Hardware reference guide
CPU Modules
35013379 02 October 2007 197
Rear Panel 
Switches
Two rotary switches (refer to the following illustration and table) are located on the 
rear panel of the CPU. They are used for setting Modbus Plus node and Modbus 
port addresses.
SW1 (the top switch) sets the upper digit (tens) of the address; SW2 (the bottom 
switch) sets the lower digit (ones) of the address. The illustration below shows the 
correct setting for an example address of 11.
The following figure shows SW1 and SW2. 
The following table shows the SW1 and SW2 address settings.
Modbus Port 
Modem Support
Modbus Port 1 has full modem interfacing ability. Modbus Port 2 RTS/CTS 
connections function properly for normal non-modem communications but do not 
support modems.
Note: The highest address that may be set with these switches is 64.
Node Address SW1 SW2
1 ... 9 0 1 ... 9
10 ... 19 1 0 ... 9
20 ... 29 2 0 ... 9
30 ... 39 3 0 ... 9
40 ... 49 4 0 ... 9
50 ... 59 5 0 ... 9
60 ... 64 6 0 ... 4
Note: If "0" or an address greater than 64 is selected, the Modbus + LED will be 
"on" steady, to indicate the selection of an invalid address.
1
3
0
9
2
6
4
5
8
7
1
3
0
9
2
6
4
5
8
7
SW1 (TOP)
SW2 (BOTTOM)
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com










