Datasheet

Filter Rated current Leakage current* Power loss Input/Output Weight
@ 50°C (40°C) @ 250VAC/50Hz @ 25°C/50Hz connections
[A] [mA] [W] [kg]
Filter selection table
FN 2415-6-29 6 (6.6) 9.4 2.2 -29 0.4
FN 2415-10-29 10 (11) 9.4 2.4 -29 0.4
FN 2415-16-29 16 (17.5) 9.4 4.3 -29 0.4
* Maximum leakage under normal operating conditions. Note: if the neutral line is interrupted, worst case leakage could reach twice this level.
Per CISPR 17; A = 50Ω/50Ω sym; B = 50Ω/50Ω asym; C = 0.1Ω/100Ω sym; D = 100Ω/0.1Ω sym
Typical filter attenuation
6A types 10A types
16A types
-29
Filter input/output connector cross sections
Solid wire 6mm²
Flex wire 4mm²
AWG type wire AWG 10
Recommended torque 0.6 - 0.8Nm
Please visit www.schaffner.com to find more details on filter connectors.
Mechanical data
All dimensions in mm, 1 inch = 25.4mm
Tolerances according: ISO 2768-m / EN 22768-m
> Components > FN 2415
Your local partner: To find your local partner within Schaffner’s global network, please go to www.schaffner.com
May 2011