Datasheet
2 EMC/EMI Products Schaffner Group Datasheets 2017
Filter selection table
Filter Rated current Leakage current* Inductance
Capacitance
Resistance Input/Output Fuses Weight
@ 40°C (25°C) @ 250 VAC/50 Hz L Cx Cy R connections
(@ 120 VAC/60 Hz)
[A] [mA] [mH] [μF] [nF] [kΩ]
[Qty] [g]
FN 9260 x-1-06-y 1 (1.2) 0.31 (0.18) 5.3 0.1 2.2 1000 -06 2 55
FN 9260 x-2-06-y 2 (2.3) 0.31 (0.18) 2.7 0.1 2.2 1000 -06 2 55
FN 9260 x-4-06-y 4 (4.6) 0.31 (0.18) 1.0 0.1 2.2 1000 -06 2 55
FN 9260 x-6-06-y 6 (6.9) 0.31 (0.18) 0.3 0.1 2.2 1000 -06 2 55
FN 9260 x-10-06-y 10 (11.5) 0.31 (0.18) 0.2 0.1 2.2 1000 -06 2 55
FN 9260 xA1-1-06-y 1 (1.2) 0.03 (0.02) 5.3 0.1 0.22 1000 -06 2 55
FN 9260 xA-2-06-y 2 (2.3) 0.07 (0.04) 2.7 0.1 0.47 1000 -06 2 55
FN 9260 xA-4-06-y 4 (4.6) 0.07 (0.04) 1.0 0.1 0.47 1000 -06 2 55
FN 9260 xA-6-06-y 6 (6.9) 0.07 (0.04) 0.3 0.1 0.47 1000 -06 2 55
FN9260 xA-10-06-y 10 (11.5) 0.07 (0.04) 0.2 0.1 0.47 1000 -06 2 55
FN 9260 xB-1-06-y 1 (1.2) 0.00 5.3 0.1 1000 -06 2 55
FN 9260 xB-2-06-y 2 (2.3) 0.00 2.7 0.1 1000 -06 2 55
FN 9260 xB-4-06-y 4 (4.6) 0.00 1.0 0.1 1000 -06 2 55
FN 9260 xB-6-06-y 6 (6.9) 0.00 0.3 0.1 1000 -06 2 55
FN9260 xB-10-06-y 10 (11.5) 0.00 0.2 0.1 1000 -06 2 55
FN 261 x-1-06-y 1 (1.2)
0.31 (0.18)
5.3 0.1 2.2 1000 -06 1 55
FN 261 x-2-06-y 2 (2.3) 0.31 (0.18) 2.7 0.1 2.2 1000 -06 1 55
FN 261 x-4-06-y 4 (4.6) 0.31 (0.18) 1.0 0.1 2.2 1000 -06 1 55
FN 261 x-6-06-y 6 (6.9) 0.31 (0.18) 0.3 0.1 2.2 1000 -06 1 55
FN 261 x-10-06-y 10 (11.5) 0.31 (0.18) 0.2 0.1 2.2 1000 -06 1 55
* Leakage current under normal operating conditions (acc. to IEC60939-3). Note: if the neutral line is interrupted, worst case leakage could reach twice this level.
Product selector
For example: FN 9260-1-06-10, FN 9260 SB-10-06-20, FN 261 S-6-06-30