Datasheet
Table Of Contents
DATASHEET
Single-Stage Filters FN2020
General Purpose AC/DC EMI Filter
Rated currents from 1 to 60 A
High differential-mode attenuation
Optional medical version (B type)
Optional safety version (A type)
Performance indicators
Technical specifications
Rated voltage*
250 VAC, 50/60 Hz; 250 VDC
Operating frequency
DC to 400 Hz
Rated currents
1 to 60 A @ 40°C max.
High potential test voltage
P –> PE 2000 VAC for 2 sec
P –> PE 2500 VAC for 2 sec (B types)
P –> N 760 VAC for 2 sec (1 to 20 A types)
P –> N 1100 VDC for 2 sec (30 and 60 A types)
Temperature range (operation and storage)
-25°C to +100°C (25/100/21)**
Certified to
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939 (applies to
AC and DC applications)
Flammability corresponding to
Terminal plastic for -06/-08 version: UL 94 V-0
Laces for -07 version: UL 94 VW-1
Grommet for -07 version: UL 94 V-0
Design corresponding to
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
Overvoltage category
II acc. IEC 60664-1
Pollution degree
2 acc. IEC 60664-1
Altitude
2000m (above derating applies)**
MTBF @ 40°C/230 V (Mil-HB-217F)
1,250,000 hours
1,750,000 hours (B types)
* maximum RMS operating voltage at rated frequency or the maximum DC operating voltage
** for dedicated requests exceeding this specification (e.g. -40 °C or higher altitude) please contact your local
Schaffner Sales office
Approvals & Compliances
Features and benefits
FN 2020 filters are designed for easy and fast chassis
mounting
FN 2020 B versions without capacitors to earth
comply to 1MOP for ME (medical equipment) acc.
IEC 60601-1
FN 2020 A versions with low capacitance to
earth for safety critical applications with necessity
for low leakage currents
All filters provide a general purpose conducted
attenuation performance, based on chokes with
high saturation resistance and excellent thermal
behavior
FN 2020 filters can be used to cover a broad range
of usage and they offer a good size/amperage ratio
FN 2020 filters are also available as two- stage filters
(FN 2060, FN 2070 series) for more noisy
environment
Various terminal options allow you to select the
desired connection style
Typical applications
Electrical and electronic equipment
Consumer goods
Household equipment
Medical equipment
Office automation equipment
Datacom equipment
Typical electrical schematic