Hardware reference guide
Intrinsically Safe Modules
462
35013379 02 October 2007
140DII33000 Intrinsically Safe Discrete Input Module
Overview The Quantum 140DII33000 Intrinsically Safe Discrete Input module provides safe 
power to dry contact closures e.g., push buttons, selector switches, float switches, 
flow switches, limit switches, etc., in a hazardous area, and receives the proportional 
current to indicate an on/off state. The received current is converted into digital 
signals that is transferred to the PLC. 
Specifications The following table provides specifications for the DII33000 Intrinsically Safe 
Discrete Input module.
Specifications
Number of Input Points  8 
LEDs Active (Green)
1 ... 8 (Green) – Indicates point status 
Operating Voltages and Currents 
No load voltage (between 
input + and input -)
8 Vdc 
Short circuit current  8 mA
Switching point 1.2 mA ... 2.1 mA
Switching hysteresis  0.2 mA 
Switching Frequency 100 Hz maximum 
Response
OFF-ON 1 ms
ON-OFF 1 ms 
Isolation 
Channel to Channel None 
Channel to Bus  1780 Vac, 47-63 Hz or 2500 Vdc for 1 min. 
Internal Resistance  2.5 KΩ
Input Protection  Resistor limited
Fault Detection None 
Bus Current Required 400 mA
Power Dissipation 2 W
External Power Not required 
Hot Swap Not allowed per intrinsic safety standards
Fusing Internal - not user accessible 
Programming Software Modsoft Ver. 2.61 or higher 