that no tilting occurs. 3.4.3. Electrical Connection Remove the cable cover at the bottom of the inverter in order to gain access to the connectors.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Figure 13: SUNWAY M XS connectors DANGER Always connect the protective earthing (PE). Follow the sequence below to carry out the electrical connection of the SUNWAY M XS. CAUTION 24/124 1. Carry out the earth connection of the inverter. 2. Carry out the electrical connection of the inverter to the photovoltaic field.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.4.3.1. Connection to the Grid CAUTION The electrical connection of the SUNWAY M XS must follow the steps given in section 3.4.3. DANGER Always remove voltage before operating on the grid. The earth conductor must be connected first. Do not connect supply voltages exceeding the equipment rated voltage, single-phase, 230 V ±20 % to avoid damaging the internal circuits.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL The connector is composed of a fixed element (see figure below): Figure 14: Fixed element of the grid connector and of a floating element supplied with the product. The installer shall connect the AC cable to this section according to the instructions given on the connector itself.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Figure 16: Mounting the floating connector for the connection to the grid Proceed as follows: 1. Install the RCD making sure that no electric load is interposed between the circuit breaker and the SUNWAY M XS. Make sure that the current capacity of the electrical installation in that point is appropriate for the connection. NOTE It is recommended that a RCD with a minimum trip threshold of 100 mA be installed for each individual inverter.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL SUNWAY M XS Model 2200TL 3000TL 3800TL Number of PV fields that can be connected 1 2 2 Number of strings per PV field that can be connected 2 1 2 DANGER Make sure that the safety circuit breaker is open and the earth connector (PE) is properly earthed. Do not connect any photovoltaic generator capable of producing field voltage exceeding the maximum allowable rating (580V).
INSTALLATION AND PROGRAMMING INSTRUCTIONS DANGER SUNWAY M XS 3000TL The voltage produced by the photovoltaic generator radiated by sunlight (even weak sunlight) can reach dangerous voltage. Cable stripping and wiring must be carried out with extreme care using proper tools. It is advisable to cover the photovoltaic panels with a sun shade. Always take EXTREME CARE to avoid any unintentional contacts with the floating pole of the PV generator.
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS Do the following: 1) Make sure that the inverter is uncoupled from the AC grid. 2) If the DC disconnect switch (optional) is fitted, set it to OFF (see Figure 17). 3) Check polarity and voltage of each string. 4) Connect the strings of the PV field to the quick-coupling connectors, making sure that polarities are respected.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.4.3.3. Specifications of the Quick-coupling Connectors Supplied with the Product 2 The product houses unipolar conductors with cross-section 4 to 6 mm and outer diameter from 6.3 to 7.8 mm. Follow the instructions below to assemble the flying connectors. Cable Type of connector Cable crosssection LC4-CP3x…4/6 4/6 mm (AWG12/10) 2 Cable outer diameter 6.37.
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS 3.4.3.4. Removing the Protective Film from the Display The SUNWAY M XS inverter is supplied with a film protecting the touchscreen display. See Figure 18. Once the inverter installation is complete, remove the protective film from the touchscreen display to start using it.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.4.3.5. Fiscal Seal A fiscal seal may be applied to the inverter, where required. The seal may be applied through the special slots on both sides of the product cover and enclosure. Remove the connector protective cover to gain access to the slots. Figure 19 shows the location of the slots.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.5. Commissioning NOTE • • • The SUNWAY M XS inverter is factory-set with a set of parameters fitting most applications; therefore, no parameter modification is generally required. Always carry out the Quick Configuration procedure of the touchscreen display (see section 3.6). Make sure that the inverter connections to the PV field and the grid are correct. Connect the inverter to the grid by closing the grid-side switch.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL According to factory setting, the inverter startup conditions are as follows: NOTE 1. Grid voltage: 230 Vac +/-15 %. 2. Grid frequency: 50 Hz +/-0.3 Hz. 3. PV field voltage ranging from 150 V to 540 V. CAUTION GRID INTERFACE CONFIGURATION – The grid interface configuration based on the Country where the inverter is installed may be changed only within the first 12 hours after the commissioning of the inverter.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.6. Quick Configuration The Quick Configuration in the Tools menu guides the user through preset operations for a quick configuration of the product. The Quick Configuration comprises: 1. Setting the language. See section 3.6.1 2. Setting the Country. See section 3.6.2 3. Setting the time zone. See section 3.6.3 4. Setting the date and time. See section 3.6.4 5. Setting the currency. See section 3.6.5 6. Setting the feed-in tariff.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL In summary: → Select the Tools icon → Select the Quick Configuration submenu → Select L402 Language → Select a language and press Save → Confirm with OK Figure 22: Setting the dialogue language 3.6.2. Setting the Country NOTE Changing the Country affects the configuration of the grid interface of the inverter.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL In summary: → Select the Tools icon → → Select the Quick Configuration submenu Select P040 Country → Select a value and press Save → Confirm with OK Figure 24: Setting the Country During the time interval when the Country may be changed (12h), the start menu shows the name of the Country which is currently selected. After that time interval, the Country is no longer displayed.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Figure 26: Time zone setting page − Select the desired time zone; − Activate your choice by pressing the Save ( ) button and confirm with system automatically quits the current page. If you press Cancel ( maintained. .
