Wiring Instructions for the 2900 Series FIREGUARD
®
Combination Door Closer-Holder and Releasing Device
with Integral Smoke Detector
CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE.
For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com
CAUTION
INSTALLER: LEAVE INSTRUCTION with building owner.
Wire 12- smoke detector unit to appropriate
power supply and fire alarm
Refer to data sticker for proper input voltage
and current specifications
9- Companion units are designed to work with
12- smoke detector units (12-2960, 12-2990,
12-2980) only
Wire companion unit to 12- smoke detector
unit as shown on wiring diagram if required
Do not disconnect any existing wires on
smoke detector unit’s terminal strip
Energize power supply. Current draw
.1 AMP per 12- unit.
Open door(s) to hold-open point.
Door(s) should hold open
Depress On/Off test switch on circuit
board. Doors should close and latch
Adjustment of spring power may be
necessary to ensure proper latching
Depress On/Off test switch to
reactivate hold open latch
assembly(s)
A7408B
1
1. DISCONNECT ALL POWER BEFORE BEGINNING
INSTALLATION TO PREVENT ELECTRICAL SHOCK AND
EQUIPMENT DAMAGE.
2. INSTALLER MUST BE A TRAINED, EXPERIENCED
SERVICE PERSON.
3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL
ELECTRICAL CODES, ORDINANCES AND REGULATIONS.
4. MAXIMUM WIRE SIZE IS 18AWG.
Wiring 12- Units with and without 9- Companion Unit
9- Companion Unit
(If required)
Field wiring by others
Wire nut
On/Off Test switch
Yellow
Red
Black
Yellow
Black
Black
Terminal strip for
power input wiring
Red
Yellow
Smoke
detector
unit
12- Smoke Detector Unit
9
1112
14
3
7
RED LED/
Reset Switch
Data
Sticker
Opening
for
surface
or
concealed
wiring
Line
Neutral
Earth Ground
120VAC
Power
Supply
*120VAC
Circuit Board
shown
Self
resetting
fuse
Wire the appropriate Power Supply
to circuit board. Power is either
120VAC or 24VDC/VAC depending
on circuit board supplied.
When 24VDC/VAC board is supplied,
wire 24VDC/VAC power supply to
+ and - terminals on circuit board.
*CAUTION: Refer to data
sticker on circuit board for
proper input voltage required.
Do NOT wire 120VAC power
to 24VDC/VAC circuit board.
Earth ground connection is required
when 120VDC power is used
*120VAC
wiring shown
Circuit board 120VAC
or 24VAC/DC
(120VAC shown)
Remove jumper and install
output connector assembly
(Part No. 63-2868) required
for this option
User supplied normally
closed momentary switch
Wiring Optional Remote Push Button