Hardware reference guide
Intelligent/Special Purpose
360
35013379 02 October 2007
Response to 
Read Rate 
Sample 
Command
The following table shows the responses to the read rate sample command. 
Rate Sample 
Mode Caution
If a version 02.00 or higher module replaces a module which has a version number 
less than 02.00 in a Rate Sample mode application, extra software configuration 
may be required. 
Rate Sample mode is set using Command 1, CONFIGURE (01XX), 4X+1 register, 
bit 13 = 1 (see the description of Command 1 in this section).
The following figure shows the module’s label. 
In modules prior to V02.00, when Rate Sample mode was selected, input was 
always handled as if it were generated by a pulse encoder. For example, 60 count 
per revolution encoders, either pulse or quadrature types, would give a rate of 60 for 
a one-second revolution when the interval was set for one second.
Register Value Description
300001 0400 Command echo
300002 XXXX Counter 1 Input rate low word
300003 XXXX Counter 1 Input rate high word: this register is a multiplier. As an 
example: 30002 has a value of 324 and 30003 a value of 3.The 
total count is (65,536 x 3) + 324 = 196,932
300004 0000 Counter 2 is disabled
300005 0000 Counter 2 is disabled
300006 0X00 X is the field power indicator
Note: To verify the version of the module, reference the indicated label found on 
the top front of the module.
140
EHC 202 00
HI SPEED CTR
High Speed CTR 2CH
500KHz   02.00
Note: Modules labeled with PV 
and SV designations are newer 
than 02.00 marked models
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com