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL − Figure 28: Setting the date − − Enter the date by pressing the buttons; Activate your choice by pressing the Save ( − system automatically quits the current page. If you press Cancel ( are maintained; Repeat the steps above for L401 – Time. ) button and confirm with .
INSTALLATION AND PROGRAMMING INSTRUCTIONS 3.6.5. SUNWAY M XS 3000TL Setting the Currency This section describes how to change the currency. Do the following: − From the start menu, select the Tools ( − Select the Quick Configuration ( ) menu.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.6.6. Setting the Feed-in Tariff This section describes how to change the parameters of the inverter net metering. The net-metering function constantly informs the consumers about the economic return of their PV plant. You have to set up the remuneration of the generated energy acknowledged by your Grid Administrator. On the basis of the remuneration and the generated energy, the inverter displays the overall gain.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.6.7. Resetting the History Data The Reset command resets the logs of the display history data and restarts the datalogging function for the integrity of the history data after the date and time have been changed. Do the following: − From the start menu, select the Tools ( − Select the Quick Configuration ( − Select L500 – Reset History. Use the arrows ( of the submenus.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.6.8. Resetting the Display Resetting the display is required to ensure its correct operation after changing the display settings during the Quick Configuration procedure. Do the following: − From the start menu, select the Tools ( − Select the Quick Configuration ( − Select L011 – RESET DISPLAY. Use the arrows ( page of the submenus; the screen below appears: ) icon; ) submenu.
INSTALLATION AND PROGRAMMING INSTRUCTIONS 3.7. SUNWAY M XS 3000TL Connectivity The Wi-Fi transmitter is to be inserted into the USB connector using the special adapter. Figure 38: Inserting the Wi-Fi transmitter 3.7.1. Wi-Fi Connectivity The SUNWAY M XS features Wi-Fi 802.11 b/g connectivity for ad hoc (point-to-point) connection or for the connection of the inverter to a WLAN (wireless area network). NOTE The Wi-Fi connection is to be disabled before changing the Wi-Fi settings. 3.7.1.1.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.7.1.2. AD HOC Connection The AD HOC connection enables connecting a PC to a different device allowing using one of the consulting methods in section 4 for one or more inverters, with no need to exploit an existing wireless network. When using the AD HOC connection, unencrypted data is transmitted from/to the inverter. NOTE When an AD HOC connection is established, the Wi-Fi status icon is green or yellow during data transmit/receive.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.7.1.3. Router Connection CAUTION The SUNWAY M XS inverter may be connected only to WPA encrypted networks by entering an alphanumeric password from 8 to 63 characters.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL − Set the IP address assignment mode. Select: • “DHCP” if you desire that the IP address is assigned by the router or access point (factory setting). By selecting the “DHCP” mode, the additional connection parameters will be set up directly by the router or access point. The IP address, however, may be changed by the router or access point over time; • “STATIC” if you desire to manually enter the IP address to be assigned to the inverter.
INSTALLATION AND PROGRAMMING INSTRUCTIONS • SUNWAY M XS 3000TL Set the gateway (only if you chose the “STATIC” method for the IP address assignment). Setting this parameter requires knowing the network the inverter is to be connected to. A typical value for domestic environments is the IP address of the router or the access point.
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS The consulting modes below are available only when the inverter is powered on. If the PV field voltage is too weak (higher than the value set in P020 – FIELD REFERENCE), the inverter stops after the time set in P041 – POWER OFF TIMEOUT. Parameter P041 may be changed by the user to keep the inverter on for the desired time even when the PV field reference is too weak, in order to exploit the functionality described above.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Do the following to consult the inverter data from your iPhone: − Launch the SUNWAY M XS application; − Figure 49: Icon of the SUNWAY M XS application on the iPhone − Complete the startup wizard; − When you are required for authentication, enter the serial number of the product as the username and enter the password received when purchasing the product; − Navigate through the contents made available from the application. 3.7.3.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.7.4. Technical Support The SUNWAY M XS inverters, if connected to the Internet via Wi-Fi, may be remotely accessed by the Customer Service of Elettronica Santerno SpA. Assistance is given via an encrypted communication channel between the inverter and Elettronica Santerno SpA Customer Service, whose staff is allowed to access the measures and programming parameters of the inverter.
