2. Processes and functions
2-8 Discharge Temperature Control (Cooling and Heating)
This function prevents the compressor motor from burnout by overheating.
Fig. 11
Chart Summary and Explanations
Discharge temperature is sensed by TH8 (discharge gas sensor).
When the temperature rises above 203°F the electronic refrigerant control valve opens at
50 steps/30 seconds until the temperature falls below 200°F.
During HEATING operation, when the temperature rises above 221°F, the control circuit
stops the outdoor fan motor until the temperature falls below 194°F. Please note that this
control does not function during COOLING operation.
For both COOLING and HEATING modes, if the temperature reaches 239°F the operation
shuts down and alarm P3 appears on the remote controller.
The outdoor fan speed is controlled on discharge temp. at heating mode.
OUTDOOR
FAN SPEED
DISCHARGE GAS
TEMP. (°F)
239
221
203
200
194
185
COMPRESSOR
ELECTRONIC REF.
CONTROL VALVE
(DISCHARGE TEMP.)
TRIP IS OPERATED.
H OR M
M
1141_THS_I
OPENOPEN
H OR M
ON