Datasheet

2
Filter selection table
FN 9264-xx-1-06-y 1 (1.2) 373/2** 5.15 0.1 2.2 1000 -06 55
FN 9264-xx-2-06-y 2 (2.3) 373/2** 2.7 0.1 2.2 1000 -06 55
FN 9264-xx-4-06-y 4 (4.6) 373/2** 1 0.1 2.2 1000 -06 55
FN 9264-xx-6-06-y 6 (6.9) 373/2** 0.3 0.1 2.2 1000 -06 55
FN 9264-xx-10-06-y 10 (11.5) 373/2** 0.21 0.1 2.2 1000 -06 55
* Maximum leakage under normal operating conditions. Note: if the neutral line is interrupted, worst case leakage could reach twice this level.
** B types without Y2-capacitors
Filter Rated current Leakage current* Inductance Capacitance Resistance Output connections Weight
@ 40°C (25°C) @ 250VAC/50Hz L Cx Cy** R
[A] [µA] [mH] [µF] [nF] [kΩ] [g]
Product selector
FN 9264xx-yy-yy-y
Snap-in range for S version only
Blank: Snap-in panel thickness range 1.0 to 2.5 mm
30: Snap-in panel thickness range >2.5 to 3.5 mm
06: Faston 6.3 x 0.8mm (spade/soldering)
1 to 10: Rated current
Blank: Standard version
B: Medical version (without Y2-capacitor, leakage current max 2µA*)
Blank: Standard housing with mounting flanges
S: Snap-in version, snappper on vertical side
Per CISPR 17; A = 50Ω/50Ω sym; B = 50Ω/50Ω asym
Typical filter attenuation
dB
90
80
70
60
50
40
30
20
10
0
10k 100k 1M 10M 100M
A
B
dB
90
80
70
60
50
40
30
20
10
0
10k 100k 1M 10M 100M
A
B
dB
90
80
70
60
50
40
30
20
10
0
10k 100k 1M 10M 100M
dB
90
80
70
60
50
40
30
20
10
0
10k 100k 1M 10M 100M
A
B
dB
90
80
70
60
50
40
30
20
10
0
10k 100k 1M 10M 100M
A
B
1A types
10A types
4A types2A types 6A types
For example: FN 9264-1-06, FN 9264B-6-06, FN 9264SB-4-06-30