INSTALLATION AND PROGRAMMING INSTRUCTIONS 3.7.5.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 3.8. Datalogging The SUNWAY M XS inverters may store the measures listed in Table 4.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4. GRAPHIC INTERFACE MODULE The full-colour, graphic touchscreen display is located on the inverter front. The touchscreen display is the HMI of the inverter. When the inverter is powered on, the appearance of the graphic interface module is as in Figure 54.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL When the inverter is started, the touchscreen display shows the following screens in sequence: → Santerno Logo → Sunway M screen → Loading… screen → Start menu Default screen (Graph as a factory setting) Figure 55: Screens of the graphic interface module at power on When no input has been received for 5 minutes, the touchscreen display automatically turns off to reduce self-consumption to a minimum.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL The graphic layout of the application is divided into 3 main areas: Area Description The Navigation Bar is populated by different icons allowing the user to know the navigation position inside the menus. Icons are displayed based on the selected items in the menus. The Menu Area displays the information about the product as well as all the configuration parameters.
SUNWAY M XS 3000TL 4.1.1. INSTALLATION AND PROGRAMMING INSTRUCTIONS Navigation Bar The Navigation Bar displays the icons for easy navigation to the different menus and submenus: • Back to the start menu icon: allows going back to the start menu from any position in the menus. • Menu and submenu icons: graphically represent the current position in the menus. Select one of the icons preceding the last icon from the right to return to the upper level. 4.1.2.
INSTALLATION AND PROGRAMMING INSTRUCTIONS • SUNWAY M XS 3000TL Wi-Fi Status icon: allows accessing the Wi-Fi Status menu, including Wi-Fi connectivity info, such as the name of the network SSID, the IP address of the inverter and the quality of the Wi-Fi connection. Figure 59: Screen of the Wi-Fi Status menu The icon can have four statuses: Hardware not fitted or hardware fault.
SUNWAY M XS 3000TL • INSTALLATION AND PROGRAMMING INSTRUCTIONS Inverter Status icon: allows accessing the inverter Status menu 4.3.9. Figure 60: Screen of the inverter Status menu The Status menu icon represents the operating conditions of the inverter. The icon can have three statuses: Indicates that the inverter is powered, but the PV field voltage is lower than the value set in parameter P020.
INSTALLATION AND PROGRAMMING INSTRUCTIONS 4.2. SUNWAY M XS 3000TL Display Windows and Data Enter Windows The windows listed below make it possible to display the measures made available from the inverter and to change the system settings: 1. 2. 3. 4. Graph window. See section 4.2.1. Alphanumeric keypad window. See section 4.2.2. List window. See section 4.2.3. Run Command window. See section 4.2.4. 4.2.1. Graph Window The graph window shows the pattern of the selected measure.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.2.2. Alphanumeric Keypad Window The alphanumeric keypad window enables entering alphanumeric values in the selected field, as detailed below: VALUE FIELD Displays the alphanumeric value relating to the selected parameter. MIN: Indicates the minimum allowable value. DEF: Indicates the DEFAULT value set for the inverter. MAX: Indicates the maximum allowable value. KEYPAD Alphanumeric keys enabling entering the desired value.
INSTALLATION AND PROGRAMMING INSTRUCTIONS 4.2.3. SUNWAY M XS 3000TL List Window The list window allows entering or changing a parameter chosen from a list, as detailed below: ITEM LIST Scrolling list of the available items. The currently active option is blue in colour. Arrow keys scrolling up and down the items in the list. STATUS Message for the execution of data entering. DEFAULT Default value of the parameter. CANCEL BUTTON Cancels the latest modification and keeps the current setting active.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3. Description of the Menus The menus and submenus of the graphic interface module are divided into the four main areas represented by the four icons in the start menu. 1 2 3 4 Figure 65: Icons of the Menu Area in the start menu 1. Info Menu Measures and programming parameters of the inverter. See section 4.3.2 for details. 2. Graph Menu Graphic display of the measures that can be customized by the user. See section 4.3.3 for details. 3.
INSTALLATION AND PROGRAMMING INSTRUCTIONS 4.3.1. SUNWAY M XS 3000TL Organisation of Measures and Parameters The parameter configuration involves two access levels: • BASIC (factory setting): displays the main measures and parameters; • ADVANCED: displays the advanced measures and enables accessing all the parameters. The access level may be changed by the user from Customization > Access Level > User Level in the Tools menu (see section 4.3.5.2).
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL The information and configuration variables are grouped as follows: o Measures. These values may only be displayed and cannot be changed by the user. Each measure is identified by letter M followed by 3 digits (e.g. M001).
