User manual

INTEGRA SATEL
23
The audible signaling may be replaced by blinking of the keys backlight PROG. The beeps
will translate, respectively, into keypad backlight extinguishments – if the backlight is ON, or
into keypad backlight going on - if it is normally OFF.
The keypad can also signal other situations, as selected by the installer (see section
PARTITION KEYPADS).
6.3.3 Operation in entry keypad mode (INT-ENT)
The main task of the entry keypad is to unblock the delay for zones with reaction time
3. INTERIOR DELAYED. The time period during which these zones will act as delayed ones is
programmable for the keypad. If several entry keypads are assigned to one partition,
a different time of delay activation can be programmed for each of them. After the
programmed time period expires, the interior delayed zones will again act as instant ones.
The keypad will execute its functions after:
entering the access code and confirming it with the key,
entering the access code and confirming it with the key,
– presenting the card.
Additionally, the entry keypad may also execute the following functions:
– 24. MONO SWITCH output control
– 25. BI SWITCH output control
guard round confirmation
The user who wants to run any function from the entry keypad must be authorized to use it
(the right is granted by the administrator or installer (service)). Except for the guard round
confirmation function, he must also have access to the given partition. Realized by the
keypad after entering the access code / presenting the card, the function depends on the
user authority level, keypad settings and security system status.
Note: Entering an invalid access code (i.e. unknown to the control panel) or placing an
unknown card in proximity may:
trigger the alarm PROG;
block the keypad for 90 seconds. After the blocking time has expired, entering
another invalid access code / reading in an unknown card will each time block the
keypad PROG.
In the entry keypad, only the LED designated is used for signaling. Blinking of the LED
indicates that countdown of the delay activation time is running (disarming has no effect on
the LED blinking).
The entry keypad can generate the following audible signals:
One short beep – confirmation of access code entry or card read-in (the ACCESS CODE
SIGNALING
(HARDWARE) option must be enabled by the installer).
Two long beeps – access code / card unknown to the control panel.
Three long beeps – activation the delay is impossible (the partition is disarmed or the
delay has already been started) or the function is unavailable.
Three short beeps – confirmation of delay activation.
Three pairs of short beeps – the user code needs to be changed (the NOTIFY OF
NECESSITY TO CHANGE ACCESS CODE
option is enabled in the control panel).
Four short beeps and one long beep – confirmation of the guard round or execution of
the 24. MONO SWITCH or 25. BI SWITCH control function.
The audible signaling may be replaced by blinking of the keys backlight PROG. The beeps
will translate, respectively, into keypad backlight extinguishments – if the backlight is ON, or
into keypad backlight going on - if it is normally OFF.