Hardware reference guide
Intrinsically Safe Modules
434
35013379 02 October 2007
Field Wiring Field wiring to the module shall consist of separate shielded twisted pair wires. The 
acceptable field wire gauge shall be AWG 20 to AWG 12. In a 2-wire field 
configuration, the maximum field wire length is a function of the required accuracy. 
Wiring between the module and the intrinsically safe field device should follow 
intrinsically safe wiring practices to avoid the transfer of unsafe levels of energy to 
the hazardous area.
RTD/Resistance 
Input Wiring
When the Universal Input module is configured as a RTD/Resistance Input module, 
the maximum wire length (distance to a sensor) for a 3 or 4-wire configuration is 200 
meters.
Thermocouple/
Millivolt Input 
Wiring
When the module is configured as a Thermocouple/Millivolt Input module, the sum 
of thermocouple source or voltage source impedance and wire resistance should not 
exceed 200 ohms for rated accuracy.
Fixed Wiring 
System
The Quantum140AII33000 Intrinsically Safe Analog Input module is designed with 
a fixed wiring system where the field connections are made to a 40-pin, fixed 
position, blue terminal strip which is plugged into the module.
Isolation 
Channel to Channel 
Channel to Bus 
None 
1780 Vac @ 47-63 Hz or 2500 Vdc for 1 min. 
Update Time  1 sec. (all channels) 
Fault Detection  Out of range or broken wire
Bus Current Required  400 mA 
Power Dissipation  2 W 
External Power  Not required for this module 
Hot Swap  Not allowed per intrinsic safety standards 
Fusing  Internal - not user accessible 
Programming Software  Modsoft Ver. 2.6 or higher or Concept Ver. 2.2 or higher 
Notes: 
1. Absolute accuracy includes all errors from the internal CJC, TC curvature, offset plus gain, for module temperature 
of 0 ... 60° C. User-supplied TC errors not included. 
2. For type J and K, add 1.5° C inaccuracy for temperatures below -100° C.
3. Type B cannot be used below 130° C.
4. All TC ranges have an open TC detect and upscale output. This results in a reading 7FFFh or 32767 decimal when 
an open TC is detected. 
Thermocouple/Millivolt Module Specifications