INSTALLATION AND PROGRAMMING INSTRUCTIONS 4.3.2. SUNWAY M XS 3000TL Info Menu The icons of the menus and submenus in the Info area are blue in colour and allow monitoring the inverter measures. Each measure is identified by letter M followed by 3 digits. Figure 66 shows the Info menu tree, while Table 8, Table 9 and Table 10 describe each submenu belonging to the Info menu.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.2.1. Field Submenu Menu Submenu Access Level Action M000 – FIELD 1 VOLTAGE Displays the instant value of the PV field 1 voltage NOTE: This measure is valid only if the PV field is coupled to the inverter BASIC Displays the measure graph. BASIC Displays the measure graph.
INSTALLATION AND PROGRAMMING INSTRUCTIONS M000 Field 1 Voltage Range Id/Address Level Function SUNWAY M XS 3000TL 0 ÷ 6200 0 ÷ 620.0 V 1/1653 BASIC PV field 1 voltage that has been measured. M001 Range 0 ÷ 6200 0 ÷ 620.0 V Id/Address 1/1651 Level ADVANCED MPPT 1 Reference When the inverter is running, this is the measure of the voltage reference Function generated by the MPPT of PV field 1; when the inverter is not running, this is the voltage value of the PV field 1 voltage.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.2.2. Inverter Submenu Menu Submenu Access Level Action Select the icon to display the following items: − M089 – INVERTER STATUS − M090 – ACTIVE ALARM − ALARM HISTORY Displays the Alarm History. See section 4.3.6 for details. BASIC Displays the Event History and the Alarm History • EVENT HISTORY Displays the Event History. See section 4.3.6 for details.
INSTALLATION AND PROGRAMMING INSTRUCTIONS M089 Inverter Status M090 Active Alarm MLBL Sunway M XS Model PRSN Serial Number L000 Display Software SWVer Inverter Software L004 Menu Version M097 Operation Time M098 Range Id/Address Level Function See Table 25 See Table 25 1/1662 BASIC Describes the operating conditions of the inverter. Range Id/Address Level Function See section 4.3.6 1/7711 BASIC Active alarm. See section 4.3.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL M058 Boost Temperature M059 Heatsink temperature Range Address Level Function -100 ÷ +120 -100.00 ÷ +150 °C 1/1660 ADVANCED Measure of the heatsink temperature in the boost converter area. Range Address Level Function -100 ÷ +120 -100.00 ÷ +120 °C 1/1669 ADVANCED Measure of the heatsink temperature in the inverter area. 4.3.2.3.
INSTALLATION AND PROGRAMMING INSTRUCTIONS M005 Grid Frequency Range Id/Address Level Function M006 MPWR 0÷32768 0÷327.7Hz 1/1658 BASIC Measured grid frequency. 2200TL: 0 ÷ 1800 3000TL: 0 ÷ 2400 3800TL: 0 ÷ 3000 Range Grid Current SUNWAY M XS 3000TL 2200TL: 0 ÷ 18.0 A 3000TL: 0 ÷ 24.0 A 3800TL: 0 ÷ 30.0 A Id/Address 1/1667 Level BASIC Function Current fed to the grid.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.3. Graph Menu The icon of the Graph menu is yellow in colour. The Graph menu displays a graph window (4.2.1) where up to three custom measures may be displayed. Measures may be selected from the Customization > Display > Graph submenu (see section 4.3.5.2) in the Tools menu. The MPWR (Power to Grid) measure is displayed as a factory setting.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL − Activate your choice by pressing the Save ( − − system automatically quits the current page. If you press Cancel ( ), the previous settings are maintained; Repeat the operation for the other measures (if any) to be graphically represented; Press to return to the start menu. ) button and confirm with .
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL − Activate your choice by pressing the Save ( ) button and confirm with system automatically quits the current page. If you press Cancel ( are maintained; − Press . The ), the previous settings to return to the start menu.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.4.1. Wi-Fi Submenu Menu Submenu Access Level L399 – WI-FI STATUS Displays the parameter current setting of the BASIC Activates a list window. Select: − OFF − ON of the BASIC Activates a list window. Select: − ROUTER: connection via Router or Access Point − AD HOC: direct connection between the inverter and the device (PC or Smartphone). of the BASIC Activates a window containing a list of the available networks.
