Hardware reference guide
Intrinsically Safe Modules
432
35013379 02 October 2007
RTD/Resistance 
Module 
Specifications
Specifications for the Quantum140AII33000 module configured as an Intrinsically 
Safe RTD/Resistance input module are as follows.
RTD/Resistance Module Specifications
Number of Channels 8
LEDs Active (Green)
F (Red)
1 - 8 (Red) Indicated channel is out of range - includes 
broken wire and short circuit conditions.
RTD Types (Configurable) 
Platinum (American and European) 
– PT100, PT200, PT500, PT1000 
-200° C to +850° C
Nickel – N100, N200, N500, N1000  -60° C to +180° C
Measurement Current 
PT100, PT200, N100, N200
PT500, PT1000, N500, N1000
2.5 mA
0.5 mA
Input Impedance  >10 MΩ 
Linearity  +/- 0.003% of full scale (0 ... 60° C) 
Resolution 12 bits plus sign (0.1° C)
Absolute Accuracy  +/- 0.5 °C (25° C)
+/- 0.9 °C (0 .. 60° C)
Accuracy Error @ 25°C  Typical: +/- 0.05% of full scale Maximum: +/- 0.1% 
of full scale 
 Input Filter > 100 dB @ 50/60 Hz 
Isolation 
Channel to Channel 
Channel to Bus 
None 
1780 Vac @ 47-63 Hz or 2500 Vdc for 1 min. 
Update Time (All Channels) 
3-wire
2 or 4-wire
1.35 sec.
750 m sec. 
Bus Current Required  400 mA 
Power Dissipation  2 W 
External Power  Not required for this module 
Fault Detection Out of range or broken wire conditions 
Hot Swap Not allowed per intrinsic safety standards 
Fusing  Internal-not user accessible 
Programming Software Modsoft Ver. 2.61 or higher 