User's Manual

Operation: C1SD, C1ST, and C1SL Versions
5-18 CENTRON Meter Technical Reference Guide
If this meter is replaced by a Load Profile register of the same form number,
voltage and current ratings, and if the utility wants the register to operate the same
way, the pulse weight would be entered in the customer files as 1.8 watthours per
pulse.
Example 2: Calculation of Pulse Weight
A Load Profile register on a singlephase, 240V, CL200, meter is programmed so that
kWh is recorded into mass memory. The maximum 12-bit data resolution is desired
for 15 minute intervals.
First, calculate the maximum watthour accumulation during 15 minutes intervals:
The maximum number of pulses is 4095; therefore, the smallest pulse weight (PW)
that can be used is:
Data Storage
The Load Profile register stores data in mass memory at the end of each interval.
This data stored is the pulse data for that interval. This process continues for each
interval until sixty intervals have been recorded. The mass memory is grouped into
segments of sixty intervals defined as a record or block. In addition to the profile
data, each record contains the following information:
PW
1.8 watt hours
pulse
----------------------------------
=
Wh Max, 240volts 200A 1phase 0.25×××=
Wh Max, 12 000 watt hours,=
PW Min,
12 000Wh,
4095P
---------------------------
2.94Wh
Pulse
-------------------
==
Time Tag
Specifies the month, day, and hour of the end of the data
record (or block).
Power Outage
Status bit is set for each interval during which a power
outage occurs (interval status).
Status Bits
There are four types of status bits written into each data
block:
Time Adjust
Status bit set along with power outage bit when time is
adjusted with Load Profile running.
Saturation
Status bit is set when the pulse count for any interval in
the block exceeds 4,095 pulses.
RAM Error
Status bit is set if any memory address within the record
fails the memory check (block status).
Field Test Status bit is set if Test mode is activated during an interval.
Register Readings
A register reading is maintained in the data record to be
used for data validation. This register reading is updated
at the end of each interval.