SUNWAY M XS 3000TL L306 Wi-Fi Password Range Default Level Function L307 IP Address Assign Mode L301 Range Default Level Function Range Default Level IP Address Function L302 Range Default Level Subnet Mask Function L303 Range Default Level Gateway Function L311 DNS Range Default Level Function 78/124 INSTALLATION AND PROGRAMMING INSTRUCTIONS Alphanumeric value ranging from 8 to 63 characters Default BASIC This variable contains the password enabling accessing the target wireless network
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.4.2. Services Submenu Menu Submenu Access Level BASIC Activates a list window. Select: − DISABLED − ENABLED BASIC Activates a list window. Select: − DISABLED − ENABLED BASIC Activates a list window. Select: − DISABLED − ENABLED BASIC Activates a “Run command” window. Press the Run Command button. The messages relating to the execution of the command will be displayed. L505 – SUNWAYPORTAL.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.5. Tools Menu The icons of the menus and submenus belonging to this macroarea are grey in colour and enable displaying the operating parameters that can be changed by the user. The identifier parameter for each item is marked with letter P, C, I, L and R followed by three digits. The SUNWAY M XS inverter is factory-set with a set of parameters fitting most applications.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.5.1. Quick Configuration Submenu The Quick Configuration submenu groups the settings to be configured when commissioning the inverter for its correct operation. See section 3.6 for details.
SUNWAY M XS 3000TL L011 Display Reset L400 Date Range Default Level Function Range Default Level Function L401 Time Range Default Level Function L402 Language L403 Currency Range Default Level Function Range Default Level Function L404 Range Default Level Time Zone Function L500 History Reset Range Default Level Function 82/124 INSTALLATION AND PROGRAMMING INSTRUCTIONS N/A N/A BASIC This is a command to reset the touchscreen display.
INSTALLATION AND PROGRAMMING INSTRUCTIONS P130 Range Default Level Address Incentive Function SUNWAY M XS 3000TL 0 ÷ 10000 0.0 ÷ 10.000 Unit / kWh 0 0 Unit / kWh BASIC 676 This parameter sets the remuneration per kWh produced. The currency may be set via parameter L403. 4.3.5.2.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL L451 Measure 1 L452 Measure 2 L453 Measure 3 Range Default Level Function See Table 4 MPWR BASIC Enables the customization of measure 1 in the main Graph. Range Default Level Function See Table 4 EMPTY BASIC Enables the customization of measure 2 in the main Graph. Range Default Level Function See Table 4 EMPTY BASIC Enables the customization of measure 3 in the main Graph. Menu Access Level Submenu BASIC Activates a list window.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Menu Access Level Submenu P001 – USER LEVEL BASIC Displays the current level for the user level SW0 – SERVICE PASSWORD ADVANCED Action Activates a list window. Select one of the following: − BASIC − ADVANCED Activates an alphanumeric keypad window. Enter the Service password. This functionality is reserved to the Customer Service of Elettronica Santerno SpA.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Menu Access Level Submenu P026 – MPPT 1 ADVANCED P020 – FIELD 1 REFERENCE ADVANCED P021 – STARTUP DELAY ADVANCED P300 – MPPT2 ADVANCED P220 – FIELD 2 REFERENCE ADVANCED Action Activates a list window. Select one of the following: − INACTIVE − ACTIVE Activates an alphanumeric keypad window. Enter the desired value. Activates an alphanumeric keypad window. Enter the desired value. Activates a list window.
INSTALLATION AND PROGRAMMING INSTRUCTIONS P220 Field 2 Reference Range Default Level Id/Address Function P226 Range MPPT 2 Default Level Id/Address Function SUNWAY M XS 3000TL 1100÷4000 110.V÷400V 2800 280V ADVANCED 1/255 If the MPPT algorithm is disabled for PV Field 2 (P226=Inactive), P220 represents the working voltage reference of PV Field 2: the inverter will try to make the PV field voltage match with the value set in P220.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Grid interface See Table 19 Energy See Table 20 Figure 77: Tools menu, Advanced Settings > Grid submenu Menu Submenu C000 – RATED GRID VOLTAGE Displays the value currently set for the parameter C001 – RATED GRID FREQUENCY Displays the value currently set for the parameter P080 – INSTANT OVERVOLTAGE THRESHOLD Displays the value currently set for the parameter P081 – INSTANT OVERVOLTAGE RELEASE RATIO GRID INTERFACE Access Level ADVANCED Act
INSTALLATION AND PROGRAMMING INSTRUCTIONS P092 – INSTANT THRESHOLD GRID SUNWAY M XS 3000TL UNDERVOLTAGE ADVANCED Activates an alphanumeric keypad window. Enter the desired value. ADVANCED Activates an alphanumeric keypad window. Enter the desired value. ADVANCED Activates an alphanumeric keypad window. Enter the desired value. ADVANCED Activates an alphanumeric keypad window. Enter the desired value. ADVANCED Activates an alphanumeric keypad window. Enter the desired value.
