Specifications

SATEL Installer Manual 23
Notes:
If programmable high-current outputs are not used, they should be loaded with 2.2 k
Ω
resistor.
The programmable high-current outputs are provided with a load presence detection
circuit, which is active when the output is inactive. If a load is connected correctly and the
control panel indicates the “No output load" trouble, connect a 2.2 k resistor in parallel to
the load. When the siren connected to the output in parallel to the resistor 2.2 k
generates undesirable sounds (when it is not controlled), reduce the resistance value.
It is recommended that the control panel be started without sirens connected (the high-
current outputs should be loaded with 2.2 k
Ω
resistor). This will prevent alarm from being
accidentally triggered when starting the control panel.
INTEGRA 128-WRL
TMPTMP
SENS.
TMP
SASO
SP-4001
Fig. 19. Connection of siren without own power supply to high-current outputs (by the
example of SP-4001). Optical signaling is triggered by OUT1 output, and audible signaling by
OUT2 output (high-current outputs with normal polarization: when activated, +12 V voltage is
supplied). Z1 is programmed as tamper zone (NC type, function 9. 24H TAMPER).
INTEGRA 128-WRL
TMPTMP
GND STO STA
SENS.
TMP
12V
SP-4002
Fig. 20. Connection of siren with own power supply (by the example of SP-4002) to control
panel outputs. The OUT2 high-current output is programmed as the supply one. Audible
signaling is triggered by OUT3 output, and optical signaling by OUT4 output (low-current
outputs with normal polarization: when activated, they are shorted to ground). Z8 is
programmed as tamper zone (NC type, function 9. 24H TAMPER).