Manual
www.schaeferpower.de
Technical Notes Technical Notes 
AC output
Operational Characteristics
DC output voltage stabilization
Soft start
The application of the input power permits the unit to 
generate an AC output. The output power increases linearly 
until it reaches its calibrated value. This delay from initial 
output generation until the nominal value is defined as the 
soft start.
No load operation
Inverters require no minimum load for operation within tolerance.
Short circuit protection
The inverter current limitation circuit provides a protection 
against an e
xternal short circuit. Due to the need for crest 
factor and pulse power requirement in many applications, the 
current limitation permits twice the nominal output current 
to be extracted for up to 1 second. The current limitation 
will then be reduced to typically 105% of the nominal value. 
Should the overloading persist, and the output voltage reduce 
to less than 20% of nominal, then the unit will perceive an 
overload condition and turn off. Recycling the input voltage 
will remove this latched off condition.
Crest factor
The ability of an inverter to deliver to a load an inrush current 
is related to the crest factor. The crest factor is the ratio 
between the nominal and the peak current.
Over voltage protection (OVP)
The high power units have this feature. It will shut down the 
pr
imary power circuit after a continued OVP operation. 
The 
input power must be re-cycled in order to remove the unit 
from shut down.
 The output voltage is measured internally. 
This measured value is compared against a reference value. 
When the reference value has been reached, this circuit turns 
off the power circuit. Once the measured value has reduced 
below the reference value the power circuit is once again 
permitted to be activated.
Sense leads
Sense leads are internally connected in all standard configurations.
Harmonic distortion
The generated inverter output is designed to follow a true 
sine w
ave signal. Deviation from this sine wave is measured 
as distortion. The level of deviation is defined as harmonic 
distortion. The total harmonic distortion THD is the 
relationship between the harmonic and fundamental wave 
forms.
Surge power
The AC output may facilitate the output load through its 
ability to provide more then the nominal current for up to 1 
second.
Power factor
The AC output may facilitate complex or other loads, through 
its ability t
o provide a phase shifted output current at nominal 
power rating. This is once again due to the ability to provide 
more than the nominal output current for a limited period of 
time.
The output voltage of a battery charger with parallel 
connected batteries varies substantially with the 
charging condition of the battery. For many applications, 
however, the load circuit requires a more stabilized 
voltage which can be accomplished by:
Voltage dropping diodes
being int
erconnected between battery and load, reduce 
the voltage to a value suitable for the load. They are 
short-circuited by one or more contactors only if a partial 
reduction or no voltage reduction is required. A control 
circuit senses the battery voltage and energizes the 
contactors. Voltage dropping diodes cause substantial 
power losses as the excess voltage is absorbed by the 
diodes. However, due to simplicity, this method is 
frequently used, especially if the voltage reduction 
is needed only during the short periods of high-rate 
charging.
AC input
battery
-
+
battery
charger
DC-load
K1
K2
control
circuit
K1 and K2
for
Switchmode step-up converters 
are DC/DC converters supplied from the battery with the 
output connected in series to the battery. They present a 
very economical solution as they only add voltage when 
the battery is discharged. Details see page 47/ 83.
battery
charger
+
-
step-up converter
(long) cable to load
+
-
sense leads
load