SUNWAY M XS 3000TL C001 Rated Grid Frequency P080 Instant Overvoltage Threshold P081 Instant Overvoltage Release Ratio P082 Instant Overvoltage Trip Time P083 Instant Overvoltage Reset Time P084 Maximum Voltage Trip Threshold P085 Maximum Voltage Release Ratio 90/124 INSTALLATION AND PROGRAMMING INSTRUCTIONS Range Default Level Id/Address Function 470 ÷ 630 47.0 ÷ 63.0 Hz 50.0 50.0Hz ADVANCED 1 e 2/1308 This parameter sets the rated value of the grid frequency.
INSTALLATION AND PROGRAMMING INSTRUCTIONS P086 Range P087 Range SUNWAY M XS 3000TL 1 ÷ 10000 0.001÷ 10.000s 100 (Italy), 0.1s (Italy), Default 150 (Spain), 0.15s (Spain), 200 (Germany) 0.2s (Germany) Maximum Level ADVANCED Voltage Trip Time Id/Address 1/1317 This is the time during which the maximum voltage trip condition must be Function maintained to prompt the activation of the grid maximum voltage fault. Maximum Voltage Reset Time P088 1 ÷ 10000 1 ÷ 10.000 s 100 (Italy), 0.
SUNWAY M XS 3000TL P092 Instant Grid Undervoltage Threshold P093 Instant Undervoltage Release Ratio Range Default Level Id/Address Function Range Default Level Id/Address Function P094 Instant Undervoltage Trip Time P095 Instant Undervoltage Reset Time Range Default Level Function Range Default Level Id/Address Function P096 30 ÷ 95 [35 ÷ 95] % of Vn 60 60 ADVANCED 1/1323 This parameter, expressed as a percentage of the grid rated voltage, sets the activation threshold of the instant grid undervoltag
INSTALLATION AND PROGRAMMING INSTRUCTIONS P098 SUNWAY M XS 3000TL Range Maximum Frequency Trip Time P099 1 ÷ 10000 0.001 ÷ 10.000 s 50 (Italy), 0.05s (Italy), Default 50 (Spain), 0.05s (Spain), 200 (Germany) 0.20s (Germany) Level ADVANCED Id/Address 1/1329 Time during which the trip condition of the maximum frequency must be Function maintained to prompt the activation of the grid maximum frequency fault. Range Maximum Frequency Reset Time P100 1 ÷ 10000 0.001 ÷ 10.000 s 10 (Italy), 0.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL P103 Range Minimum Frequency Reset Time 40 ÷ 10000 0.04 ÷ 10.0 s 100 (Italy), 0.10s (Italy), Default 100 (Spain), 0.10s (Spain), 10000 (Germany) 10.0s (Germany) Level ADVANCED Id/Address 1/1334 Time during which the reset condition of the minimum frequency must be Function maintained to reset the minimum frequency fault.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.5.4. Commands Submenu Menu Submenu Access Level AUTOTEST BASIC L500 – HISTORY RESET BASIC RST – INVERTER RESET ADVANCED L011 – DISPLAY RESET BASIC I002 – PARTIAL ENERGY RESET I008 – WARNING RESET ADVANCED BASIC Action Displays the following: − I030 – TEST VMIN − I031 – TEST VMAX − I032 – TEST FMIN − I033 – TEST FMAX Each item activates a run command window. For any details on the grid interface Autotest commands, see section 5.
SUNWAY M XS 3000TL I002 Range Partial Energy Reset Default Level Id/Address Function L011 Display Reset I030 Test V Min Range Default Level Function Range Range Test V Max Default Level Address Function Test f Min I033 Test f Max L500 Range 0 ADVANCED 2/1389 Resets the partial active energy meter (M011). N/A N/A BASIC This is a command. Enables restarting the touchscreen display.
INSTALLATION AND PROGRAMMING INSTRUCTIONS RST Reset inverter Range SUNWAY M XS 3000TL 0, 34 0: No command 34: Reset inverter 0 Default 0 Level ADVANCED Id/Address 1/50 This is a command. It resets the control electronics of the inverter without Function affecting the touchscreen display functionality. I008 Range Reset warning Default Level Id/Address Function 0, 555 0 BASIC 1 and 2/1400 Inactive functionality 0: Inactive 555: Active 0: Inactive 4.3.5.5.
SUNWAY M XS 3000TL 4.3.6. INSTALLATION AND PROGRAMMING INSTRUCTIONS Alarms Menu When a safety device or an alarm trips, the inverter STOPS; the connection to the electric grid of the output power and the current delivery are inhibited. When an alarm message is displayed, find the cause responsible for the alarm before restarting the equipment. CAUTION When a protection or an alarm trips, the inverter operation is disabled. Carefully read the following sections before operating on the inverter.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Menu Submenu M089 – INVERTER STATUS Displays the current inverter status Access Level BASIC Displays detailed information. BASIC Displays detailed information. See section Table 24 or information on the displayed values.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL NOTE The Sunway MXS is controlled by two microcontrollers; each of them constantly checks the inverter status and stops power delivery when severe conditions occur that may damage the equipment. Alarms may be triggered by microcontroller 1 (identified as section A) and alarms triggered by microcontroller 2 (identified as section B).
