Hardware reference guide
CPU Modules
35013379 02 October 2007 167
Front Panel 
Switches
Two, three-position slide switches are located on the front of the CPU. The left 
switch is used for memory protection when in the top position and no memory 
protection in the middle and bottom positions. The three-position slide switch on the 
right is used to select the comm parameter settings for the Modbus (RS-232) ports. 
The following figure shows the three options that are available for the 140CPU43412 
module. 
Setting the slide switch to the top position assigns ASCII functionality to the port; the 
following comm parameters are set and cannot be changed.
Setting the slide switch to the middle position assigns remote terminal unit (RTU) 
functionality to the port; the following comm parameters are set and cannot be 
changed.
Note: The CPU hardware defaults to bridge mode when the front panel switch is 
set to RTU or ASCII mode. When networking controllers, a panel device connected 
to the CPU Modbus port can communicate with the controller to which it is 
connected, as well as log into any nodes on the Modbus Plus network.
ASCII Comm Port Parameters
Baud 2,400
Parity Even
Data Bits 7
Stop Bits 1
Device Address Rear panel rotary switch setting
RTU Comm Port Parameters
Baud 9,600
Parity Even
Data Bits 8
Stop Bits 1
Device Address Rear panel rotary switch setting
ASCII
RTU
memnot used
off
mem
prt