Manual
www.schaeferpower.de
Technical Notes Technical Notes 
Operational Characteristics
AC or DC input DC output
inrush current 
Power factor correction (PFC)
Power supplies draw line current in pulses from the input 
supply
. Should it be required, a PFC will integrate these pulses 
to be both, effectively sinusoidal in shape, and in phase with 
the AC input supply. The result of this integration, be it active 
or passive, is the reduction of the harmonic distortion and 
allows a more effective loading of the input source.
Spike suppression
High input voltage spikes generated in the supply system that   
could disturb oper
ation of the unit or cause damage will be 
absorbed by a varistor across the input lines.
Input under and over voltage turn off
The input voltage range of the unit is defined as the voltage 
limits at which it will operate. Should the input be reduced to 
a specific voltage, the unit will turn off by switching off the 
power circuit. The same applies to an increase in the input 
voltage. Once a preset value is reached then the power circuit 
will be switched off. It must be considered that the switching 
off of the power circuit does not mean a removal of the input 
circuit from the power supply.
Thermal shutdown with auto restart
The higher power Schaefer modules are fitted with a thermal 
shutdo
wn. In the event of a temperature rise above a preset 
value, the unit will turn off. This safety feature will then 
remain active until the point of temperature measurement has 
reduced significantly. The time duration for this to be reached 
is dependent upon the environment and level of cooling.
Temperature derated load
It is the responsibility of the client to reduce the loading of the 
Schaefer product with respect to the temperature (derated 
load: 2.5 % / °C from +55 °C operating temperature). The 
maximum operating temperature of +75 °C must lead to the 
unit being switched off.
Efficiency
The optimum efficiency is obtained through a high input 
voltage measured against a high output voltage at maximum 
power rating.
Soft start
The application of the input power permits the unit to 
generate a secondary output. The switching on of the primary 
power circuit is controlled and gradually increased to allow 
a controlled charging of the secondary capacitors. The time 
duration for the secondary capacitors to be charged is defined 
as the soft start.
No load operation
Single output converters require no minimum load for 
operation within tolerance. Multi output converters require 
the main output be loaded. Semi-regulated auxiliary outputs 
may also require a minimum load to be applied.
Short circuit protection
The main output of a converter will be immune against 
a momentary or continuous short circuit. The secondary 
current limitation will not permit the sustained output current 
to be higher than the calibrated setting, and it will actively 
reduce the output voltage in accordance to the overload. The 
removal of the overload / short circuit will result in the output 
voltage being increased to the calibrated value. Regulated 
auxiliary outputs will also reduce the output voltage / current 
in accordance to their overloading. The characteristic may 
vary according to the circuit employed.
Over voltage protection (OVP)
The main output voltage is measured, either internally or 
thr
ough sense leads. This measured value is compared 
against a calibrated value. When the calibrated value has 
been reached, this circuit turns off the primary power circuit. 
Once the measured value has reduced below the calibrated 
value, the primary power circuit is permitted, once again, to 
be activated. The high power units have an additional feature, 
which will shut down the primary power circuit after a 
continued OVP operation. 
The input power must be re-cycled 
in order to remove the unit from shut down.
voltage adjustment [V] 5 9 12 15 24 28 48 60 110 200 220 400
Over voltage protection [V] 6.5 12 15 18 30 35 60 70 140 220 280 440
Sense leads
Through the use of sense leads, an output voltage may be 
r
egulated to a point outside of the unit. The sense leads should 
be connected to the power connection at the point of load 
under regard of polarity. There should be a non-interruptible 
connection between sense and load points. Interruption 
may lead to damage or the activation of the OVP circuit. The 
units, which have sense leads, have the ability to regulate to 
a higher voltage at the output connection. This increase is 
largely dependent upon the unit. The details may be found in 
the respective unit specification. Parallel operation with sense 
leads allows a common point for the units to regulate their 
voltages to. Units whose output voltage has been calibrated 
to be near identical will now be able to supply a common 
load.
De-coupled outputs will be sensed both, before and after the
decoupling diodes, which in turn will lead to an output 
voltage regulation, specifi c to load and unit. Sense leads 
are typically employed with a decoupled output voltage of 
less than 40 VDC. The current sharing option will effectively 
override the sense lead output voltage setting, but the point 
at which the output voltage is regulated, will be the point of 
sense lead connection.
-
+
-S
+S
LOAD
+
-
When the module is connected to the input power, the 
primary capacitors will be charged by a high current pulse. The 
magnitude of this pulse depends mainly on the input supply 
system. With a thermistor (temperature dependent resistor) 
in series with the input, this current pulse can be reduced, 
as the thermistor has a relatively high value of resistance as 
long as it is cold. This resistance becomes very low as the 
thermistor heats up. If the input power is interrupted for a 
short period of time not allowing the thermistor to cool 
down, and the primary capacitors are discharged, the current 
limitation function of the thermistor will not be effective. The 
thermistor is standard on mains input models up to 45 Amps 
input current. For higher input current there are two further 
alternatives available: Schaefer PFC or an electronic current 
limitation.