INSTALLATION AND PROGRAMMING INSTRUCTIONS A001÷A101 Description Event Possible Causes Solutions A003÷A103 Description Event Possible Causes Solutions A004-A104 Description Event Possible Causes Solutions A005-A105 Description Event Possible Causes Solutions A006-A106 Description Event Possible Causes Solutions SUNWAY M XS 3000TL Control board failure: E2P Timeout sect.A/sect.
SUNWAY M XS 3000TL A007-A107 Description Event Possible Causes Solutions A008-A108 Description Event Possible Causes Solutions A009-A109 Strong electromagnetic disturbance. Possible failure of the microcontroller or other circuits in the control board. Reset the alarm (see Figure 80). If the alarm persists, contact the Customer Service of Elettronica Santerno SpA. Control board failure: Sect.A/Sect.
INSTALLATION AND PROGRAMMING INSTRUCTIONS A013-A113 Description Event Possible Causes Solutions A015 Description Event Possible Causes Solutions A016-A116 Description Event Possible Causes Solutions A122 Description Event Possible Causes Solutions A026 Description Event Possible Causes Solutions SUNWAY M XS 3000TL Control board failure: Sect.A/Sect.
SUNWAY M XS 3000TL A028 Description Event Possible Causes Solutions A029 Description Event Possible Causes Solutions A030÷A130 Very unstable grid. Failure in the measurement circuit. Reset the alarm (see Figure 80). If the alarm persists, contact the Customer Service of Elettronica Santerno SpA.
INSTALLATION AND PROGRAMMING INSTRUCTIONS A034 Description Event A136 A037 A038 A144 Control board failure: programme locked in “wait” status The programme controlling the inverter is locked in “wait” status. Possible Causes Strong electromagnetic conducted disturbance or radiated disturbance. Solutions Reset the alarm (see Figure 80). If the alarm persists, contact the Customer Service of Elettronica Santerno SpA.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL A046 Description Event Possible Causes Solutions A048-A148 Description Event Possible Causes Solutions A049 Description Overcurrent 1 detected by the system software Tripping of instant current limiter 1. Wrong wiring in the PV plant. The wiring circuits of field 1 and field 2 are not completely separate. Output short-circuit or earth short-circuit. Check cable tightening and wiring. Reset the alarm (see Figure 80).
INSTALLATION AND PROGRAMMING INSTRUCTIONS A065 Description Event Possible Causes Solutions A066 Description Event Possible Causes Solutions A067 Description SUNWAY M XS 3000TL AC section overtemperature The temperature in the DC/AC conversion section is higher than the maximum allowable temperature. The temperature in the place where the inverter is installed is too high. The inverter has been installed in direct sunlight. The cooling fans are faulty.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL A068 Description Event A081 Insulation loss between the PV field and the earth. Solutions Check if warnings relating to PV insulation are displayed (Status page, 4.3.7). Decouple the PV field from the inverter and check if short-circuits or low-impedance paths occur between the PV field and the earth. Reset the alarm (see Figure 80). If the alarm persists, contact the Customer Service of Elettronica Santerno SpA.
INSTALLATION AND PROGRAMMING INSTRUCTIONS A136 Description Event Possible Causes Solutions A137 Description Event Possible Causes Solutions A138 Description Event Possible Causes Solutions A199 Description Event Possible Causes Solutions SUNWAY M XS 3000TL Protection against leakage current instant variations Instant variations of the leakage current exceeding the maximum allowable variations. The leakage current variation has been at the maximum value of 30 mA for 300 ms.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.6.2. What to Do When an Alarm trips Read and make a note of the data items displayed for the alarm tripped from the ALARM HISTORY. Those data items are very useful to identify the cause responsible for the alarm and to find possible solutions. The alarm data items are also required if you need to contact the Customer Service of Elettronica Santerno SpA. 1. The following pages provide a description of the alarms.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL In summary: → Select the Alarms icon → Select L013 – ALARM RESET → Press the Run Command button Wait for the success message and quit by pressing the return button Figure 80: Resetting an alarm The SUNWAY M XS inverters implement the Autoreset function; this means that the inverter tries to automatically restart when an alarm trips. The factory setting is four restart attempts.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.7.1. Status Conditions The status conditions of the inverter are as follows: Status message M089 Description 102 The inverter is stopped. The inverter is in STOP status when: o it is at its first startup; o the STOP button has been pressed from the graphic interface module. The inverter quits this status only after the START button is pressed from the front panel.
