140AII33010 Intrinsically Safe Current Input Module
Overview The Quantum 140AII33010 Intrinsically Safe Current Input module interfaces with 
eight intrinsically safe analog inputs which are software-configurable. The module 
accepts 0 ... 20 mA, 0 ... 25 mA, and 4 ... 20 mA inputs. The module allows any mix 
and match of current input ranges that can be configured by the software. The 
module provides power to intrinsically safe transmitters located in hazardous areas. 
Specifications Specifications for the Quantum 140AII33010 Intrinsically Safe Current Input module 
are as follows.
Specifications
Number of Channels  8
LEDs Active (Green)
F (Red)
1 ... 8 (Red), 1 per channel
Note: This module produces a fault signal F if any one 
channel detects a broken wire condition or an out-of-
range condition (4 ... 20 mA only). 
Current Input 
Linear Measuring Range  4 ... 20 mA
0 ... 20 mA
0 ... 25 mA
Absolute Maximum Input  25 mA internally limited
Input Impedance  100 Ω +/- 0.1% between V+ and signal terminals 
Resolution  4 ... 20 mA, 0 to 4,095 counts
4 ... 20 mA0 to 16,000 counts 
0 ... 20 mA, 0 to 20,000 counts
0 ... 25 mA, 0 to 25,000 counts
Available Voltage Terminals V+, V-, :~ 14.5 Vdc at 25 mA 
Terminals V+, Signal :~ 13.6 Vdc at 20 mA
Accuracy Error @ 25°C  Typical: +/- 0.05% of full scale 
Maximum: +/- 0.1% of full scale 
Linearity  + 0.003% of full scale
Accuracy Drift w/ Temperature  Typical: +/- 0.0025% of full scale /°C
Maximum: +/- 0.005% of full scale /°C
Common Mode Rejection > 100 dB @ 50/60 Hz 
Input Filter  Single pole low pass, -3 dB cutoff @ 15 Hz, +/- 20% 
Isolation
Channel to Channel None 
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com