Hardware reference guide
Intrinsically Safe Modules
454
35013379 02 October 2007
Field Wiring  Field wiring to the module should consist of separate shielded, twisted pair wires. 
The acceptable field wire gauge should be AWG 30 to AWG 18. Wiring between the 
module and the intrinsically safe field device should follow intrinsically safe wiring 
practices to avoid the transfer of unsafe levels of energy to the hazardous area.
Fixed Wiring 
System
The Quantum140AIO33000 Intrinsically Safe Analog Output module is designed 
with a fixed wiring system where the field connections are made to a 40-pin, fixed 
position, blue terminal strip which is plugged into the module.
Terminal Strip 
Color and Keying 
Assignment
The module’s 140XTS33200 field wiring terminal strip is color-coded blue to identify 
it as an intrinsically safe connector.
The terminal strip is keyed to prevent the wrong connector from being applied to the 
module. The keying assignment is given below.
Module Class  Module Part Number  Module Coding  Terminal Strip Coding 
Intrinsically Safe  140AIO33000  CEF  ABD 
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com