INSTALLATION AND PROGRAMMING INSTRUCTIONS 4.3.8. SUNWAY M XS 3000TL Warnings Warnings are service messages addressed to the user and are displayed in the Status Info field in the inverter Status window. When a warning appears, the Status window will include the “Warning” wording followed by the active warnings. Figure 82: Example of a warning NOTE Warning Message INTERNAL FAN FAULT Warnings are neither protections nor alarms and are not stored to the Alarm History.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Warning Message Causes of the Warning POSITIVE FAILURE POLE INSULATION The insulation to earth of the positive pole of the PV field is too weak (lower than 700 kΩ). NEGATIVE FAILURE POLE INSULATION The insulation to earth of the negative pole of the PV field is too weak (lower than 700 kΩ). FIELD VOLTAGE LIMITING The inverter is in limiting mode because the field voltage is higher than the maximum MPPT voltage.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 4.3.9.1. Wi-Fi Status The Wi-Fi Status window shows the activation status of the Wi-Fi functionality set from the Wi-Fi submenu in the Connectivity menu (3.7). The Wi-Fi status icon shows additional brief information about the Wi-Fi connectivity status, as described in section 4.3.9. 4.3.9.2. Connection Details The Connection Details field shows detailed information on the Wi-Fi connection. Information is periodically updated.
SUNWAY M XS 3000TL INSTALLATION AND PROGRAMMING INSTRUCTIONS 5. ADVANCED INSTALLATION 5.1. Serial Communications 5.1.1. General The SUNWAY M XS 2200, 3000 and 3800 inverters may be connected to a PC via serial link. This allows reading and writing all the parameters normally managed through the touchscreen display as well as the acquisition of the data processed by the inverter.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL The metal case of the connector is connected to the inverter grounding. Connect the braid of the shielded duplex cable used for serial communications to the metal case of the female connector that is to be connected to the inverter. The Modbus-IDA association (http://www.modbus.org) defines the type of connection for Modbus communications over serial link RS485, which is used by the inverter, as a ‘2-wire cable’ configuration.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 5.2. USB Connection The inverters of the SUNWAY M XS series are provided with a USB connector featuring IP67 degree of protection. The USB connector is utilized for the connection of an external Wi-Fi dongle or a USB memory stick for the inverter software update. 5.3.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL When the test is inactive, the trip thresholds of the protections are fixed and set to the values required by the standards in force: Nominal value of the variable (factory setting) Value of the trip threshold (factory setting) 230 Vac 184 Vac 230 Vac 276 Vac 49.7 Hz (49 Hz) (1) 50 Hz 49.7 Hz 50.3 Hz (51 Hz) (1) 50 Hz 50.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL The autotest procedure is as follows: • from the start menu, select the Tools ( • use the arrow keys ( ) from the status bar to scroll to the second page and select the Commands ( ) submenu; ) icon; • select the relevant icons from the Autotest submenu; carry out the following tests in sequence: minimum voltage and maximum voltage; minimum frequency and maximum frequency; • press the Run Command ( ) button to enable the test: the trip
INSTALLATION AND PROGRAMMING INSTRUCTIONS 5.5. SUNWAY M XS 3000TL Removing the Inverter Follow the sequence below to remove the inverter from its installation place: 1. Set the inverter to OFF to cease power delivery; make sure that the status bar of the display. symbol appears on the 2. Decouple the inverter from the grid by opening the moulded-case circuit breaker; make sure that the inverter is disconnected (the display is to be off). 3. Set the PV field disconnect switch (if any) to OFF. 4.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Figure 88: Removing the quick-coupling connectors 7. Remove the serial link connector (if any) 8.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL 6. SPECIFICATIONS SUNWAY M XS Model 2200 3000 3800 Nominal output power (W) 2200 3000 3800 Maximum efficiency (%) 96.3 96.3 96.4 European efficiency (%) 95.3 95.4 95.6 2640 3600 4500 INPUT Maximum peak power (Wp) suggested by the photovoltaic generator MPPT range (Vdc) 125 ÷ 480 580 Maximum open-circuit voltage (Vdc) Number of independent MPPTs Maximum current of the photovoltaic generator (A) 1 2 2 12.5 2*10 2*12.
INSTALLATION AND PROGRAMMING INSTRUCTIONS SUNWAY M XS 3000TL Power Limiting The Sunway M XS inverters may limit their output power based on 3 factors: o Internal temperature The power limiting associated with the internal temperature decreases the power output by 20% every °C over 75 °C. This means that the output power is zero when the internal temperature reaches 80 °C.